Manual 2100-574 Page 1 of 23 MD4000 SERIES SOLID ST A TE DUAL UNIT LEAD/LAG CONTROLLER for use with H-Series W all Mount Air Conditioners with F & G Spyder™ Economizers only INST ALLA TION INSTRUCTIONS & REpLACEMENT p ARTS LIST Manual No.: 2100-574 Supersedes: NEW File: V ol.
Manual 2100-574 Page 2 of 23 CONTENTS Economizer Failure Alarm ..................................... 16 Dirty Filter Alarm .................................................... 16 2-Compressor Run Alarm ...................................... 16 Alarm Wiring .
Manual 2100-574 Page 3 of 23 Getting Other Information and Publications These publications can help you install the air conditioner or heat pump. Y ou can usually nd these at your local library or purchase them directly from the publisher . Be sure to consult current edition of each standard.
Manual 2100-574 Page 4 of 23 shIPPInG DamaGe Upon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately , preferably in writing, requesting inspection by the carrier ’ s agent.
Manual 2100-574 Page 5 of 23 sPecIFIca tIOns/Fea tures FOr mD4000-b cOntrOller MD4000 Basic Controller •Input power: 18-32 V AC, 60/50Hz, power is supplied from A/C #1 and/or A/C #2 •Isolation cir.
Manual 2100-574 Page 6 of 23 lOca teD In the mD4000 P anel bOx Unit #1 t erminal Block R – 24V AC hot from Unit C – 24V AC common from Unit Y – Compressor Signal to Unit F – Economizer Shutdow.
Manual 2100-574 Page 7 of 23 lOW vOl t aGe FIelD WIrInG The MD4000 is powered from the air conditioners that it is controlling, 24 V AC (18-32V) low voltage only . Circuitry in the MD4000 isolates the power supplies of the two air conditioners so that no back feeds or phasing problems can occur .
Manual 2100-574 Page 8 of 23 FIre suPPressIOn cIrcuIt T o disable the MD4000 and shut down both air conditioners, terminals F1 and F2 may be used. The F1 and F2 terminals must be jumpered together for normal operation.
Manual 2100-574 Page 9 of 23 General PrOGrammInG Over vIeW mD4000 cOntrOller buttOns anD FunctIOn On/Off Button 1. Press and release the On/Off button to turn On controller, 4-character display will illuminate and Lead unit LED will light. 2. Press and release the On/Off button to turn Off controller .
Manual 2100-574 Page 10 of 23 MD4000 decides Lead unit Spyder 1 is lead Signals Spyder2 as lag. Spyder 2 is lead Signals Spyder1 as Lag DC Amp load is read and converted to building load with the equation DCA * 106.4-.2455 = BTUH Calculate Available Cooling (AC) for 1 econ Available cooling =( SP- MTD-OAT)*1.
Manual 2100-574 Page 1 1 of 23 sPecIFIca tIOns FOr OPtIOnal remOte cOmmunIca tIOn bOarD CB4000 COMMUNICA tION BOARD Note: If this communication boar d was not originally factory installed it can be eld-installed at anytime. Bar d part number is CB4000.
Manual 2100-574 Page 12 of 23 USER P AGE 1. The designated Admin person can assign up to 9 additional users and set-up as Admin, W rite or Read authority . 2. User Name and password must be assigned, each must be at least 3 characters long, and are case sensitive.
Manual 2100-574 Page 13 of 23 cOntrOller WIrInG The MD4000 can be used for controlling two (2) air conditioners with economizers. securItY (lOckInG) Fea ture The MD4000 controller can be locked such that unauthorized persons cannot make any changes to temperature set points or any other selectable parameters of the controller system.
Manual 2100-574 Page 14 of 23 FIGure 1 mD4000-b cOntrOller cOnnectIOns 1-st aGe (h**a/h**l serIes) aIr cOnDItIOners WIth (ecOnWmt) ecOnOmIzers system t ype model series mD4000-b newer ecOnWmt economiz.
Manual 2100-574 Page 15 of 23 FIGure 2 mD4000-bc cOntrOller cOnnectIOns 1-st aGe (h**a/h**l serIes) aIr cOnDItIOners WIth (ecOnWmt) ecOnOmIzers anD WIth alarm bOarD & cb4000 cOmmunIca tIOn bOarD 2 E F 2 3 E F 3 C 3 2 1 3 -3 2 -3 1 -3 NC NO CU , AND SIL VER M US T NO TE : A LL SENS OR S ARE POL AR I TY SENS ITI VE .
Manual 2100-574 Page 16 of 23 alarm WIrInG Alarm relays can be wired for NO (close on alarm) or NC (open on alarm) strategy . Alarm relays can be used individually if there are enough available building alarm points, or can be arranged into smaller groups or even a single group so that all alarm capabilities can be utilized.
Manual 2100-574 Page 17 of 23 2nD st aGe cOOlInG alarm This alarm output is available for use if desired. It is important to note that in some installations, due to A/C system sizing and internal heat load, that the secondary (lag) air conditioning unit may be called upon to assist the lead air conditioner some of the time.
Manual 2100-574 Page 18 of 23 FIGure 3 alarm bOarD cOnnectIOns FOr nOrmall Y clOseD "nc" OPen-On-alarm stra teGY IMPOR t ANt! LED display board is shipped loose to pr otect it from possible damage during installation of the wiring to main contr oller boar d and/or the alarm board.
Manual 2100-574 Page 19 of 23 FIGure 4 alarm bOarD cOnnectIOns FOr nOrmall Y OPen "nO" clOse-On-alarm stra teGY IMPOR t ANt! LED display board is shipped loose to pr otect it from possible damage during installation of the wiring to main contr oller boar d and/or the alarm board.
Manual 2100-574 Page 20 of 23 PrOGrammInG InstructIOns T o swap lead and lag unit positions, press the ADV ANCE button. T o enter the Program mode, press the PROGRAM button and release it when the message PROG appears on the display . When in Program mode, the DOWN and UP arrows are used to scroll through the programming steps.
Manual 2100-574 Page 21 of 23 Material: 10 mil HP92WP lexan Adhesive: 7952MP Premask: 4075 Colors: black, spot white, trans red, spot frosted clear trans red window adhesive die emboss die cut 11” 8.
Manual 2100-574 Page 22 of 23 FIGure 5 P arts lIst DescrIPtIOn DIaGram 20 10 8 6 18 SEXP-648 1 5 9 2 13 7 12 19 4 15 3 17 14 11.
Manual 2100-574 Page 23 of 23 Parts List Dwg. no. Part no. Description mD4000-b mD4000-bc ab3000-b cb4000 1 127-423-4 Control Box X X 2 8612-038 Controller Board X X 3 8612-021 Alarm Board B X X X 4 8.
デバイス3D Connexion mD4000-bの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
3D Connexion mD4000-bをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこには3D Connexion mD4000-bの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。3D Connexion mD4000-bの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。3D Connexion mD4000-bで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
3D Connexion mD4000-bを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又は3D Connexion mD4000-bの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、3D Connexion mD4000-bに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわち3D Connexion mD4000-bデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。