Bosch AppliancesメーカーD296/D297の使用説明書/サービス説明書
ページ先へ移動 of 12
D296/D297 Series Projected Beam Smoke Detectors Application Guide.
2 D296/D297 Series Application Guide Contents 1.0 Scope --------------------------------------------------------------- 3 2. 0 Glossary of T erms ------------------------------------------------ 3 3.0 Introduction -------------------------------------------------------- 4 4.
D296/D297 Series Application Guide 3 1. 0 Scope This application guide is intended to assist in determining the best locations and applications of the D296 Series Long Range Beam Smoke Detectors.
4 D296/D297 Series Application Guide 3.0 Introduction Why should I use Beam Smoke Detectors and where should I use them? • Where there are high ceilings such as in atriums and aircraft hangers. Because the detectors mount on the walls easier access is achieved.
D296/D297 Series Application Guide 5 4.0 Specifications Power: D296 18 to 32 VDC Receiver: 45 mA @ 24 VDC, Transmitter: 20 mA @ 24 VDC D297 10.2 to 18 VDC Receiver: 50 mA @ 12 VDC, Transmitter: 20 mA @ 12 VDC Alarm Output: One Normally Open (NO) Contact rated 1 A, 60 VDC maximum for resistive loads.
6 D296/D297 Series Application Guide 6.0 Applications 6. 1 Coverage The D296 Series Projected Beam Smoke Detectors are primarily used to provide for smoke detection in large areas with open or high ceilings. The D296 Series Detectors have a coverage range of up to 350 ft (106 m).
D296/D297 Series Application Guide 7 6. 3 Environmental Considerations 6.3.1 Outdoor Beam smoke detectors are inappropriate for outdoor applications. Environmental conditions such as temperature extremes, bright sunlight, rain, freezing rain, snow , sleet, fog and dew can interfere with the proper operation of the detector .
8 D296/D297 Series Application Guide 6. 5 Location and Spacing NFP A 72-2002 ® , 5.7.3.4.1 states: “Projected beam-type smoke detectors shall be located in accordance with the manufacturer ’s documented instructions.
D296/D297 Series Application Guide 9 If the ceiling beams (joists) exceed 1 ft (.03 m), the spacing between the beams exceeds 8 ft (2.4 m) or the ceiling height exceeds 12 ft, the detectors must be located in every ceiling beam pocket.
1 0 D296/D297 Series Application Guide 6.6.3 Peaked Ceilings Peaked structures follow the same guidelines as sloped ceilings with one exception: When calculating the location of the detectors, the first detector is within 3 ft (1 m) of the peak, measured horizontally .
D296/D297 Series Application Guide 11 7.0 Worksheet Be sure to include site features such as: • Support Beams (include direction) • Support posts • Peaks • Lights • Air handling units (HV AC) • Shelving • Anything suspended from the ceiling that might interfere with the beam • Directions (North, South, etc.
© 2004 Bosch D296/D297 Series Projected Beam Smoke Detectors 130 Perinton Parkway , Fairport, New Y ork, USA 14450-9199 Application Guide Customer Service: (800) 289-0096; T echnical Support: (888) 8.
デバイスBosch Appliances D296/D297の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Bosch Appliances D296/D297をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはBosch Appliances D296/D297の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Bosch Appliances D296/D297の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Bosch Appliances D296/D297で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Bosch Appliances D296/D297を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はBosch Appliances D296/D297の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Bosch Appliances D296/D297に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちBosch Appliances D296/D297デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。