INST ALLA TION INSTRUCTIONS W ARNING These instructions are intended as an aid to qualified licensed service personnel for proper installation, adjust- ment and operation of this unit. Read these instructions thoroughly before attempting installation or operation.
Cased/Uncased Coils INST ALLA TION INSTRUCTIONS Heat Contr oller , Inc. 1 1.0 MODEL NOMENCLA TURE .....................................................................................2 2.0 SAFETY .......................................................
Heat Contr oller , Inc. INST ALLA TION INSTRUCTIONS Cased/Uncased Coils 2 1.0 Model Nomenclature C D G 18 F A - A C = Uncased Coil M = Multi Postion Cased Coil Design Series R-410A Refrigerant 18 = 18.
Cased/Uncased Coils INST ALLA TION INSTRUCTIONS Heat Contr oller , Inc. 3 When you see the symbols below on labels or in manual, be alert to the potential or immediate hazards of personal injury , property and/or product damage.
Heat Contr oller , Inc. INST ALLA TION INSTRUCTIONS Cased/Uncased Coils 4 The unit can be positioned for bottom return air in the upow position, left and right return in the horizon - tal position, top return in downow position. 3.1 Codes & Regulations This product is designed and manufactured to comply with national codes.
Cased/Uncased Coils INST ALLA TION INSTRUCTIONS Heat Contr oller , Inc. 5 AUXILIARY DRAIN CONNECTION 3/4'' NPT FEMALE PIPE THREAD 3/4'' NPT FEMALE PIPE T HREAD A W 21'' 2.
Heat Contr oller , Inc. INST ALLA TION INSTRUCTIONS Cased/Uncased Coils 6 H The Max.resistant pressure of evaporator is up to 16MPa (2320PSI) TOP AIR STOP LIQUID LINE CONNECTION V APOR LINE CONNECTION W D AUXILIARY DRAIN CONNECTION 3/4'' NPT FEMALE PIPE THREAD PRIMARY DRAIN CONNETION 3/4'' NPT FEMALE PIPE THREAD The Max.
Cased/Uncased Coils INST ALLA TION INSTRUCTIONS Heat Contr oller , Inc. 7 4.0 Installation Instructions 4.1 Parts Contact your distributor for authorized replacement parts. 4.2 Pre-Installation Instructions Carefully read all instructions for installation prior to installing product.
Heat Contr oller , Inc. INST ALLA TION INSTRUCTIONS Cased/Uncased Coils 8 5.0 Drain Applications 5.1 Condensate Drain Piping Consult local codes for special requirements. T o provide extra protection from water damage, install an additional auxiliary drain pan, provided by installer under the entire unit with a separate drain line.
Cased/Uncased Coils INST ALLA TION INSTRUCTIONS Heat Contr oller , Inc. 9 Drain pan has two drain connections on each side to provide exibility of connection and drainage. Make sure pan has proper pitch and plugged if second connection is not used.
Heat Contr oller , Inc. INST ALLA TION INSTRUCTIONS Cased/Uncased Coils 10 6.0 Refrigerant Connections T o prevent refrigerant leak, use proper tools to ensure clean, burr-free cut. Use brazing shield when welding close to the cabinet surface and wet rag to protect rubber grommet.
Cased/Uncased Coils INST ALLA TION INSTRUCTIONS Heat Contr oller , Inc. 1 1 Condensing Unit Model No. HCI Indoor Coil PISTON SIZE Cased Coil Uncased Coil RSG18S-1D RSG18R-1D MDG18F A -A CDG18F A - A 0.050 MDG18FB-A CDG18FB- A RSG2 4S-1D RSG2 4R-1D MDG2 4F A- A CDG2 4F A - A 0.
04/2009 0 7 /201 1.
デバイスHeat Controller CDG SERIESの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Heat Controller CDG SERIESをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはHeat Controller CDG SERIESの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Heat Controller CDG SERIESの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Heat Controller CDG SERIESで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Heat Controller CDG SERIESを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はHeat Controller CDG SERIESの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Heat Controller CDG SERIESに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちHeat Controller CDG SERIESデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。