All information contained herein is subject to change without notice. I NST ALLA TION I NSTRUCTIONS F OR L IGHT C OMMERCIAL S ELF -C ONT AINED P ACKAGED H EA TING & C OOLING U NIT 3 T ON - 6 T ON CPC/CPH S ERIES Goodman Manufacturing Company , L.P .
2 REPLACEMENT PARTS O RDERING P ARTS When reporting shortages or damages, or ordering rep air part s, give the complete unit model and serial numbers as stamped on the unit’ s nameplate. Replacement parts for this appliance are available through your contractor or local distributor .
3 T HIS UNIT MU ST NOT BE USED AS A “ CONST RUC TION HEATE R ” DURING THE FINISHING PHAS ES OF CONST RUC TION ON A NEW STRUCT UR E . T HIS TYPE OF USE MA Y RESU LT IN PREMAT UR E FAILURE OF THE UNIT DUE TO EXT REME LY LOW RETURN AIR TEMP ERAT URES AND EXPO SURE TO CORR OSIVE OR VER Y DIRT Y ATMO SPHE RES .
4 NOTE: When inspecting the unit for transportation damage, remove all packaging materials. Recycle or dispose of the packaging material according to local codes. P RE -I NSTALLATION C HECKS Carefully read all instructions for the installation prior to in- stalling unit.
5 Full perimeter roof curbs are available from the factory and are shipped unassembled. Field assembly , squaring, level- ing and mounting on the roof structure are the responsibility of the installing contractor . All required hardware necessary for the assembly of the sheet metal curb is included in the curb accessory .
6 P ROTRUSION Inspect curb to ensure that none of the utility services (elec- tric) routed through the curb protrude above the curb. I F PROT RUSIO NS EXI ST , DO NO ATTEMPT TO SET UNIT ON CURB . CAUTION ROOF TOP DUCT CONNECTIONS Install all duct connections on the unit before placing the unit on rooftop.
7 Lower unit carefully onto roof mounting curb. While rigging unit, center of gravity will cause condenser end to be lower than supply air end. T o assist in determining rigging requirements, unit wei.
8 T O PRE VENT SEVE RE DAMAG E TO THE BOTTOM OF THE UNIT , DO NOT FORK LIFT UNIT AFTER WOOD STRUT S HAVE BEEN REMOV ED . CAUTION Bring condenser end of unit into alignment with the curb. With condenser end of the unit resting on curb member and using curb as a fulcrum, lower opposite end of the unit until entire unit is seated on the curb.
9 LOW VOLT AGE BLOCK MA IN PO WER LOW VO L T AGE ENTRANCE POWER THRU THE CURB CONTROL BOX F AILU RE OF UNIT DUE TO OPERATION ON IMP ROPER LINE VOLTAGE OR WITH EXC ESSI VE PHAS E UNBAL ANC E CONSTITUTES PRODUCT ABUSE AND WILL VO I D YO U R WARRANT Y AND MA Y CAUSE SEVE RE DAMAG E TO THE UNIT ELECTR ICAL COMPONE NTS .
10 CIRCULA TING AIR AND FIL TERS D UCTWORK The supply duct from the unit through a wall may be installed without clearance. However , minimum unit clearances must be maintained (see “Clearances” section). The supply duct should be provided with an access panel large enough to inspect the air chamber downstream of the heat exchanger .
11 T OOLS R EQUIRED Refrigeration gauge and manifold V oltmeter Clamp-on ammeter Ohmmeter T est lead (Minimum #16 A WG with insulated alligator clips) Air temperature measuring device General refriger.
12 t = Span length, inches C = Center distance, inches D = Larger sheave diameter , inches d = Smaller sheave diameter , inches h = Deflection height, inches DRIVE BELT TENSION ADJUSTMENT BE L T DR IV E Use d Ne w A , A X Sta nda r d 3.0 to 4 .0 4. 2 ± .
13 1 1. Slowly raise the heating temperature setting. When the heating first stage makes contact, stop raising the temperature setting.. The compressor , blower and fan should now be running with the reversing valve in the de-energized (heating) position.
14 E V A P O R A T O R COOLI NG SERV I C E VALVE SERVICE PO RT REVERSI NG VALVE C O N D E N S E R SERV I C E POR T COM PRES S OR SERV I C E POR T ACCUMULAT O R EXPANSION D EVI C E CH ECK VALVE ORI FI .
15 DRIVE ADJUSTMENTS MOTOR SHEA VE ADJUSTMENTS V L , V M , & 2 VP V ARIABLE P ITCH K EY T YPE M OTOR S HEAVES The driving and driven motor sheaves should be in align- ment with each other and the shaft s parallel. V L & V M S HEAVES A DJUSTMENT 1.
16 L UBRICATION The fan shaft bearings, the 1 to 2 HP supply fan motors the condenser fan motors and compressors are permanently lu- bricated. F UNCTIONAL P ARTS Refer to the unit Parts Catalog for a list of functional p arts. Parts are available from your distributor .
17 APPENDIX A BLOWER PERFORMANCE TABLES DIRECT DRIVE ST ANDARD DOWN SHOT AND HORIZONT AL SPE ED T A P E XTE RNAL S T AT IC PR E SS UR E ( ESP ) in w . c . S T A N DARD CFM A M PS WA T TS R PM 0. 10 1287 1 .66 3 50 770 0. 20 1233 1 .63 3 42 815 0. 30 1176 1 .
18 APPENDIX A BLOWER PERFORMANCE TABLES DIRECT DRIVE ST ANDARD DOWN SHOT AND HORIZONT AL SPE ED T A P E XTE RNAL S T AT IC PR E SS UR E ( ESP ) in w . c . S T A N DARD CFM A M PS WA T TS R PM 0. 10 1602 2 .48 5 28 835 0. 20 1538 2 .37 5 06 878 0. 30 1474 2 .
19 APPENDIX A BLOWER PERFORMANCE TABLES DIRECT DRIVE ST ANDARD CPC/H060 DOWN SHOT SP EED TAP E XTE RNAL S T ATIC PR E SSU R E ( ESP ) in w . c . S T ANDAR D CF M AM P S W ATTS R P M 0. 10 1 334 1.6 5 180 62 7 0. 20 1 286 1.7 5 192 66 5 0. 30 1 212 1.8 3 202 71 5 0.
20 APPENDIX A BLOWER PERFORMANCE TABLES DIRECT DRIVE ST ANDARD CPC/H060 HORIZONT AL SP EED TAP E XTE RNAL S T AT IC PR E SSU R E ( ESP ) in w . c . STANDAR D CF M AMP S W AT T S R PM 0. 10 1 355 1.57 174 59 9 0. 20 1 281 1.66 182 65 1 0. 30 1 235 1.76 196 69 3 0.
21 APPENDIX A BLOWER PERFORMANCE TABLES BEL T DRIVE ST ANDARD DOWN SHOT CP C/H0 36 ST AND AR D BEL T DR I VE DO W N SHO T CFM BHP C FM BHP CFM BH P CF M B HP C F M BHP CFM BH P 0. 2 1 42 4 0. 3 0 1 2 39 0. 2 3 0. 4 152 0 0. 39 1 292 0.2 9 10 73 0 .22 77 9 0 .
22 APPENDIX A BLOWER PERFORMANCE TABLES BEL T DRIVE HIGH ST A TIC DOWN SHOT CP C/H036 HI G H S T ATI C BE L T DRI V E DOWN S HOT CFM BHP C FM BHP CFM BH P CF M B HP C F M BHP CFM BH P 0. 6 16 9 2 0 . 54 1 44 9 0. 4 1 1 1 73 0. 2 9 0. 8 167 8 0. 58 1 397 0.
23 APPENDIX A BLOWER PERFORMANCE TABLES BEL T DRIVE ST ANDARD HORIZONT AL CP C/H036 STAND ARD BE L T DRI VE HORI Z O NT AL CFM BHP C FM BHP CF M BH P C FM B HP C FM BHP CFM BH P 0. 2 1 65 8 0. 3 5 1 4 89 0. 2 8 0. 4 1 560 0. 3 6 13 39 0 . 28 112 9 0 .
24 APPENDIX A BLOWER PERFORMANCE TABLES BEL T DRIVE HIGH ST A TIC HORIZONT AL CP C/H036 HI G H S T AT I C BE L T DRI VE HORIZO NT AL CFM BHP C FM BHP CFM BH P CF M B HP C F M BHP CFM BH P 0. 6 1 74 2 0. 5 0 1 4 31 0. 3 6 0. 8 16 2 6 0 . 52 1 35 7 0. 3 9 1 0 78 0.
25 APPENDIX B ELECTRICAL DA T A MIN. M AX . Q TY RLA LRA QTY H P R LA H P FLA 20 8 /2 3 0- 60 - 1 18 7 2 53 1 1 6. 6 7 7 9 1 1 / 4 1. 4 0 D D S T D S T A T I C 1 / 3 2. 5 DD S TD S TA T I C 1 / 3 2.5 BD ST D ST A T I C 1.0 3 .8 46 0- 60 -3 41 4 5 06 1 5 .
26 A TTENTION INST ALLING PERSONNEL Use only the heater kit specified for each model as dict ated by the table above. APPENDIX B ELECTRICAL DA T A UNIT HE AT ER KIT MO DE L NU M B ER MI N I MU M C F M.
27 APPENDIX C UNIT DIMENSIONS HORIZONTAL DISCHARGE VERTICAL DISCHARGE NOTE For horizontal discharge, remove the supply and return duct covers and place them over the vertical discharge return and supply openings. Install with insulation facing up, using the longer screws provided in the literature package.
28 Goodman Manufacturing Company , L.P . 5151 Felipe, Suite 500, Houston, TX 77056 www .goodmanmfg.com www .amana-hac.com © 2010,2012 Goodman Manufacturing Company , L.
デバイスGoodman Mfg CPC/CPHの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Goodman Mfg CPC/CPHをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはGoodman Mfg CPC/CPHの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Goodman Mfg CPC/CPHの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Goodman Mfg CPC/CPHで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Goodman Mfg CPC/CPHを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はGoodman Mfg CPC/CPHの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Goodman Mfg CPC/CPHに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちGoodman Mfg CPC/CPHデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。