1 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN Application Enginee ring BULLE TIN Safety Safety Instructions ................................................................. 2 Safety Icon Explanation .
2 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN Safety Instructions Copeland Scroll ® compressors with CoreSense ™ Diagnostics technology are manufactured according to the latest U.S. and European Safety Standards.
3 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN ELECTRICAL SHOCK HAZARD • Disconnect and lock out power before servicing. • Discharge all capacitors before servicing. • Use compressor with grounded system only .
4 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN INTRODUCTION Overview CoreSense ™ Diagnostics is a breakthrough innovation for troubleshooting residential air conditioning and heat pump systems.
5 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN OPERA TION Compressor Protection The CoreSense Diagnostics module utilizes proprietary algorithms to protect the compressor and system from repeated trips of system pressure controls and the compressor internal overload.
6 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN off. This event will cause a lockout of the compressor and indicates that the module is mis-wired or the contactor coil is shorted to ground. NOTICE Code 10 is not speci fi ed on the module label.
7 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN ALERT TRIP / LOCK POWER 1 Long Run Time 2 Compressor (Pressure) Trip 3 Pressure Switch Cyclin.
8 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN 2- S t a g e Th e rmo s tat I ndoor Uni t O utdoor Uni t C R Y1 Y2 C R L Y Y2 L DC So l en o .
9 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN Alert Code Alert Condition Lockout Level Lockout Indication Normal Run Solid Green Normal operation, no trip. N/A N/A Code1 Y ellow Flash 1 Long run time.
10 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN Status Description T roubleshooting Information Solid Green “RUN” Module has power and o.
11 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN Y ellow “ALERT” Flash Code 4 Locked Rotor 1. Run capacitor has failed 2. Low line voltage (contact utility if voltage at disconnect is low) • Check wiring connections 3.
12 © 201 1 Emerson Climate T echnologies Printed in the U.S.A. AE8-1385 Application Enginee ring BULLE TIN Red “LOCKOUT” Flash Code 5 Y ellow Off Compressor (Moderate Run) T rip Compressor is locked out after 4 consecutive or 10 total compressor (moderate run) trip events 1.
デバイスEmerson AE8-1385の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Emerson AE8-1385をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはEmerson AE8-1385の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Emerson AE8-1385の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Emerson AE8-1385で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Emerson AE8-1385を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はEmerson AE8-1385の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Emerson AE8-1385に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちEmerson AE8-1385デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。