EatonメーカーPowerware BladeUPS Barの使用説明書/サービス説明書
ページ先へ移動 of 28
Powerware BladeUPS Bar Installation Guide ® ®.
Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information: RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol.
EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 i Table of Contents 1 Introduction 1 ......................................................... Safety Warnings 2 ................................................................
TABLE OF CONTENTS EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 ii.
EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 1 Chapter 1 Introduction Up to six of Eaton’s Powerware ® BladeUPS ® uninterruptible power systems (UPSs) can be installed in an industry standard rack outfitted with a BladeUPS Bar 60 for interconnecting the cabinets’ wiring.
INTRODUCTION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 2 Safety Warnings IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions t hat you should follow during installation and maintenance of the BladeUPS Bar 60.
INTRODUCTION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 3 WICHTIGE SICHERHEITSANWEISUNGEN AUFBEWAREN Dieses Handbuch enthält wichtige Hinweise, welche Sie bei der Installation und Wartung des BladeUPS Bar 60 beachten sollten.
INTRODUCTION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 4 INSTRUCCIONES DE SEGURIDAD IMPORTANTES GUARDE ESTAS INSTRUCCIONES Este manual contiene instrucci ones importantes que debe seguir durante la instalación y el funcionamiento del BladeUPS Bar 60.
EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 5 Chapter 2 Installation This section explains: S Equipment inspection S BladeUPS Bar 60 setup and installation Inspecting the.
INSTALLATION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 6 Checking the Package Contents Verify that the following items are included: S BladeUPS Bar 60 A six - socket ba.
INSTALLATION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 7 Installation To install the BladeUPS Bar 60: 1. Remove the access cover and terminal block housing from the wireway housing (see Figure 2). Retain the wireway terminal block housing, wireway access cover, and screws.
INSTALLATION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 8 4. Install an M6 hex nut onto each of the three wireway studs to secure the wireway to the rear of the rack. Install the first stud in the fourth hole location from the bottom.
INSTALLATION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 9 9. Place the ferrite assembly on the floor of the wireway and secure with the supplied tie wrap. Loop the tie wrap through both attachment sites on the wireway floor and through the ferrite assembly.
INSTALLATION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 10 NOTE Verify that the bar is secure as shown in F igure 4. The sheetmetal at the base of the bar should be below the tab on the wireway floor. 12. Secure the bar to the wireway with three M6 × 12 hex bolts.
INSTALLATION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 11 14. Secure the base bracket to the rack with three M6 × 12 hex bolts. Install the bolts from the rear of the rack. Use a large screwdriver or crowbar to lift the bar in place to align the holes in the base bracket with the holes in the rack.
INSTALLATION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 12 16. Install two M4 × 8 pan - head screws into the tab on the wireway floor, securing the base of the bar to the wireway. See Figure 7. Torque the screws to 1.7 ± 0.
INSTALLATION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 13 17. Using two M6 × 12 hex bolts, secure the left side of the wireway terminal block housing to the rack. See Figure 8. Torque the bolts to 5.1 ± 0.8 Nm (45 ± 7l bi n ) .
INSTALLATION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 14 19. Using five M4 × 8 pan - head screws, install the wireway access cover. See Figure 9. Torque the screws to 1.7 ± 0.2 Nm (15 ± 2l bi n ) . M4 × 8 Pan-Head Screws (5 places) Wireway Access Cover Figure 9.
INSTALLATION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 15 21. Using four M5 × 16 hex bolts and four M5 cage nuts, secure the front cover mounting panel to the front of the rack. Verify that the bent edge of the panel is at the top.
INSTALLATION EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 16 22. Snap the two front covers into place, as shown in Figure 12.
EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 17 Chapter 3 Specifications This section provides the following specifications: Table 1. BladeUPS Bar 60 Dimensions (WxDxH) 14.0 × 11.3 × 183.8 cm (5.5 ” × 4.4 ” × 72.4 ” ) Depth of Wireway 90.
SPECIFICATIONS EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 18.
EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 19 Chapter 4 Service and Support If you have any questions or problems with the BladeUPS Bar, call your Local Distributor or the Help Desk at one of the following telephone numbers and ask for a UPS technical representative.
SERVICE AND SUPPORT EATON Powerware ® BladeUPS ® Bar Installation Guide S 164201723 Rev P01 20.
.
.
.
*164201723P01* 164201723 P01.
デバイスEaton Powerware BladeUPS Barの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Eaton Powerware BladeUPS Barをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはEaton Powerware BladeUPS Barの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Eaton Powerware BladeUPS Barの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Eaton Powerware BladeUPS Barで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Eaton Powerware BladeUPS Barを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はEaton Powerware BladeUPS Barの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Eaton Powerware BladeUPS Barに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちEaton Powerware BladeUPS Barデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。