45282 GTX-I Natural Gas or Propane Freestanding Direct Vent Gas Stove Installation and Operating Instructions WARNING: If the information in this manual is not followed exactly, a fire or explo sion may result causing property damage, personal injury, or loss of life.
2 Table of content 1.0 INTRODUCTION .............................................................................................................. 3 1.1 Specifications ...................................................................................
3 1.0 INTRODUCTION 1.1 Specifications TABLE 1 ITEM NATURAL GAS (NG) PROPANE (LPG) INPUT: Hi 32,500 Btu/hr (9.5 kW) 27,000 Btu/hr (7.9 kW) INPUT: Lo 22,500 Btu/hr (6.6 kW) 21,000 Btu/hr (6.2 kW) MANIFOLD PRESSURE: Hi 3.5” w.c. (0.82kPa) 10.0” w.c. (2.
4 APPLIANCE DIMENSIONS 30 1/2" 26 1/16" 29 1/16" 19 5 16 " 20 11 16 " Figure 1 INSTALLATION CODES Installation must conform to local codes. In the absence of local codes, installation must conform to the National Fuel Gas C ode, ANSI Z233.
5 1.2 Features Ignition system : Standing pilot ignition system with thermopile and thermocouple flame detection and piezo igniter. Gas control : Gas control valve type: Automatic millivolt powered combination gas control valve with variable flame control for convenience and on/off switch.
6 2.0 OPERATION 2.1 Operation safety Inspect the appliance before use. Always keep the appliance area clear and free from combustible materials, gasoline, and other flamm able vapors and liquids. Never obstruct the flow of ventilation air. Keep the front of the applianc e clear of all obstacles and foreign materials.
7 2.2 Lighting instructions FOR YOUR SAFETY, READ BEFORE LIGHTING WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. A. This appliance has a pilot which must be lighted by hand.
8 2.3 Heat output adjustment The valve supplied with the appliance has a HI/LO knob to control the heat output and flame height (see Figure 2). 2.4 Fan operation The fan control knob is located on the control pane l and may be adjusted to the following settings: OFF: Turn the control fully count er-clockwise until the switch operates.
9 3.0 INSTALLATION 3.1 Installation and safety notes Read all instructions before starting installation and follow them ca refully during installat ion to ensure maximum benefit and safety. Failure to follow these instructions will void your warranty and may present a fire hazard.
10 3.3.2 Gas line installation Install supply line us ing any piping approved for your installation meet ing CAN/CGA 6. 10, AA 3, ANSI Z21.24 or Z21.45. A qualified gas fitter s hould install the gas line in accordance with all local building codes.
11 TABLE 2: THERMOSTAT WIRE INFORMATION WIRE SIZE MAX. WIRE LENGTH AWG mm ft . m 22 0.6 10 3.1 20 0.8 25 7.6 18 1.0 40 12.2 16 1.3 64 19.5 14 1.6 100 30.
12 Figure 4 3.3.4 Vent installation 3.3.4.1 Acceptable configurations The stove must be connected to Simpson GS Dura Ve nt or Security Chimneys International (Secure Vent) 4” x 6 5/8” venting. Inst all the vent components according to the manufacturer's instructions.
13 The minimum vertical length using the maximum horizontal length consists of: • A minimum of 24” (61cm) vertical l ength directly on top of the stove. • A maximum of one 90 degree elbow. • A maximum of 12” (31cm) total horizontal length. • A wall thimble.
14 3.3.4.2 Typical vent installation Vent terminals shall not be recessed into a wall or siding. Figure 5.
15 3.3.4.3 Use of sealant Sealant is required on vent system joints. On longer vent runs, espec ially vertical runs, sealant will ensure that the combustion air ente rs from outdoors, and not through t he vent joints.
16 3.3.4.4 Horizontal wall vent termination The position of the horizontal vent termination must be pos itioned in such a way as to meet all local building codes.
17 HOT Basement Installations To achieve the minimum vertical rise a 36” snorkel must be used. Where the bottom of the terminal may be blocked by snow, ensure provision is made for adequate drainage.
18 Through Roof Framing Maintain 10” opening relative to the pitch of the roof. Use a suitable round or square support through the roof. Ensure adequate heat shield protection is provided. Termination above Roof Consult local codes for minimum vent cap height above the roof .
19 3.3.4.6 Vent terminal locations Figure 7 A = clearances above grade, ve randa, porch, deck, or balcony [* 12" (305 mm) minimum] B = clearance to window or door that may be opened [* 12" (.
20 3.3.5 Installation of the logs Note: If the pictures in this section are not cl ear enough, you may see them in color by downloading this owner’s manual via Drolet’s web site at www.
21 3.3.6 Initial firing At the time of the firs t burn, the appliance may em it an odor, accompanied by smoke. This is perfectly normal. As the metal heats to the critical point (about 375 degrees F) , part of the paint components turns to light gray smoke as the dormant silicon e resin activates and begins to bond with the metal.
22 3.3.7 Altitude adjustment All valves have been pre-set and certified for installati on at elevations from 0 – 4500 feet (1 – 1372m) above sea level.
23 4.0 MAINTENANCE 4.1 Maintenance safety Turn off the gas to the main burner and allow th e heater to cool for up to 30 minutes before servicing. Service and repair should be done by a qualified service person. The applianc e should be inspected before use and at least annually by a professional service technic ian.
24 4.4 Burner & pilot cleaning Periodic cleaning is necessary for proper operati on. Remove the burner, and check that the burner orifice is clean.
25 5.0 TROUBLE SHOOTING SYMPTOM POSSIBLE CAUSE CORRECTIVE ACTION I. Pilot will not light after repeated triggering of the piezo ignition button A. No spark at electrode (weak or not heat sou rce for pilot ignition) 1. Improper ignition 1. Align the electrode with 1/8” (3mm) gap to pilot hood 2.
26 III. Main burner will not light A. Valve / S witches 1. Valve control off 1. Turn to “ON” position 2. Blockage at the burner (l ine, orifice, or ports) 2. Check and clean 3. Defective wall switch or thermostat 3. Conduct a continuity test or jumper wi re test and replace if defective 4.
27 6.0 REPLACEMENT PARTS When requesting service or replacement parts, refer to your dealer. The fo llowing information’s will be asked for; the model name GTX-I, the type of gas used, serial number and proof of purchase. The damaged parts must be replaced by Dr olet genuine parts.
28 DROLET LIMITED LIFETIME WARRANTY The warranty of the manufactur er extends only to the original consum er purc haser and is not transfe rable. This warranty covers brand new produ cts only, which have not been altered, modified nor repaired sin ce shipment from factory.
デバイスDrolet GTX-Iの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Drolet GTX-Iをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはDrolet GTX-Iの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Drolet GTX-Iの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Drolet GTX-Iで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Drolet GTX-Iを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はDrolet GTX-Iの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Drolet GTX-Iに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちDrolet GTX-Iデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。