Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 www .rosemount.com Section 3 Inst allation Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1 Safety Messages . . . . . . . . . . .
Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-2 W arnings Explosions could result in death or serious injury: • Do not remove the transmitter cover in explosive atmospheres when the circuit is alive.
Reference Manual 00809-0100-4690, Rev EA March 2007 3-3 Rosemount 2088 and 2090 Figure 3-1. Installation Flowchart. Check for Leaks (Process Connections) Zero T rim T ransmitter for Mounting Effect s .
Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-4 GENERAL CONSIDERATIONS The accuracy of the pressure measurement depends on proper installation of the transmitter and impulse piping. The piping between the process and transmitter must accurately transmit pr essure to the transmitter .
Reference Manual 00809-0100-4690, Rev EA March 2007 3-5 Rosemount 2088 and 2090 MECHANICAL CONSIDERATIONS Mounting Rosemount 2088 The Rosemount 2088 Smart T ransmitter weighs approximately 2.44 lb. (1,1 1 kg). The 2088 Analog T ransmitter weighs approximately 1.
Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-6 Impulse Piping Impulse piping configurations depend on specific measurement conditions. Use the following information and Figur e 3-3 as a guideline when installing impulse piping.
Reference Manual 00809-0100-4690, Rev EA March 2007 3-7 Rosemount 2088 and 2090 Access Requirement s When choosing a mounting location and pos ition, take into account the need for access to the transmitter . Make wiring terminations through the conduit openings at the top of the electronics housing.
Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-8 Nameplate 3.9 (100) 2X 1 / 4 –20 UNC–2BX 0.60 Deep Mounting Bracket Holes 4.7 (140) T erminal Connections T ransmitter Circuitry Side Optional Meter Cover 5.0 (125) W eld Spud 1.
Reference Manual 00809-0100-4690, Rev EA March 2007 3-9 Rosemount 2088 and 2090 Rosemount 2090P Installing the Rosemount 2090P transmitter involves att aching a weld spud to the tapped process vessel, att aching t he transmitter to the weld spud, and making electrical connections.
Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-10 3. Hand tighten the transmitter using the knurled retaining ring, then snug an additional 1 / 8 turn with adjustable pliers. IMPORT ANT Do not over-tighten the retaining ring.
Reference Manual 00809-0100-4690, Rev EA March 2007 3-1 1 Rosemount 2088 and 2090 Rosemount 2090F The Rosemount 2090F sanitary pressu re transmitter is designed to be installed directly to a sanit ary fitting. T he transmitter is available with either a 1.
Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-12 Figure 3-9. T ransmitter Load Limitations Field Wiring All power to the transmitter is supplie d over the signal wiring. Signal wiring need not be shielded, but use twisted pairs for best results.
Reference Manual 00809-0100-4690, Rev EA March 2007 3-13 Rosemount 2088 and 2090 Figure 3-10. Rosemount 2088 Smart Signal Wiring T erminals. FAILURE MODE AND SECURITY JUMPERS Failure Mode As part of normal operation, the Rosemount 2088/2090 Smart Pressure T ransmitter continuously monitors its own operation.
Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-14 With a meter inst alled The failure mode alarm jumper is located on the LCD faceplate in the electronics module side of the transm itter housing and is labeled ALARM (See Figure 3-1 1).
Reference Manual 00809-0100-4690, Rev EA March 2007 3-15 Rosemount 2088 and 2090 NOTE If either the alarm or security jumper is dislodged or removed from its position the transmitter reverts to defaul.
Reference Manual 00809-0100-4690, Rev EA March 2007 Rosemount 2088 and 2090 3-16 Disabling the Zero and Sp an Adjustment s After you rerange the transmitter usi ng the sp an and zero adjustments, you may wish to disable the adjustments to prevent further reranging.
デバイスEmerson Process Management 2090の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Emerson Process Management 2090をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはEmerson Process Management 2090の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Emerson Process Management 2090の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Emerson Process Management 2090で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Emerson Process Management 2090を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はEmerson Process Management 2090の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Emerson Process Management 2090に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちEmerson Process Management 2090デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。