Greenheck Fanメーカー240XP-CUbの使用説明書/サービス説明書
ページ先へ移動 of 24
Fan Selection Application-Based Selection Performance Theory.
This book is designed to help you select the fan that will best fit the application for which it is intended. With the large number of differ ent fan types and sizes available it's necessary to know which fan model does the best job in certain applications and then be able to select the most economical fan size for the job.
T ABLE OF CONTENTS SECTION 1 INTRODUCTION TO F AN SELECTION T erms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 Model Designation . . . . . . . . . . . . . . . . . . . . . .4 Reading Performance Charts . . . . . . . . . . . . . .5 Matching a Specification .
This is the first and most basic of this manual’s three sections, all of which are designed to enable you to select the right fan for the job. Look at this first section as a “user’s manual” for Greenheck literature.
Reading Performance Charts Assume that a job requires a belt drive roof exhauster to move 1000 cfm against 0.25 in. Ps. Refer to the performance model at the bottom of this page. Start at the top of the chart with the 0.25 in. Ps column. (All numbers in this column correspond to .
Model Common Accessories Roof Curb G & GB Backdraft Damper Roof Curb CUBE Grease Trap SB Wall Mount Housing or Wall Mount Collar Model Common Accessories Speed Control SP & CSP Discharge Vents.
Model RSF and BCF Selection The RSF and BCF selection charts are different from all other selection charts. For these models, the cfm values are at the left side of the chart in a single column and the rpms are in the performance boxes. It is just the opposite for other models.
Cross Refer ence Chart (Models in italics refer to older models) Direct Drive 120 W 1 0 D Direct Drive rpm x 100 Model ACW Wheel Size Belt Drive 150 V 6 B Belt Drive 3/4 hp Model VCR Wheel Size = 15 in. Direct Drive PW 135 A 8 860 rpm 1/20 hp Wheel Size =13.
F AN SELECTION BASED ON F AN APPLICA TION Direct Drive vs Belt Drive Direct drive fans are economical for low volume (2000 cfm or less) and low static pressure (0.50 in. or less). They require little maintenance and most direct drive motors can be used with a speed control to adjust the cfm.
Recommended Exhaust Fans Commer cial Kitchen V entilation Model CUBE Model USGF Model CWB Model SWB Belt Drive Belt Drive Belt Drive Belt Drive Upblast Roof Exhaust Upblast Roof Exhaust Sidewall Exhaust Utility Blower 300-30,000 cfm 300-7,000 cfm 300-12,000 cfm 500-30,000 cfm Up to 5.
Commer cial Kitchen V entilation Fan Sizing Exhaust When not specified by local codes, the following guidelines may be used to determine the minimum kitchen hood exhaust cfm. Some local codes require 100 cfm/ft. 2 of hood area for wall style hoods. Supply Recommended supply airflow is 90% of exhaust cfm.
General Commer cial V entilation Models SQ and BSQ are versatile fans that can be used for exhaust or supply and can be mounted in any position. Two removable side panels provide access for service. Model G Direct Drive Roof Exhaust 90-3,200 cfm Up to 1.
T ypical Commer cial V entilation Installations 13.
General Industrial V entilation Typical Applications Propeller fans are ideal for ventilating high air volumes at low static pressures (0.50 in. or less). Industrial applications often include factories and warehouses. A variety of fan models offer flexibility for roof or wall mount as well as exhaust or supply.
High Static Pr essure V entilation Typical Applications Models SWB and BSQ are general, all-purpose fans that are capable of moving high air volumes against high static pressures (up to 5.0 in wg). High static pressures are generated by long or complex duct systems, especially when capture hoods are present.
Area Min./Chg. Area Min./Chg. Area Min./Chg. Assembly Hall 3-1 0 Dance Hall 3-7 Machine Shop 3-6 Attic 2-4 Dining Room 4-8 Mill 3-8 Auditorium 3-10 Dry Cleaner 2-5 Office 2-8 Bakery 2-3 Engine Room 1-.
Determining Static Pressur e (Ps) The pressures generated by fans in ductwork are very small. Yet, accurately estimating the static pressure is critical to proper fan selection. Fan static pressure is measured in inches of water gauge. One pound per square inch is equivalent to 27.
GB-200-5 (512-770) GB-180-7 (764-1055) GB-180-5 (700-940) 0.000 0.125 0.250 0.375 0.500 0.625 0.750 0.875 1.000 Sone Bhp Sone Bhp Sone Bhp Sone Bhp Sone Bhp Sone Bhp Sone Bhp Sone Bhp Sone Bhp STATIC PRESSURE / CAPACITY Preliminary Selections At this point we know the model, cfm and Ps.
Motor Horsepower The motor horsepower for direct drive fans is always sized by Greenheck and does not require further consideration. For belt drive models, the catalog identifies which horsepower is recommended. However, there are times when it is wise to bump the horsepower one size.
Installation To ensure proper fan performance as cataloged, caution must be exercised in fan placement and connection to the ventilation system. Obstructions, transitions, poorly designed elbows, improperly selected dampers, etc., can cause reduced performance, excessive noise, and increased mechanical stressing.
F AN PERFORMANCE System Dynamics For a given flow rate (cfm), an air distribution system produces a resistance to airflow (Ps). This resistance is the sum of all static pressure losses as the air flows through the system. Resistance producing elements include ductwork, dampers, grills, coils, etc.
Combining Fan and System Dynamics The previous two sections introduced fan curves and system resistance curves. This section will show how these relate to each other to provide an understanding of the way the fan-system operates as a complete entity. Remember that a fan curve is the series of points at which the fan can operate at a constant rpm.
Adjusting Fan Performance There is a direct relationship between cfm and rpm within a system. Doubling the fan rpm will double the cfm delivered. Sample problem: The figure on page 21 showed a fan curve at 700 rpm which had an operating point of 1000 cfm at 0.
In a steady-state system, as the fan rpm changes, cfm, Ps and BHp (horsepower) also change. The equations below, known better as fan laws, show the relationship between these performance parameters.
デバイスGreenheck Fan 240XP-CUbの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Greenheck Fan 240XP-CUbをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはGreenheck Fan 240XP-CUbの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Greenheck Fan 240XP-CUbの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Greenheck Fan 240XP-CUbで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Greenheck Fan 240XP-CUbを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はGreenheck Fan 240XP-CUbの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Greenheck Fan 240XP-CUbに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちGreenheck Fan 240XP-CUbデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。