AC P ow er For Business-Criti cal C on tinuity™ Li eber t ® NXL ™ Install ation M anual – 250-400kV A, 60Hz, Three Pha s e Single-Module.
C ONT ACTING L IEBERT FOR S UPPORT To contact Liebert Services for information or repair service in the United States, call 1-800-LIEBERT (1-800-54 3-2378). Liebert Services offe rs a complete range of start-up services, repair services, preventive maintenanc e plans and service contracts.
i T ABLE OF CONTENTS C ONT ACTI NG L IEBERT FOR S UPPORT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I NSIDE F RONT C OVER I MPORT ANT S AFE TY I NSTRUC TIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ii FIGURES Figure 1 Cabinet arrangement—Liebert NXL, battery cabinets, maintenance bypass cabinet . . . . . . . . . . 5 Figure 2 External Interface Board connections layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 I MPORT ANT S AFETY I NSTRUCTIONS SA VE THESE INSTRUCTIONS This manual co ntains important ins tructions that should be followed during installation of your Liebert NXL ™ UPS.Read this ma nual thoroughly, paying spec ial attent ion to the sections that apply to your installation, befo re working with the UPS.
2 NOTICE This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules. These li mits provide reasona ble protection against ha rmful interference in a commercial environment.
Single-Module Mechanic al Installation 3 1.0 S INGLE -M ODULE M ECHANICAL I NST ALLATION 1.1 Introduction This following se ction describes the requiremen ts th at must be taken into account when p lanning the positioning and cabling of the Liebert NXL uni nterruptible power supply and relat ed equipment.
Single-Module Mechanic al Installation 4 1.3.2 Storage Should the equipment not be installed immed iately, it must be stored in a room for protection ag ainst excessive humidity and or heat sources (see Environmental Parameters in Table 6 ). 1.4 Positioning The cabinet is structurally desi gned to handle lifting fr om the base.
Single-Module Mechanic al Installation 5 1.6 Cable Entry Cables can enter the UPS cab inet from bottom or t o p into the Input/Output (I/O) section of the unit, see the figure s in 4.
UPS Electrical Installation 6 2.0 UPS E LECTRICAL I NST ALLATION This chapter provid es guidelines fo r qualified install ers who must have knowledge of local wiring practices pertaining to the equipment to be installed.
UPS Electrical Installation 7 The following are guidelines only and superseded by local regulations and codes of practice where applicable: • Take special care when determin ing the size of the neut.
UPS Electrical Installation 8 Bottom Cable Entry When making the power connections for bottom cable entry, the recomme nded order of pull- ing and installi ng cables is to start from the bottom connections to the top connections. The cables must be routed around the fault braces (see Detail in Figure 9 ).
UPS Electrical Installation 9 2.3.1 Dry Cont act s Volt-free and isolated contacts are used for interf acing to customer connections external to the NXL unit.
UPS Electrical Installation 10 Switch Auxiliary Input s Dry Cont acts Control St atus Output Dry Cont acts Status signals are outputs through volt-free, normally open and norm ally closed contacts.
Optional Equipme nt 11 3.0 O PTIONAL E QUIPMENT 3.1 Single-Module System Options 3.1.1 Matching Maintenance Byp ass Cabinet A matching Liebert NXL Main tenance Bypass cabinet is available. See Maintenance Bypass Ca binet Installation Manua l (SL-24532) for more d etails.
Installation Drawings 12 4.0 I NST ALLATION D RAWINGS Figure 3 Main component s location, 250kV A Liebert NXL UPS HMI Scr ee n EMO But ton (optional) Lieb ert Inte llislot Bay s ® Custo mer Interface.
Installation Drawings 13 Figure 4 Outline drawing, 250kV A Liebert NXL UPS 71.8" (1823mm) 34.8" (884mm) 33.5" (850mm) 76.8" (1950mm) 17.6" (448mm) 56.8" (1443mm) 8.5 (2 16) 8.5 ( 216) 26.1 (664mm) 27" (685mm) 9.8" (2 50) 9.
Installation Drawings 14 Figure 5 Main component s location, 300kV A Liebert NXL UPS HMI Scre en EMO Bu tt on (optional) Lieb ert Intellis lot Bays ® Cust ome r Interface Boa r d Main Input Circu it .
Installation Drawings 15 Figure 6 Outline drawing, 300kV A Liebert NXL UPS.
Installation Drawings 16 Figure 7 Input/output conduit det ail dr a wing, 250-300kV A Liebert NXL UPS OUTP U T NEUTRA L INNER PANE L REMOVED FOR CLARIT Y SHO WN IN EXTE NDED POS IT IO N DC (2) 3" CONDUI T NOTES: 1. ALL D IM ENSI O NS AR E I N i nches (m m).
Installation Drawings 17 Figure 8 T op cable entry routing and inst allation order The cables must be rout ed around the fault braces. This is to prevent the cables from coming in cont act with other busbars.
Installation Drawings 18 Figure 9 Bottom cable entry routing and in st allation order SIDE VIEW F AU L T BRACE OUTPU T F AU L T BRACE RECT IFI ER INPU T F AU L T BRACE BYP ASS INPU T BYP ASS NEUT RA L.
Installation Drawings 19 Figure 10 Input/output terminal det ail, 400kV A Liebert NXL UPS NOTES: 1. ALL DI MEN SIO N S ARE I N inc hes (mm) . 2. 2 4" MI NI MUM CLEAR ANC E ABO VE U NI T REQ UI RED FO R AIR EXHA US T . 3. KE EP CAB IN ET WIT HI N 15 DEG R EES O F VERTI CAL .
Installation Drawings 20 Figure 1 1 Main component s, 40 0kV A Liebert NXL UPS HMI SCREEN MAIN INPU T CIRCUI T BREA KER (CB1) BACKFEED BREAKE R (BF B) EMO BUT TON OPTIONA L EXTERNA L INTER F ACE BOARD.
Installation Drawings 21 Figure 12 Outline drawing, 400kV A Liebert NXL UPS 3.7 (9 5 ) 10.6 ( 269 ) 12.4 (3 1 6 ) 12.4 ( 316 ) 10.6 ( 269 ) 3.1 (8 0 ) TY P 32.
Installation Drawings 22 Figure 13 Ground strap location for connected ca binet s REFERENC E OF CORNER-PO ST OF CONNECTE D CABINETS Cabinet- to-Cabinet Bolting I nstruct ions T ypical Ground Str ap In.
Specifications 23 5.0 S PECIFICATIONS T able 6 Liebert NXL UPS specif ications 250 300 400 Input Parameters Input Voltage to Rectifie r, VAC 480V 3-phase, 3-wire Input Voltage to Bypass, VAC 480V 3-ph.
Specifications 24 Physical Parameters and Standards, in (mm) Width, With Side Panels 71.8 (1823) 78.5 (1993) 78.5 (1993) Depth 33.5 (850) 33.5 (850) 39.
Specifications 25 Notes on T ables 1. Nominal input current (considered continuous) is based on full -rated output load. Maxi mum current includes nominal input current and ma ximum battery recharge current (considered noncontinuous). Continuous and noncontinuous cu rrent are defined in nec 100.
Specifications 26 T able 12 Recommended conduit and cable sizes Rectifier Input UPS Rat ing Voltag e (VAC) Nominal Selection Alternate Selection Top Cable Entry Input Wire & Condu it Ph, G THW / F.
Specifications 27 T able 13 Recommended lug sizes Cable Size T&B Series 54000 One Hole T&B Series 54000 Two Hole #8 AWG 54930BE 54850BE #6 AWG 54905BE 256-30695-868 #4 AWG 54906BE 256-30695-73.
EmersonNetworkPower.com Ensuring The Hi gh Av ai lab ilit y 0f Mission-Critic al Dat a And App lic ations. Emerson Net work P ower , the global leader in enabling business-critical continuity , ensure.
デバイスEmerson 250の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Emerson 250をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはEmerson 250の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Emerson 250の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Emerson 250で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Emerson 250を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はEmerson 250の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Emerson 250に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちEmerson 250デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。