ZONEKIT2ZCAR WeatherMaker® Two-Zone Installation and Start-Up Instructions NOTE: Read the entire instruction manual before starting the installation. This symbol → indicates a change since the last issue. TABLE OF CONTENTS PAGE Safety Considerations .
Step 2—Wiring To prevent personal injury or possible equipment damage, disconnect the power supply before routing wire. All wiring must comply with local, state, and national codes.
2. Properly seal joint using duct tape, mastic, or other approved method. Do not allow mastic to come in contact with actuator. 3. Insulate damper using 1-1/2-in. to 2-in. insulation. (Check your local codes.) (See Fig. 7.) NOTE: All zone dampers and ductwork must be properly sup- ported according to local codes or SMACNA standards.
Step 5—Install Barometric Bypass Damper NOTE: The barometric bypass damper is a critical part of the WeatherMaker Two-Zone System for control of minimum airflow and noise reduction. It is recommended that the bypass be installed. The bypass should be installed according to local codes and SMACNA standards.
In automatic changeover, the zoning system works on a first come first serve basis. If 1 zone is calling for heating and the other for cooling, the zone which sent its demand to the I/O center first will operate the equipment in that mode until that zone is satisfied.
Fig. 12—WeatherMaker Two-Zone Circuit Board with Standard Thermostat Wiring A97293 3 Thermostat Zone 2 Y 2 Y 1 R W 1 W 2 C G Thermostat Zone 1 Y 2 Y 1 R W 1 W 2 C Sensors HP Duct Equipment R c.
NOTE: An HP temperature sensor must be used with a heat pump application using electric strip heat. This is necessary in case the DTO is set to the Off position. Timeguard The WeatherMaker Two-Zone provides equipment protection with an internal 5-minute timeguard delay.
timer will start counting down 15, 14, 13...0 minutes. Once the timer expires the control will allow a new mode to restart the equipment. The internal time, as well as the cooling 5-minute timeguard can be cleared by using the comprotec override feature.
TROUBLESHOOTING This section contains information to assist you in troubleshooting problems and errors associated with the WeatherMaker Two-Zone system. See Table 2. Step 1—System Diagram, Jumpers, and Switches NOTE: For correct control board operation, it must have either a sensor attached or a 10k resistor in place at the duct and HP inputs.
I Red LED—Displays ON when fan is energized. J Red LED—Displays ON when first-stage cooling is energized. K Red LED—Displays ON when second-stage cooling is energized. L Red LED—Displays ON when reversing valve is ener- gized. M Red LED—Displays ON when first-stage heat is energized.
Table 3 shows a temperature/ohm/voltage relationship to help aid in troubleshooting the WeatherMaker Two-Zone System. This table will evaluate both the Duct/HP temperature sensor operation.
→ Fig. 17—Typical Fan Coil With Single-Speed Air Conditioner A97298 SINGLE-SPEED AIR CONDITIONER TYPICAL FAN COIL C Y G W2 W3 C R Y/Y2 O L E RH G W2 W1 Y1 Y2 O B RC TWO-ZONE SYSTEM See notes 1 and 3 * * * * * Y1 * * → Fig.
→ Fig. 21—Typical Fan Coil With 2-Speed Air Conditioner A97302 2-SPEED AIR CONDITIONER TYPICAL FAN COIL R G R C W2 Y/Y2 E W3 L O Y1 C Y2 Y1 RH G W2 W1 Y1 Y2 O B RC TWO-ZONE SYSTEM See notes 1, 2, and 3 * * * * * → Fig.
→ Fig. 23—Single-Stage Furnace With Single-Speed Heat Pump A97304 SINGLE-STAGE FURNACE TWO-ZONE SYSTEM INTERFACE CONTROL R GF RF WF R GT E HP O HP OT Y HP C W2 Y O RH G W2 .
→ Fig. 27—Single-Stage Furnace With 2-Speed Heat Pump A97308 2-SPEED HEAT PUMP SINGLE-STAGE FURNACE R G R C W Y C Y2 W3 RH G W2 W1 Y1 Y2 O B RC TWO-ZONE SYSTEM W2 Y1 O See notes 2, 5, 6, 7, 9, 10, and 11 → Fig.
→ Fig. 29—Typical Fan Coil With 2-Speed Heat Pump A97310 RH G W2 W1 Y1 Y2 O B RC 2-SPEED HEAT PUMP TYPICAL FAN COIL C G W2 Y/Y2 R C W3 L E Y1 R W2 O W3 Y1 Y2 O TWO-ZONE SYSTEM See notes 1, 2, 3, 9, and 11 * * * * * → Fig.
デバイスCarrier ZONEKIT2ZCARの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Carrier ZONEKIT2ZCARをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはCarrier ZONEKIT2ZCARの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Carrier ZONEKIT2ZCARの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Carrier ZONEKIT2ZCARで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Carrier ZONEKIT2ZCARを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はCarrier ZONEKIT2ZCARの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Carrier ZONEKIT2ZCARに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちCarrier ZONEKIT2ZCARデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。