CarrierメーカーWEATHERMAKER 8000 58ZAVの使用説明書/サービス説明書
ページ先へ移動 of 24
WeatherMaker 8000™ 58ZAV Downflow/Horizontal Induced-Combustion Furnaces Installation, Start-Up, and Operating Instructions Sizes 050—135, Series 151 and 161 NOTE: Read the entire instruction manual before starting the installation. This symbol → indicates a change since the last issue.
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS PROCEDURE Electrostatic discharge can affect electronic components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will pre- vent electrostatic discharges from personnel and hand tools which are held during the procedure.
INTRODUCTION The model 58ZAV Series 151 and 161 Furnaces are available in sizes 46,000 through 135,000 Btuh input capacities. The design of the downflow/horizontal gas-fired furnace is CSA (A.G.A. and C.G.A.) certified for natural and propane gases and for installation on noncombustible flooring.
Improper installation, adjustment, alteration, service, mainte- nance, or use can cause carbon monoxide poisoning, explo- sion, fire, electrical shock, or other conditions which may cause personal injury, loss of life, or property damage.
The operation of exhaust fans, kitchen ventilation fans, clothes dryers, or fireplaces could create a NEGATIVE PRESSURE CONDITION at the furnace. Make-up air MUST be provided for the ventilation devices, in addition to that required by the furnace. All fuel-burning equipment must be supplied with air for combus- tion of the fuel.
Step 3—Supply Air Connections DOWNFLOW FURNACES Connect supply-air duct to supply-air opening on furnace. The supply-air duct attachment must ONLY be connected to furnace supply/outlet or air conditioning coil casing (when used), when installed on non-combustible material.
Do not install furnace on its back. Safety control operation will be adversely affected. Never connect return-air ducts to back of furnace. Failure to follow this warning could result in fire, personal injury, or death. Step 5—Downflow Installation NOTE: This furnace is approved for use on combustible materials or wood flooring.
Fig. 6—Furnace, Plenum, and Subbase Installed on a Combustible Floor A96285 DOWNFL OW SUBBASE SHEET MET AL PLENUM FL OOR OPENING FURNACE (OR COIL CASING WHEN USED) COMBUSTIBLE FL OORING Fig.
If coil assembly CD5, CK5, or Coil Box KCAKC is used, install as shown in Fig. 7. Step 6—Horizontal Attic Installation Do not install the furnace on its back; safety control operation will be adversely affected. Never connect return-air ducts to the sides or back of the furnace.
Step 10—Electrical Connections 115-V WIRING Refer to the unit rating plate or Table 6 for equipment electrical requirements. The control system requires an earth ground for proper operation. Do not connect aluminum wire between disconnect switch and furnace.
The cabinet MUST have an uninterrupted or unbroken ground according to NEC ANSI/NFPA 70-1999 and Canadian Elec- trical Code CSA C22.1 or local codes to minimize personal injury if an electrical fault should occur.
Two quick-connect terminals marked EAC-1 and EAC-2 are provided for EAC connection. (See Fig. 14.) These terminals are energized with 115-v, (1.5-amp maximum) during blower motor operation. 2. Humidifier (HUM) A quick-connect terminal (HUM) and screw terminal (C OM ) are provided for 24-v humidifier connection.
Fig. 15—Heating and Cooling Application Wiring Diagram A98521 115-V FIELD- SUPPLIED DISCONNECT AUXILIARY J-BOX 24-V TERMINAL BLOCK THREE-WIRE HEATING-ONLY FIVE WIRE NOTE 1 NOTE .
→ Fig. 16—Furnace Wiring Diagram A00304 PCB BLOWER OFF DELAY SELECTION CHART 90 SEC 135 SEC 180 SEC 225 SEC GVR H I/L O RELA Y SEC-1 SEC-2 PL1 3 2 1 6 5 4 9 87 LED TEST/TWIN BLOWER OFF DELAY G R Y.
When the thermostat "calls for cooling," R-G and R-Y circuits close. The R-Y circuit starts the outdoor condensing unit and combined R-Y and R-G circuits start the furnace blower motor on cooling speed. The EAC-1 terminal is energized with 115v whenever the blower is operating on cooling speed.
→ Table 7—Model 58ZAV Orifice Size† and Manifold Pressure for Correct Input (Tabulated Data Based on 23,000 BTUH Per Burner, Derated 4 Percent per 1000 Ft Above Sea Level)* ALTITUDE RANGE (FT) AVG GAS HEAT VALUE AT ALTITUDE (BTU/CU FT) SPECIFIC GRAVITY OF NATURAL GAS 0.
→ Table 7—Model 58ZAV Orifice Size† and Manifold Pressure for Correct Input (Continued) (Tabulated Data Based on 23,000 BTUH Per Burner, Derated 4 percent per 1000 Ft Above Sea Level)* ALTITUDE RANGE (FT) AVG GAS HEAT VALUE AT ALTITUDE (BTU/CU FT) SPECIFIC GRAVITY OF NATURAL GAS 0.
b. Adjust manifold pressure to obtain input rate. (1.) Remove regulator adjustment seal cap. (See Fig. 18.) (2.) Turn adjusting screw, counterclockwise (out) to de- crease manifold pressure or clockwise (in) to increase manifold pressure. NOTE: This furnace has been approved for a manifold pressure of 3.
d. Refer to Table 9 for cu ft of gas per hr. e. Multiply gas rate (cu ft/hr) X heating value (Btu/cu ft) using natural gas heating value from local gas utility/supplier.
terminal. (See Fig. 14.) Select desired blower motor speed lead from 1 of the other terminals and relocate it to HEAT terminal. See Table 10 for lead color identification. Recon- nect original lead on SPARE terminal. Follow this same procedure for proper selection of COOL speed selection.
d. Set thermostat to "call for heat" and wait 1 minute. When pressure switch is functioning properly, hot surface igniter should NOT glow and control diagnostic light flashes a status 31. If hot surface igniter glows when inducer motor is disconnected, shut down furnace immediately.
CHECKLIST—INSTALLATION LOAD CALCULATION ____________ Heating Load (Btuh) ____________ Cooling Load (Btuh) ____________ Furnace Model Selection AIR FOR COMBUSTION AND VENTILATION ____________ Unconfi.
23.
A94328 SER VICE TRAINING P acka g ed Service T raining programs are an e xcellent wa y to increase y our knowledge of the equipment discussed in this man ual, including: • Unit F amiliarization • .
デバイスCarrier WEATHERMAKER 8000 58ZAVの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Carrier WEATHERMAKER 8000 58ZAVをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはCarrier WEATHERMAKER 8000 58ZAVの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Carrier WEATHERMAKER 8000 58ZAVの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Carrier WEATHERMAKER 8000 58ZAVで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Carrier WEATHERMAKER 8000 58ZAVを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はCarrier WEATHERMAKER 8000 58ZAVの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Carrier WEATHERMAKER 8000 58ZAVに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちCarrier WEATHERMAKER 8000 58ZAVデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。