Install ation and Ope rati on Instructions Installation and Ope ration Instru ctions Mark II Mark II XG XG Dies e l Engine Fire P ump C ontroll e rs Diese l Engine Fire Pump C ontrolle rs NS1100-50 E .
T abl e of Contents INTR ODUC TION .................................................................................................................. ......... 1 MOUNTING C ONTR OLLER ...................................................................
Pressure (con tinued) Ove rpressure Alarm ................................................................................................. 10 R ecor ding - Delta ........................................................................................
MAIN MENU - F AC T OR Y (continued) Con fi guration - Model Pressure Se nsor .................................................................................................... .... 15 Auto st ar t NC ................................................
These instructions are intended t o as sist in the understanding of the installation and ope ration of the F T A1100. Re ad through these instruc tions thoroughly prior to c onnec ting the controlle r .
5. U sing eithe r the dimension print or b y measuring the distanc e bet wee n the cen ter lines o f the 2 lowe r bracket slo ts, transcribe this dimension on t o the wall. Note : The bottom edge o f the en- closure should be a minimum o f 12” (305 mm.
2. V erify that the c ontrolle r inform ation is wh at is required on the project: • Firetrol catalog numbe r • Engine voltage and polarity of grounding • Incoming line v olt age and freque nc y • Maximum syste m pressure 3.
6. Connect AC pow er t o “L1” and “L2” (CB1) —120 V olt, 60 Hz or as called for on c ontroller d ata plat e. 7. Connec t remo te normally open ST ART push-button wires t o terminals “13” and “14” (if u sed). 8. If deluge valv e is used, remo ve jumper from t ermin als “16” and “17”.
AC POWER A V AILABLE ALARM MAIN SWITCH IN AUTO MAIN SWITCH IN MANUAL SYSTEM PRESSURE LOW ENGINE RUNNING ENGINE F AIL TO ST ART ENGINE TEMPERA TURE HIGH ENGINE OIL PRESSURE LOW ENGINE OVERSPEED ENGINE .
Mark II XG Us er Me nu Stru c ture Main Menu Setting s System Se tup Da te & Time Timers Pressure Engine & Cranking Alarm Limits Fe at. Settings Displa y Language/Units Passwords Time Date Daylight Sa ving On Dela y T ime Min.
Programming No tes The Firetrol Mark II XG is multi-leve l passwor d protected. User programm able func tions are protected b y a Lev el 1 pas s wor d. LE VEL 1 P A SSW ORD 2 - 1 - 1 - 2 Note: Many me nu settings f eature an “e nable/disable” option.
Mark II XG Us er Me nu Settings SET TINGS SYSTEM SETUP DIS PLA Y BRIGHTNESS 1 Use and arro ws to set de sired displa y brightness. Press to c on fi rm. Syst em Setup - Dis play SET TINGS SYSTEM SETUP DISPLA Y CONTRAST 1 Use and arro ws to set de sired displa y contrast.
SET TINGS D A TE & TIME D A YLIGHT SA VING 1 Use arrows t o enable or disable autom atic D aylight Saving time adju stments. Press t o con fi rm. (DST +) “Begin ” - Hour Use arrows t o set number of minute s to adju st for at the beginning or en d of Da ylight Saving time.
Use arrows t o enable or disable this setting. Pre ss to c o n fi rm. SET TINGS PRESS URE OVERP RESSURE ALARM 1 Use arro ws to en able or disable the overpre ssure alarm f eature . Press to con fi rm. Limit Use arro ws to set the pre ssure limit for the o verpressure al arm.
Use arrows t o set maximum voltage point f or Battery T rouble alarm. Press t o con fi rm. SET TINGS ALARM LIMITS 1 MAX Use arro ws to set minimum v olt age point f or AC V oltage Low alarm. Pres s to con fi rm. SET TINGS ALARM LIMITS 1 V MIN Use arro ws to set m aximum voltage point for A C Voltage High al arm.
SET TINGS FEA TURE SET TINGS MANUAL TEST 1 DURA TION Use arro ws to set the minimum run time (duration) whe n manual test pu sh -button is u sed (10 - 99 min.). Press t o con fi rm. SET TINGS FEA TURE SET TINGS PUMP RUN ALARM 1 AUD IBL E Use arro ws to en able or disable the audible alarm for Pump R un.
13 SET TINGS FEA TURE SET TINGS RELIEF V AL VE OPEN 1 AUD IBL E Use arro ws to en able or disable the audible alarm for R elief V alve Open. Pre ss to con fi rm. 1 COMMON ALARM Use arro ws to en able or disable the common alarm output (ALR re lay) f or Relie f Valv e Open.
SET TINGS OPTION SET TING S NOTE: The list of avail able options and the settings a ssociat ed with them will vary with each con troller . Listed below are the most c ommon use r de fi ned settings th at may appe a r . 1 AUD IBL E Use arro ws to en able or disable the audible alarm for selected op tion.
FA C TO RY CONFIG URA TION MODEL 3 SERIAL NUMBER Use arro ws to en ter the con troller serial numbe r . Press to c on fi rm. NO TE: This is a fac tory set paramete r and under norm al circumstance s would never be c hanged. 3 MODEL Use arrows t o selec t required mode l number .
LAMP TEST 1 Use arro ws to en able the lamp test. Press t o begin test. All System S tatus LED’s should illuminat e . Use arro ws to disable the lamp t est. Press t o end test. Syste m Status LED’s should turn off and return to norm al indications.
When installing the batt ery charge r as a re place men t par t, it is nece ssar y to verify the proper ch arge r setting s and adjust a s necessar y . 1. Incoming A C voltage 115 or 230 volts. 2. Batte r y voltage - 12 or 24 volts DC. 3. Batte r y t y pe - Le ad Acid / Ni-Cad 9 or 18 Cell / Ni-Cad 10 or 20 Cell.
デバイスEmerson FTA1100の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Emerson FTA1100をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはEmerson FTA1100の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Emerson FTA1100の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Emerson FTA1100で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Emerson FTA1100を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はEmerson FTA1100の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Emerson FTA1100に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちEmerson FTA1100デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。