Reference Manual 00809-0100-4514, Rev BA January 2008 www .rosemountnuclear .com Rosemount 1 154 Alphaline ® Nuclear Pressure T ransmitter.
IMP OR TA N T NOTI CE -- ER RA T A Model 115 4 Produc t Manu al 00809-01 00-4514 R ev BA (Janu ary 2008) No. Affected Pa ges Description of Change Effect.
Reference Manual 00809-0100-4 514, Rev BA January 2008 Rosemount 1154 www .rosemountnuclear .com Rosemount 1 154 Alphaline ® Nuclear Pressure T ransmitter NOTICE Read this manual before working with the product.
Rosemount 1154 Reference Manual 00809-0100-4514, Rev BA January 2008 ii Rosemount Nuclear Instrument s, Inc. W arranty and Limit ations of Remedy Authorization for return is required from Rosemount Nuclear Instruments, Inc.
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 www .rosemountnuclear .com Revision S t atus Changes From June 1999 to January 2008 NOTE The above Revision S tatus list summar izes the changes made. Please refe r to both manuals for complete comparison det ails.
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 iv.
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 www .rosemountnuclear .com SECTION 1 Introduction Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 About The Transmitter . .
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 TOC -2 SECTION 5 Maintenance and Troubleshooting Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1 Safety Messages . . . . . .
Reference Manual 00809-0100-4514, Rev BA January 2008 TOC -3 Rosemount 1154 Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6 Materials of Construction . . . . . . . . . . . . . . . . . . . . . . . . .
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 TOC -4.
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 www .rosemountnuclear .com Section 1 Introduction OVERVIEW This manual is designed to assist in installing, opera ting, and maintaining the Rosemount 1 154 Pressure Transmitter .
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 1-2.
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 www .rosemountnuclear .com Section 2 Inst allation Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1 General Considerations . . . . . . .
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 2-2 Figure 2-1. Qualified Life vs. Ambient T emperature. MECHANICAL CONSIDERATIONS This section contains information you should consider when prep aring to mount the transmitter . Read this section carefully before proceeding to the mechanical installation procedure.
Reference Manual 00809-0100-4514, Rev BA January 2008 2-3 Rosemount 1154 T ransmitters with Flange Options A, D, H, J, L, or M are shipped with Swagelok fittings for process connecti ons.
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 2-4 The piping between the process and the transmitter must transfer the pressure measured at the process tap s to the transmitter .
Reference Manual 00809-0100-4514, Rev BA January 2008 2-5 Rosemount 1154 Signal wiring need not be shielded, but twisted pairs yield the best results. In electrically noisy environments, shielded cable should be used for best results. Do not run signal wiring in cond uit or open trays with power wiring, or near heavy electrical equipment.
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 2-6 INST ALLATION PROCEDURES Installation consists of mounting the transmitter and conduit and making electrical connections.
Reference Manual 00809-0100-4514, Rev BA January 2008 2-7 Rosemount 1154 Figure 2-5. T ransmitter Dimensional Drawings. 0.8 (20) DET AI L A 3 / 8 -in. Mating T ubing Pressure Range Code Dimension A 4, 5 2.13 (54) 6, 7 2.19 (55.6) 8 2.25 (57.2) 9 2.28 (57.
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 2-8 Conduit 1. Seal the conduit threads with thread sealant. (The transmitter conduit seal interface was qua lified using Grafoil ™ t ape.) Conduit threads mate with a standard 1 / 2 –14 NPT male fitting.
Reference Manual 00809-0100-4514, Rev BA January 2008 2-9 Rosemount 1154 Figure 2-7. T ransmitter T e rminal Block. T est T erminals Signal T erminals.
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 2-10.
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 www .rosemountnuclear .com Section 3 Calibration Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1 Calibration . . . . . . . . . . . . .
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 3-2 Figure 3-1. Zero Adjustment Range. CALIBRATION PROCEDURES Zero and Sp an Adjustment NOTE The Rosemount 1 154 Pressure Transmitter cont ains electronic circuit boards which may be static sensitive.
Reference Manual 00809-0100-4514, Rev BA January 2008 3-3 Rosemount 1154 Figure 3-2. Zero and S pan Adjustment Screws. Example (for Range Code 4) Initial transmitter calibration: 25 to 125 inH 2 O (10.
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 3-4 Material • Wire: 22-gauge tinned solid coppe r – Fed S pec QQW343, ASTM B33 • Solder: 60% tin, 40% lead (60/40) – Fed S pec QQ-S-571 • Flux: MIL F 14256, T ype A, Fed S pec QQ-S-571 T ype RA Method a.
Reference Manual 00809-0100-4514, Rev BA January 2008 3-5 Rosemount 1154 1. Apply mid-range pressure and note the error between theoretical and actual output signal. 2. Apply full-scale pressure. Multiply the error noted in step 1 by six and by the rangedown factor: 3.
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 3-6 The damping adjustment permits damping of rapid pressure variations by adjusting the single-turn trim potentiometer locate d on the upper right-hand side of the amplifier board (see Figur e 3-4).
Reference Manual 00809-0100-4514, Rev BA January 2008 3-7 Rosemount 1154 1. Calibrate the unit per preceding section to output = 4 mA at –100 inH 2 O and 20 mA at 300 inH 2 O. 2. Calculate correction factor: 3. Calculate zero adjus tment corre ction in terms of pressure: 4.
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 3-8 Equalize pressure to both process connections, and turn the zero adjustment until the ideal output at zero differential input is observed. Do not readjust the span potentiometer .
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 www .rosemountnuclear .com Section 4 Operation Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1 T ransmitter Operation . . . . . . . . .
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 4-2 K 1 is a constant. C 1 is the capacit ance between the high pressure side and the sensing diaphragm. C 2 is the capacit ance between the low pressure side and the sensing diaphragm.
Reference Manual 00809-0100-4514, Rev BA January 2008 4-3 Rosemount 1154 Figure 4-2. Electrical Block Diagram. THE δ -CELL ™ SENSOR Process pressure is transmitted thro ugh an isolating diaphragm and silicone oil fill fluid to a sensing diaphragm in the center of the δ - Cell .
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 4-4 OSCILLATOR The oscillator has a frequency determined by the capacit ance of the sensing element and the inductance of the transformer windings. The sensing element capacit ance is va riable.
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 www .rosemountnuclear .com Section 5 Maintenance and T roubleshooting Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-1 Safety Messages .
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 5-2 SAFETY MESSAGES Instructions and procedures in this sect ion may require special precautions to ensure the safety of the people performing the opera tions. Information that raises potential safety issues is indicated by a warning message.
Reference Manual 00809-0100-4514, Rev BA January 2008 5-3 Rosemount 1154 SENSING MODULE CHECKOUT NOTE Numbers in parentheses refer to item numbers in Figure 5-2 on page 5-5. The sensing module (12) is not field-repairable and must be replaced if defective.
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 5-4 DISASSEMBLY PROCEDURE Process Flange Removal NOTE Numbers in parentheses refer to item numbers in Figure 5-2 on page 5-5. NOTE The Rosemount 1 154 Pressure Transmitter cont ains electronic circuit boards which may be static sensitive.
Reference Manual 00809-0100-4514, Rev BA January 2008 5-5 Rosemount 1154 Figure 5-2. Rosemount 1 154, Exploded View . T a ble 5-1. Rosemount 1 154 Parts List.
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 5-6 Electrical Housing Disassembly 1. The signal terminals and test term inals are accessible by unscrewing the cover (1) on the terminal side. Th is compartment is identified as “terminal side” on the nameplate.
Reference Manual 00809-0100-4514, Rev BA January 2008 5-7 Rosemount 1154 Preliminary 1. Replace the cover O-rings (2) w henever you remove a cover . Clean the sealing areas with alcohol, if necessary , and lightly grease the O-ring with Dow Corning 55 Silicone O-ring Grease (Rosemount P/N 01 153-0248-0001 or P/N 01 153-0053- 0001).
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 5-8 Process Flange Reassembly 1. Replace the met al O-rings (1 1) with new O-rings if the flanges were removed. 2. Carefully place an O-ring (1 1) in th e isolator well of the high side (“H”) of the sensing module.
Reference Manual 00809-0100-4514, Rev BA January 2008 5-9 Rosemount 1154 POST ASSEMBLY T EST S 1. Conduct hydrost atic testing to 150% of maximum working pressure or 2,000 psi, whichever is greater . 2. Calibrate the transmitter per the calibration section of this manual.
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 5-10 Low Output or No Output Primary Element Check for restrictions at primary el ement, improper installation or poor condition. Note any changes in process fluid properties that may affect output.
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 www .rosemountnuclear .com Section 6 S pecifications and Reference Dat a Nuclear Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6-1 Performance Specifications .
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 6-2 Post DBE Operation Accuracy at reference conditions shall be within ±2.5% of upper range limit (±3.
Reference Manual 00809-0100-4514, Rev BA January 2008 6-3 Rosemount 1154 Drif t ±0.2% of upper range limit for 30 months Range Code 0: ±(0.3% of upper range limit) T emperature Effect Range Codes 4–9: ±(0.75% upper range limit +0.5% span ) per 100 °F (55.
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 6-4 St atic Pressure Zero Effect Rosemount 1 154DP: Per 1,000 psi (6.89 MPa): Rosemount 1 154HP: Per 1,000 psi (6.89 MPa): St atic Pressure Sp an Effect Effect is systematic and can be calibrated out for a particular pressure before installation.
Reference Manual 00809-0100-4514, Rev BA January 2008 6-5 Rosemount 1154 Sp an and Zero Continuously adjustable externally Zero Elevation and Suppression Maximum zero elevation: 600% of calibrated spa.
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 6-6 St atic Pressure and Overpressure Limit s Rosemount 1 154DP: 0.5 psia to 2,000 p sig (3.4 kPa abs to 13.8 MPa) maximum rated static pressure for operation within specifica tions; overpressure limit is 2,000 psig (13.
Reference Manual 00809-0100-4514, Rev BA January 2008 6-7 Rosemount 1154 Electrical Connections 1 / 2 –14 NPT conduit with screw terminals Process Connections 3 / 8 in. Swagelok compression fitting, 316 SST ( 1 / 4 –18 NPT optional) Wei ght 24 lb (10.
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 6-8 ORDERING INFORMATION T a ble 6-1. T ransmitter Design S pecifications. Model Description 11 5 4 Alphaline Pressure T ransmitters for Nuclear Applicat ions, IEEE St d 323-1974 and IEEE S td 344-1975 Code Pressure Measurement DP HP GP Differential Pressure, 2,000 ps ig (13.
Reference Manual 00809-0100-4514, Rev BA January 2008 6-9 Rosemount 1154 T a ble 6-2. Rosemount 1 154DP , 1 154HP , and 1 154GP S pare Parts. S pare Parts Category (1) T raceable Part Quantity Required Item Number (see Figure 5-2 on page 5-5) Rosemount 1 154DP Rosemount 1 154HP Rosemount 11 5 4 G P Part Description Order No.
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 6-10 S pare Parts Category (3) T raceable Part Quantity Required Item Number Rosemount 1 154DP Rosemount 1 154HP Rosemount 11 5 4 G P Part Description Order No.
Reference Manual 00809-0100-4514, Rev BA January 2008 6-1 1 Rosemount 1154 SP ARE PART S SHELF LIFE S tore all spare transmitters and sp are component parts in accordance with ANSI N45.
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 6-12.
Reference Manual 00809-0100-4514, Rev BA January 2008 Index-1 Rosemount 1154 A Adjustment . . . . . . . . . . . . . . 3-7 zero . . . . . . . . . . . . . . . . 3-7 B BOARD CHECKOUT . . . . . . . 5-2 C Conduit . . . . . . . . . . . . . . . . . 2-4 Conduit Connection .
Reference Manual 00809-0100-4514, Rev BA January 2008 Rosemount 1154 Index-2.
.
Emerson Process Management ¢00809-XXXX-XXXX ¤ The Emerson logo is a trade mark and se rvice mar k of Emerson Electric Co. Rosemount, the Rosemount logotype, and Alphaline are registered trademarks of Ro semount, Inc. Cell is a trademarks of Rosemount, Inc.
デバイスEmerson 00809-0100-4514の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Emerson 00809-0100-4514をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはEmerson 00809-0100-4514の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Emerson 00809-0100-4514の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Emerson 00809-0100-4514で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Emerson 00809-0100-4514を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はEmerson 00809-0100-4514の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Emerson 00809-0100-4514に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちEmerson 00809-0100-4514デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。