SIDE WALL POWER VENTER KIT Model : SWG, SWGII & SWG Stainless Series * Patented TYPICAL VENTING SYST EM COMPONENTS 1 - SWG Series Power Venter 1 - CK Series Control Kit (sold separately) OPTIONAL SYSTEM COMP ONENTS SWG S ERIES T HROUGH - W ALL E XTENSION K IT F or installation in wall thickness over 8 inches.
Page 2 CONTROL KITS CK - 20F/HWK: For operation with 30 or 750 millivolt gas - fired water heaters, gas - fired space heaters and gas - fired pool or spa heaters with an internally mount ed thermostat. Includes a fixed post purge. CK - 21: For operation with gas - fired instantaneous water heaters with a pressure tap port in the burner manifold.
Page 3 INSTALLATION OF SWG POWER VENTER ( See Table 1) Table 1 UNIT SIZING CHART OIL GAS MAXIMUM EQUIVALENT FEET OF VENT PIPE MAX* OIL GPH INPUT MAX** BTU/HR. IMPUT AT MAX BTU/HR INPUT AT 60% OF MAX BTU /HR INPUT VENTING WITH VENT PIPE SIZE MODEL 21 80 3” 50 100 4” N/A 70,000 --- --- --- SWG - 3 --- 23 3” 35 100 4” 1.
Page 4 P ROCEDURE F OR C ALCULATING T OTAL E QUIVALENT P IPE L ENGTH I N F EET 1. Calculate the total equivalent feet for each type of fitting used in the venting system from the chart below. 2. Calculate the total amount of feet for the st raight lengths of vent pipe.
Page 5 Figure 2 Figure 3 Figure 4 3. After determining the location of the venting system termination point (see Diagram A), cut a square hole through the wall 1 " larger than the outer pipe diameter of the power venter. Mount the power venter through the wall, keeping the outer pipe centered in the hole.
Page 6 Figure 5 C ONNECTING P OWER V ENTER T O A PPLIANCE Venting system should be installed and supported in accordance with the National Flue Gas Code A.
Page 7 Figure 6 Figure 7 Figure 8 CLASS B AND CLASS L DOUBLE WALL VENT PIP E INSTALLATION (Follow vent pipe manufacturer's listed or recommended cleara nces from combustible material) 1. Using a hand crimper or a like device, crimp the inner pipe of the S WG power venter approximately 1" long.
Page 8 GENERAL INSTALLATION INSPECTION Recommended procedures for safety inspection of an appliance in accordance with the National Fuel Gas Code A.N.S.
Page 9 Figure 9 Figure 10 REPLACEMENT PARTS Should the motor or blower wheel need replacing, the following replacement items are available. The Repair Motor Assembly contains the Motor and Blower Wheel factory assemble to a mounting bracket.
Page 10 Figure 11 Figure 12 Figure 13 Figure 14 I NSTALLATION 1. Insert the blower wheel through the hole in the front plate of the power venter housing. (See Figure 11) 2. Using two nails or awls, align the two center holes of the motor mount bracket and cover plate.
Page 11 INITIAL BURNER AND V ENTING SYSTEM OP ERATIONAL INFORMATIO N List the following for each operating appliance on the sidewall venting system, as a guide for tune - up or service information annually.
Page 12 P/N 46139100 Rev J 05/01.
デバイスField Controls SWGの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Field Controls SWGをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはField Controls SWGの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Field Controls SWGの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Field Controls SWGで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Field Controls SWGを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はField Controls SWGの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Field Controls SWGに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちField Controls SWGデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。