Event electronicメーカーK_NA4C3P21Rの使用説明書/サービス説明書
ページ先へ移動 of 16
K eep This Manual With Air Conditioner AIR CONDITIONER OPERA T OR'S MANU AL CA UTION BEFORE INST ALLING AND USING THIS AIR CONDITIONER, IT IS IMPORT ANT THA T THIS MANU AL BE READ AND UNDERST OOD THOR OUGHL Y K OOL TRONIC, INC. 30 P ennington-Hopewell Road P ennington, NJ 08534 609 • 466-3400 F AX: 609 • 466-1114 www .
T ABLE OF CONTENTS P age I. Introduction 2 II. Incoming Inspection 3 III. Product Handling 3 IV . Product Identification Label 4 V . Pr inciples of Operation 5 - 6 VI. Pre-Installation T esting 6 VII. Specific Model Data 7 - 10 Mounting Dra wings and Dimensions T echnical Data Major Component Replacements Standard F eatures Wiring Schematic VIII.
3 II. Incoming Inspection K ooltronic Air Conditioners are designed, b uilt and packaged to withstand the shoc k and vibration normally associated with shipment by common carriers.
4 IV . Pr oduct Identification and Labels Each K ooltronic Air Conditioner includes an identification label. This label provides: ➀ Model Number ➁ Serial Number ➂ Electrical power characteristic.
V . Principles of Operation K ooltronic Air Conditioners are required when the equipment operating temper ature must be k ept near or low er than the ambient room temperature, and/or the cabinet m ust be sealed from dust, fumes, oil, corrosiv es and other contaminants.
The heater kit consists of a heater , a heat control ther mostat and a heater limiter . The heater control ther mostat is a bimetal disk with a fix ed set point of 60°F . When the entering e vapor ator air temperature r ises abov e 60°F the heater shuts off, and when the e vapor ator air temperature f alls below 40°F the heater will engage.
VII. Specific Model Data Mounting The K ooltronic Special Pur pose Air Conditioners K_NA4C3P21R hav e been engineered to be installed easily . These units utilize doub le lay er gaskets. The first gasket la yer is placed on the outside perimeter of the front panel that is sealed against the customer enclosure.
8 21.19 [538.2] DRAIN 12.48 [316.9] .36 [9.1] 8.08 [205.2] TYP. 3.40 [86.3] TYP. 9.20 [233.6] TYP. 11.54 [293.1] TYP. 9.20 [233.6] 7.50 [190.5] 1.92 [48.7] 2.00 [50.8] 12.01 [305.0] POWER CORD Drawings and Dimensions K_NA4C3P21R SERIES Dimensions, inches [mm], are f or reference only and are subject to change.
9 T echnical Data KNA4C3P21R 3000 2160 125 0 115 60 11.3 76 K2NA4C3P21R 3000 2160 131 0 230 60 4.7 76 K2NA4C3P21R5 3000 1940 131 0 230 50 4.6 76 * Rating shown is f or operation at maximum ambient temperature . Ambient Ambient Appro ximate BTU/H BTU/H T emp.
10 Wiring Schematic EVAPORATOR FAN CAP. WE GN SUPPRESSOR HEATER THERMAL CUTOUT T-STAT 115 V 230 V TO CUSTOMER ALARM SYSTEM (OPTIONAL) TERMINAL BLOCK COOLING EFFECT DETECTOR BK T-STAT SHORT CYCLE TIMER OPTIONAL SHORT CYCLE PROTECTOR OPTIONAL HEATER SPEED CONTROLLER CONDENSER BLOWER MOTOR CAP.
11 VIII. Maintenance K ooltronic W ater-Cooled Air Conditioners require no maintenance. Air-Cooled Air Conditioners are designed to require only the routine cleaning of air filters to assure unimpeded airflo w through the condenser heat e xchanger .
12 B. Blower s The design lif e of the blowers used in all K ooltronic Air Conditioners is substantially in excess of 20,000 hours. All Kooltronic condenser and e vapor ator blow ers are equipped with automatic-reset ther mal o verload protectors.
. IX. T roub le-Shooting Each K ooltronic Air Conditioner is engineered for perf or mance and b uilt f or reliability . They are designed to require no routine maintenance other than the cleaning of ambient air filters. If your air conditioner should require warr anty ser vice, please contact K ooltronic.
14 This page intentionally left blank.
15 THIS W ARRANTY CONSTITUTES THE ENTIRE W ARRANTY WITH RESPECT T O THE PR ODUCT AND IS IN LIEU OF ALL O THERS, EXPRESSED OR IMPLIED , INCLUDING ANY W ARRANTY OF MERCHANT ABILITY AND W ARRANTY OF FITNESS FOR A P ARTICULAR PURPOSE AND IN NO EVENT IS K OOL TRONIC RESPONSIBLE FOR ANY CONSEQUENTIAL D AMA GES OF ANY NA TURE WHA TSOEVER.
BEAT THE HEAT! KoolTray II - 19” width fan cooling units. Available in 1, 2 and 3 row configurations. Custom/Special units available. Pennington, NJ Ventura, CA Tel: (609) 466-3400 Tel: (805) 642-85.
デバイスEvent electronic K_NA4C3P21Rの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Event electronic K_NA4C3P21Rをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはEvent electronic K_NA4C3P21Rの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Event electronic K_NA4C3P21Rの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Event electronic K_NA4C3P21Rで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Event electronic K_NA4C3P21Rを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はEvent electronic K_NA4C3P21Rの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Event electronic K_NA4C3P21Rに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちEvent electronic K_NA4C3P21Rデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。