Dellメーカー1000Wの使用説明書/サービス説明書
ページ先へ移動 of 73
Dell t Line-Interactive Rack UPS 1000W, 1920/1500W, and 2700/2300W User's Guide H919N, J718N, K792N, H928N, K802N, H945N, J727N J735N, K811N w w w .
Notes and Warnings NOTE: A NOTE indicates important information that helps you make better use of your software. DANGER: A DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
3 Table of Contents | Table of Contents 1 Introduction Finding Information 8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Safety Warnings 3 Installation Inspecting the Equipment 12 . . . . . . . . . .
4 | Table of Contents Display Functions 40 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Startup Screen 40 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Screen Locked 41 .
5 Table of Contents | 6 UPS Maintenance UPS and Battery Care 60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Transporting the UPS 61 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 | Introduction Introduction The Dell t Line-Interactive Rack uninterruptible power system (UPS) protects your sensitive electronic equipment from basic power problems such as power failures, power sags, power surges, brownouts, and line noise. Power outages can occur when you least expect them and power quality can be erratic.
7 Introduction | Providing outstanding performance and reliability, the UPS's unique benefits include: S Buck and Boost voltage regulation that ensures regulated voltage to your load by correcting voltage fluctuations. S Start‐on‐battery capability for powering up the UPS even if utility power is not available.
8 | Introduction Finding Information CAUTION: The Safety, Environmental, and Regulatory Information document provides important safety and regulatory information.
9 Safety Warnings | Safety Warnings CAUTION: Before performing the procedures in this document, read and follow the safety instructions and important regulatory information in your Safety, Environmental, and Regulatory Information document.
10 | Safety Warnings S Unpacking the cabinet in a low-temperature environment may cause condensation to occur in and on the cabinet. Do not install the cabinet until the inside and outside of the cabinet are absolutely dry (hazard of electric shock).
11 Safety Warnings | WARNING: Additional instructions for Rack-Mounted Systems S Your rack kit has been approved only for the rack cabinet provided. It is your responsibility to ensure that installation of the equipment into any other rack complies with all applicable standards.
12 | Installation Installation This chapter explains: S Equipment inspection S Unpacking the cabinet S UPS rear panels S UPS setup and installation, including the External Battery Module (EBM) S Remot.
13 Installation | Unpacking the Cabinet CAUTION: Unpacking the cabinet in a low-temperature environment may cause condensation to occur in and on the cabinet. Do not install the cabinet until the inside and outside of the cabinet are absolutely dry (hazard of electric shock).
14 | Installation 2 With one person on each side, carefully lift the cabinet out of the outer carton using the handles on the cardboard and set it on a flat, stable surface (see Figure 3). Place the cabinet in a protected area that has adequate airflow and is free of humidity, flammable gas, and corrosion.
15 Installation | Identifying the UPS Rear Panels This section shows the rear panels of the Dell Line-Interactive Rack models. IN P U T 10 0 − 1 2 0V~ Four 5‐15 Receptacles (Load Segment 1) UPS Communication Bay IEC-C14 Input Connector USB Port Two IEC 320-C13 Receptacles (Load Segment 2) REPO Ports RS-232 Port Ground Screw Figure 4.
16 | Installation UPS Communication Bay IEC-C20 Input Connector USB Port Two IEC 320-C13 Receptacles (Load Segment 2) REPO Ports RS-232 Port Ground Screw Six 5-15/5-20 and Two IEC 320-C19 Receptacles (Load Segment 1) EBM Connector Cover/Strain Relief Bracket Figure 6.
17 Installation | UPS Communication Bay USB Port Two IEC 320-C13 Receptacles (Load Segment 2) REPO Ports RS-232 Port Ground Screw EBM Connector Cover/Strain Relief Bracket 2m, L5-30P Input Cord One L5-20, Two 5-15/5-20, and Two IEC 320-C19 Receptacles (Load Segment 1) Output Circuit Breakers Figure 8.
18 | Installation REPO Ports IEC-C20 Input Connector Ground Screw USB Port RS-232 Port UPS Communication Bay Two IEC 320-C13 Receptacles (Load Segment 2) EBM Connector Cover/Strain Relief Bracket Six IEC 320-C13 and Two IEC 320-C19 Receptacles (Load Segment 1) Figure 10.
19 Installation | UPS Setup The Dell Line-Interactive Rack UPS can be installed in 19-inch racks and needs only 2U of valuable rack space (3U for 2700/2300W UPS models). NOTE: No tools are needed to attach the rack rails to a round- or square-hole EIA rack.
20 | Installation Unclip the right battery connector and move the connector out of the way. Pull the battery tray out using the plastic tabs and remove the battery tray (see Figure 13). Figure 13. Removing the Battery Tray 2 If installing additional UPSs, repeat Step 1 for each cabinet.
21 Installation | 5 Attach the rails to the rack: Engage the back end of the rail until it fully seats on the vertical rack flange and the hook latch locks in place (see Figure 14). Pull the rail toward the front. Push the front end of the rail until it fully seats on the vertical rack flange and the hook latch locks in place.
22 | Installation 6 Slide the cabinet into the rack (see Figure 15). Repeat for any additional cabinets. Figure 15. Installing the Cabinet 7 Secure the front of the cabinet to the rack using the four thumbscrews on the mounting brackets (see Figure 16).
23 Installation | 8 Install the UPS battery tray (see Figure 17). NOTE: A small amount of arcing may occur when connecting the batteries. This is normal and does not damage the unit or present any safety concern. 9 Connect the internal battery connector and reclip the right battery connector.
24 | Installation 12 Install the UPS front cover (see Figure 18). Figure 18. Installing the UPS Front Cover Tower Setup CAUTION: The UPS and EBM are heavy (see page 65).
25 Installation | 2 Loosen the thumbscrew on the metal battery cover, slide the cover to the right, and open (see Figure 20). Figure 20. Opening the Metal Battery Cover 3 Connect the internal battery connector.
26 | Installation 4 Rotate the control panel 90 ° counterclockwise (see Figure 22). Figure 22. Adjusting the UPS Control Panel Orientation 5 Close the metal battery cover and tighten the thumbscrew. Torque the screw to 0.7 Nm (6.2 lb in). 6 Rotate the Dell logo 90 ° counterclockwise and install the UPS front cover (see Figure 23).
27 Installation | NOTE: Dell recommends a minimum of 63.5 mm (2.5 ” ) free space behind the UPS rear panel, and a minimum of 127 mm (5 ” ) between cabinets. 7 Place the cabinet horizontally so that the right end of the cabinet is accessible (see Figure 24).
28 | Installation Installing the EBM NOTE: A small amount of arcing may occur when connecting an EBM to the UPS. This is normal and will not harm personnel. Insert the EBM cable into the UPS battery connector quickly and firmly. An optional EBM can be installed for 1920–2700W UPS models.
29 Installation | 2 Install the battery connector cover under the EBM cable to provide strain relief (see Figure 27). Rotate the battery connector cover on its side and position under the EBM cable. Figure 27. Installing the Battery Connection Cover 3 Plug the EBM cable into the UPS battery connector (see Figure 28).
30 | Installation Installing the UPS To install the UPS: 1 If you plan to use Dell UPS Management Software, connect your computer to the USB port using the supplied cable.
31 Installation | NOTE: For Europe, the emergency switch requirements are detailed in Harmonized document HD-384-48 S1, “Electrical Installation of the Buildings, Part 4: Protection for Safety, Chapter 46: Isolation and Switching.” REPO Connections Wire Function Terminal Wire Size Rating Suggested Wire Size REPO L1 4–0.
32 | Installation NOTE: A separate contact must simultaneously cause UPS input AC power to be removed. 5 Connect the switch or circuit to the REPO connector on the UPS rear panel using insulated 0.
33 Installation | The power cord current ratings are listed in Table 2. Table 2. Power Cord Ratings Dell UPS Model and Voltage Power Cord Rating Country Supplied Cord Set 1000W 100V JIS C8303 to C13 1.
34 | Installation Table 2. Power Cord Ratings (continued) Dell UPS Model and Voltage Supplied Cord Set Country Rating Power Cord 1920W 230V C13 to C14 Jumper 10A China/Korea/Australia Yes C13 to C14 J.
35 Installation | Table 2. Power Cord Ratings (continued) Dell UPS Model and Voltage Supplied Cord Set Country Rating Power Cord 2700W 230V CEE 7/7 Schuko to C19 16A Europe (Schuko) Yes BS 1363 to C19 13A United Kingdom (New) Yes GB2009.
36 | Installation 10 To change other factory-set defaults, see “Operation” on page 37. 11 If you installed an optional REPO, test the REPO function: Activate the external REPO switch. Verify the status change on the UPS display. Deactivate the external REPO switch and restart the UPS.
37 Operation | Operation This chapter contains information on how to use the UPS, including: S UPS startup and shutdown S Control panel and display functions S Retrieving the Event Log S Behavior on overload S Configuring load segments, battery settings, and automatic restart UPS Startup and Shutdown NOTE: The button controls only the UPS output.
38 | Operation Starting the UPS on Battery NOTE: Before using this feature, the UPS must have been powered by utility power with output enabled at least once. NOTE: Utility power cannot be present at startup. To start the UPS on battery: 1 Press the button on the UPS front panel until the UPS beeps.
39 Operation | Control Panel Functions The UPS has a three-button graphical LCD with dual color backlight. Standard backlight is used to light up the display with white text and a blue background. When the UPS has a critical alarm, the backlight changes the text to dark amber and the background to amber.
40 | Operation To select an option: 1 When scrolling through the settings, the present setting displays for each selection. 2 Press the button to select the option. The current setting for the option flashes when selected. 3 Use the or buttons to toggle the available options.
41 Operation | Screen Locked To lock a screen, press the button. The current view stays locked and does not automatically return to the default screen after time-out. When the screen is locked, the image of a key appears on the UPS status summary screen just to the left of the status icon.
42 | Operation Table 4. Status Summary Screens Status Summary Screen Description UPS Critical Failure The UPS is in Fault mode. The status icon and background are flashing. Battery Mode The status icon and background of the icon are flashing. An audible alarm (0.
43 Operation | Table 4. Status Summary Screens (continued) Status Summary Screen Description Normal Mode The UPS is operating in Normal mode from utility power. The UPS monitors and charges the batteries as needed and provides filtered power protection to your equipment.
44 | Operation Event Log The Event Log holds up to 50 events. You can scroll through the event screens, beginning with the most recent event. NOTE: The date format is dependent on the language selection. The first row of each event screen contains the date (MM/DD/YYYY) and time (hh:mm:ss) at which the event occurred.
45 Operation | Control Screens Table 6 describes the available control screens. Table 6. Control Screens Control Screens Description Battery Test Schedule Battery Test: yes | Cancel Battery test: no Starts a manual battery test. See “Testing Batteries” on page 64.
46 | Operation Identification The identification screens display the following UPS information: S Type and model S Part number S Serial number S UPS firmware S Network Management Card firmware NOTE: The NMC firmware screen displays only if the Network Management Card is installed.
47 Operation | Table 7. Settings (continued) Description Default Setting Available Settings Set Date and Time Set Month, Day, Year, Hours, Minutes, and Seconds Date:mm/dd/yyyy Time: hh:mm:ss NOTE: The date format is dependent on the language selection.
48 | Operation Table 7. Settings (continued) Description Default Setting Available Settings Battery Saving Mode [Disabled] [10%] [20%] [30%]...[100%] The UPS output is turned off in five minutes if the UPS is on battery and output power is below the selected level.
49 Operation | Table 7. Settings (continued) Description Default Setting Available Settings Reset Peak Consumption Watts [No] [Yes] If No, no action. If Yes, the Peak Consumption Watts value is cleared and the date and time stamp for this statistic is set to the current date and time.
50 | Operation Retrieving the Event Log To retrieve the Event Log through the display: 1 Press the button for one second to go to the main menu selection and scroll down to the Event Log menu using the button. 2 Press the button to enter the Event Log list.
51 Operation | Configuring Load Segments Load segments are sets of receptacles that can be controlled by the Dell UPS Management Software, the Dell Network Management Card, or through the LCD display, providing an orderly shutdown and startup of your equipment.
52 | Operation Configuring Automatic Start Delay You can configure the load segment to turn on automatically after the utility power returns, if it was shut down by: S The button S An external command.
53 Operation | Configuring Automatic on Battery Shutdown If set to Off (default), the load segment turns off only when commanded manually by the button, an external command, or through the display (Control > Load Segments). If set to zero seconds (0s), the load segment turns off automatically when the UPS on Battery state activates.
54 | Operation Configuring Battery Settings Configure the UPS settings for an installed EBM, including whether to run automatic battery tests and automatic restart configuration. Configuring the UPS for an EBM If the UPS is not configured for the EBM, the UPS reports less battery time remaining on the UPS front panel and to any remote software.
55 Operation | Running Automatic Battery Tests The automatic discharge test, enabled by default, runs during the transition from Float to Rest mode. After the test completes, the charge cycle restarts to completely charge the batteries and then continues to Rest mode normally.
56 | Additional UPS Features Additional UPS Features This chapter describes: S Communication ports (RS-232 and USB) S Dell Network Management Card S Dell UPS Management Software RS-232 and USB Communi.
57 Additional UPS Features | Table 9. RS-232 Communication Port Pin Assignment Pin Signal Name Function Direction from the UPS 1 Unused — 2 Tx Transmit to external device Out 3 Rx Receive from exter.
58 | Additional UPS Features Dell Network Management Card (Optional) The Dell Line-Interactive Rack UPS has one available communication bay, which supports the optional Dell Network Management Card. See Figure 33 for the location of the communication bay.
59 Additional UPS Features | Dell UPS Management Software Each Dell Line-Interactive Rack UPS ships with Dell UPS Management Software. Dell UPS Management Software provides up-to-date graphics of UPS power and system data and power flow.
60 | UPS Maintenance UPS Maintenance This chapter explains how to: S Care for the UPS and batteries S Transport the UPS S Store the UPS and batteries S Test the batteries S Update the UPS firmware UPS and Battery Care For the best preventive maintenance, keep the area around the UPS clean and dust‐free.
61 UPS Maintenance | Transporting the UPS NOTE: The internal UPS batteries MUST be disconnected before transportation. CAUTION: The following procedure should be performed or supervised by personnel knowledgeable about batteries and the required precautions.
62 | UPS Maintenance 4 Open the metal battery cover. Loosen the thumbscrew on the metal battery cover, slide the cover to the right, and open (see Figure 35). Figure 35. Opening the Metal Battery Cover 5 Disconnect the internal battery connectors (see Figure 36).
63 UPS Maintenance | 6 Close the metal battery cover. Adjust the battery connector so that the door closes properly. Push the door slightly to the right and then to left. 7 Tighten the thumbscrew. Torque the screw to 0.7 Nm (6.2 lb in). 8 Replace the UPS front cover (see Figure 37).
64 | UPS Maintenance When to Replace Batteries When the status summary screen displays the UPS fault icon with the “Service Battery” alarm and the audible alarm sounds continuously, the batteries may need replacing. Contact your service representative to order new batteries.
65 Specifications | Specifications This chapter provides the following specifications: S Model list S Dimensions and weights S Electrical input and output S Environmental and safety S Battery S UPS block diagram Table 10.
66 | Specifications Table 12. Electrical Input 100/120V Models 208V Models 230V Models Nominal Voltage 100/120V 208V 230V Voltage Range 84–150V auto-sensing 160–278V auto-sensing 160–286V auto-s.
67 Specifications | Table 14. Environmental and Safety 100/120V Models 208V Models 230V Models Operating Temperature Up to 1,500 meters: 0°C to 40°C (32°F to 104°F) Above 1,500 meters: 0°C to 35.
68 | Specifications Table 15. Battery Configuration 1000W: (3) 12V, 9 Ah internal batteries (no EBM) 1920/1500W: (6) 12V, 9 Ah internal batteries; (12) 12V, 9 Ah EBM 2700/2300W: (8) 12V, 9 Ah internal.
69 Troubleshooting | Troubleshooting The Dell Line-Interactive Rack UPS is designed for durable, automatic operation and issues alarms to alert you whenever potential operating problems occur. Usually the alarms shown by the control panel do not mean that the output power is affected.
70 | Troubleshooting Event Log Menu From the Event Log menu, you can access the last 50 events, which includes events, notices, and alarms, arranged from newest to oldest. Events are silent conditions that are recorded in the Event Log as status information, such as “Clock Set Done.
71 Troubleshooting | Table 16. Typical Alarms and Conditions (continued) Alarm or Condition Action Possible Cause Battery test did not run or was interrupted. One of the conditions listed in “Running Automatic Battery Tests” on page 55 was not present.
72 | Troubleshooting Table 16. Typical Alarms and Conditions (continued) Alarm or Condition Action Possible Cause Input AC Over Voltage (Alarm 6) Intermittent Alarm Utility voltage exceeds the maximum operating range. The UPS transfers to Battery mode if supporting load.
73 Troubleshooting | Table 16. Typical Alarms and Conditions (continued) Alarm or Condition Action Possible Cause Charger Failure (Alarm 34) Continuous Alarm A battery charger fault has been detected. The UPS turns off the charger until the next power recycle.
デバイスDell 1000Wの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Dell 1000Wをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはDell 1000Wの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Dell 1000Wの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Dell 1000Wで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Dell 1000Wを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はDell 1000Wの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Dell 1000Wに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちDell 1000Wデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。