A.O. SmithメーカーDB/DW-720-1810の使用説明書/サービス説明書
ページ先へ移動 of 44
1 WITH ELECTRONIC INTERMITTENT PILOT IGNITION AND INST ALLA TIONS W ARNING: If the information in this manual is not followed exactly , a fire or explosion may result causing property damage, personal injury or loss of life. — Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
2 FOREWORD CA UTION TEXT PRINTED OR OUTLINED IN RED CONT AINS INFORMA TION RELA TIVE TO YOUR SAFETY . PLEASE READ THOROUGHL Y BEFORE USING APPLIANCE. Detailed installation diagrams are in this manual. These diagrams will serve to provide the installer with a reference for the materials and method of piping suggested.
3 W ARNING AN AMPLE SUPPL Y OF AIR MUST BE PROVIDED FOR PROPER COMBUSTION AND VENTILA TION. Minimum Clearances T o Combustibles Water Blank T op Side Side Rear V ent Front All Models 12" (305mm) 18" (457mm) 6" (155mm) 6" (155mm) 6" (155mm) Alcove CAUTION Label all wires prior to disconnection when servicing controls.
4 W ARNING Y our Dura-Max boiler is not designed to operate with a boiler inlet water temperature of less than 100 ° F (38 ° C). Colder inlet water temperatures will result in significant condensation developing on the heat exchanger .
5 FEA TURES IMPORT ANT Only qualified personnel shall perform the initial firing of the heater . At this time the user should not hesitate to ask the individual any questions regarding the operation and maintenance of the unit. Lighting and Operating instructions are included at the rear of this manual.
6 AUT OMA TIC RESET HIGH TEMPERA TURE LIMIT CONTROL CAUTION LIMIT CONTROLS ARE NOT TO BE USED AS THERMOST A TS. ALL MODELS - This limit is a safety device wired in series with the ignition system. Set the limit control dial to a minimum of 10 ° F (6 ° C) above the maximum designed system temperature.
7 INST ALLA TION INSTRUCTIONS REQUIRED ABILITY INST ALLA TION OR SERVICE OF THIS BOILER REQUIRES ABILITY EQUIV ALENT TO THA T OF A LICENSED TRADESMAN IN THE FIELD INVOL VED. PLUMBING, AIR SUPPL Y , VENTING, GAS SUPPL Y AND ELECTRICAL WORK ARE REQUIRED.
8 If the confined space is within a building of tight construction, air for combustion, ventilation, and draft hood dilution must be obtained from outdoors. When directly communicating with the outdoors or communicating with the outdoors through vertical ducts, two permanent openings, located in the aforementioned manner , shall be provided.
9 W ARNING F AILURE TO CORRECT BACK DRAFTS MA Y CAUSE AIR CONT AMINA TION AND UNSAFE CONDITIONS. V ent connectors serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under positive pressure.
10 T ABLE 5 Multipliers T o Be Used W ith T able 1 When Applying The Gravity Factor T o Other Than .60 Specific Gravity Specific Specific Gravity Multiplier Gravity Multiplier .35 1.31 1.00 .78 .40 1.23 1.10 .74 .45 1.16 1.20 .71 .50 1.10 1.30 .68 .55 1.
11 Applications of the gravity factor converts the figures given in table 1 to capacities with another gas of different specific gravity . Such application is accomplished by multiplying the capacities given in table 1 by the multipliers shown in table 5.
12 IF ANY OF THE ORIGINAL WIRE, AS SUPPLIED WITH THE APPLIANCE, MUST BE REPLACED, IT MUST BE REPLACED WITH TYPE 105 ° C WIRE OR ITS EQUIV ALENT , EXCEPT FOR THE FLAME SENSOR AND IGNITION CABLE WHICH ARE 250 ° C. SERVICING WIRING AND/OR CONTROL CAUTION Label all wires prior to disconnection when servicing controls.
13 The flow switch shall be mounted in the top opening of the reducing tee and provide adequate paddle length in the flow stream. For example in a 2" pipe installation use a 2" x 2" x 1" reducing tee. For 2" or 3" pipe use the paddle segments as supplied.
14 Thereafter , during the heating season, lubricate the three oil cups at least once every four months. Combination heating/cooling systems or water heating (Cer-temp) systems should be lubricated every four months year-round. Use 2 or 3 teaspoonfuls in bearing oil cups, fig.
15 A system bypass should be installed as shown in fig. 10 to prevent boiler circulation starvation when the system zones call for reduced flow . This bypass may also be used with multiple boilers manifolded for reverse-return flow . The system bypass would be installed from boiler outlet to suction side of pump.
16 NOTES: 1. BUILDING TEMPERA TURE CONTROLS SUPPLY ELECTRIC POWER T O BUILDING CIRCULA T OR. 2. MAIN FLOW SWITCH PROVES MAIN W A TER FLOW BEFORE ENERGIZING, SEQUENCING AND RESETTING CONTROLS. 3. OUTDOOR THERMOST A T REQUIRED IF BUILDING CONTROLS DO NOT PROVIDE AUTOMA TIC SHUT-DOWN OF RESET CONTROLS DURING W ARM WEA THER.
17 BYP ASS BALANCING With systems where water temperature can be expected to drop appreciably due to long standby periods, or heavy draw down, a bypass pipe of at least 1" size with a balancing cock should be installed between the boiler inlet and outlet (see fig.
18 generator type boilers establish temperature rises. The deciding factor in choice of boiler temperature rise relates to the boiler inlet temperature.
19 FIGURE 14 NO . SUGGESTED ITEMS FOR INST ALLA TION 1. SHORT PIPE NIPPLE AND P AIR OF BOILER LOOP TEES IN PIPING BETWEEN SYSTEM SUPPL Y AND RETURN - ONE SET PER EACH BOILER 2. BOILER PIPE LOOP (See Piping Sizing Data T able 3.) 3. BOILER CIRCULA TING PUMP (See Piping Sizing Data T able 3.
20 USE ONY TYPE 105 ° C THERMOPLASTIC OR ITS EQUIV ALENT IF ANY OF THE ORIGINAL WIRES AS SUPPLIED MUST BE REPLACED. USE ONY TYPE 105 ° C THERMOPLASTIC OR ITS EQUIV ALENT IF ANY OF THE ORIGINAL WIRES AS SUPPLIED MUST BE REPLACED.
21 DURA-MAX - PUMP MOUNT - SINGLE ST AGE - SCHEMA TIC DIAGRAM DURA-MAX - SINGLE ST AGE FIRING - UNITED ST A TES MODELS WITH PUMP . 120 VOL T SYSTEM CONTROLLER.
22 DURA-MAX - PUMP MOUNT - DUAL ST AGE - SCHEMA TIC DIAGRAM DURA-MAX - DUAL ST AGE FIRING - UNITED ST A TES MODELS WITH PUMP . 120 VOL T SYSTEM CONTROLLER.
23 DURA-MAX - PUMP MOUNTED - MODULA TING - SCHEMA TIC DIAGRAM DURA-MAX - MODULA TED FIRING - UNITED ST A TES MODELS WITH PUMP . 120 VOL T SYSTEM CONTROLLER.
24 DURA-MAX - SINGLE ST AGE FIRING - SCHEMA TIC DIAGRAM DURA-MAX - SINGLE ST AGE FIRING - UNITED ST A TES & CANADIAN MODELS WITHOUT PUMP . 120 VOL T SYSTEM CONTROLLER.
25 DURA-MAX - DUAL ST AGE FIRING - SCHEMA TIC DIAGRAM DURA-MAX - DUAL ST AGE FIRING - UNITED ST A TES & CANADIAN MODELS WITHOUT PUMP . 120 VOL T SYSTEM CONTROLLER.
26 DURA-MAX - MODULA TED FIRING - SCHEMA TIC DIAGRAM DURA-MAX - MODULA TED FIRING - UNITED ST A TES & CANADIAN MODELS WITHOUT PUMP . 120 VOL T SYSTEM CONTROLLER.
27 HOT W A TER SUPPL Y APPLICA TIONS Cer-T emp 80 Recovery Systems W A TER LINE CONNECTIONS This section provides detailed installation diagrams for typical methods of application for the unit using a Cer-T emp 80 Recovery System (for one temperature water).
28 ONE DURA-MAX (MODEL DW) COMMERCIAL BOILER WITH HORIZONT AL T ANK CAUTION TO PREVENT CONDENSA TION THE MINIMUM BOILER INLET TEMPERA TURE IS 100 ° F (38 ° C) IMPORT ANT SAFETY FLOW SWITCH AS SHOWN TO PROTECT THE BOILER IN CASE OF WA TER SERVICE INTERRUPTION OR CIRCULA TOR F AILURE.
29 TWO DURA-MAX (MODEL DW) HOT W A TER SUPPL Y BOILERS WITH VERTICAL T ANK CAUTION TO PREVENT CONDENSA TION THE MINIMUM BOILER INLET TEMPERA TURE IS 100 ° F (38 ° C) SEE P AGE 31 FOR ADDITIONAL PIPING INFORMA TION. CAUTION PUMP MUST BE RA TED FOR SYSTEM OPERA TING TEMPERA TURE AND PRESSURE .
30 TWO DURA-MAX (MODEL DW) HOT W A TER SUPPL Y BOILERS WITH HORIZONT AL T ANK CAUTION TO PREVENT CONDENSA TION THE MINIMUM BOILER INLET TEMPERA TURE IS 100 ° F (38 ° C) IMPORT ANT THE INST ALLA TION OF SAFETY FLOW SWITCHES AS SHOWN IS REQUIRED TO PROTECT THE BOILER IN CASE OF W A TER SERVICE INTERRUPTION OR CIRCULA TO R F AILURE.
31 FIGURE 24 MANIFOLDING OF MODEL TJV-120M & TJV-200M T ANKS NOTE: PIPE SIZES BETWEEN MANIFOLDS AND BOILER(S) TO BE SELECTED FROM THE CER-TEMP 80 DIAGRAM FOR THE HEA TER MODEL TO BE INST ALLED. ALL PIPING FROM TEES TO BE EQUIDIST ANT TO T ANKS. INST ALL IN ACCORDANCE WITH ALL LOCAL CODES.
32 ST ART-UP AND OPERA TING INSTRUCTIONS W ARNING After placing boiler into operation, the ignition system safety shutoff device must be tested by the following test method. 1. Reset Manual High T emperature Safety Limit Control (High Limit) to the lowest setting.
33 LIGHTING AND OPERA TING INSTRUCTIONS WARNING: HOT W A TER CAN PRODUCE 3rd DEGREE BURNS IN 6 SECONDS A T 140 ° F . (60 ° C). IN CASE OF POWER F AILURE DO NOT A TTEMPT TO OPERA TE BOILER. IMPROPER INST ALLA TION, ADJUSTMENT , AL TERA TION, SERVICE OR MAINTENANCE CAN CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
34 INTERNAL CONT AMINANTS The system must be internally cleaned and flushed after a new or replacement unit has been installed to remove contaminants that may have accumulated during installation. This is doubly important when a replacement unit is installed into an existing system where Stop Leak or other boiler additives have been used.
35 1. Remove main burners from unit. 2. Check that burner venturi and ports are free of foreign matter . 3. Clean burners with bristle brush and/or vacuum cleaner 3/4" DO NOT distort burner ports or pilot location. 4. Reinstall burners in unit. Making sure front and rear of burners are installed correctly in burner support brackets.
36 CHECKING HONEYWELL S8600H OR S8610M (NA T . GAS) INTERMITTENT IGNITION CONTROLS NO SP ARK A T PILOT BURNER NO Replace ignition module Is voltage (24 V ac) across the 24 V terrminals on module durin.
37 SP ARK A T PILOT BURNER BUT PILOT WILL NOT LIGHT Ensure all manual shutoff valves are fully open; All filters are clean; All gas connections are gas tight; Pilot tubing is not damaged, obstructed or kinked; and pilot orifice is unclogged. Check for air in gas line, purge (bleed) line if necessary .
38 PILOT BURNER LIGHTS BUT MAIN BURNER DOES NOT LIGHT Correct the situation by consulting N O the installation or user ’ s manual Does the pilot flame cover 3/8 ° to 1/2" on how to adjust pilot flame. (10 mm to 12 mm) of igniter/sensor rod? YES Replace ignition NO NO module.
39 CAUTION DO NOT USE A NYLON BRUSH OR OTHER ST A TIC CREA TING MA TERIAL TO CLEAN DUST AND CARBON DEPOSITS FROM HEA TING SURFACES AND VENT . SUCH DEPOSITS ARE FLAMMABLE AND MA Y BE IGNITED BY ST A TIC ELECTRICITY . USE A MET AL BRUSH TO MINIMIZE THE DANGER OF EXPLOSION 1.
40 The time between cleaning will vary from two to six months depending upon water conditions and usage. A change of approximately 5 ° F in the normal temperature rise through the boiler is usually an indication that scale should be removed.
41 DURA-MAX LIMITED W ARRANTY A. O. Smith Corporation, the warrantor, extends the following LIMITED W ARRANTY to the owner of this hydronic boiler: 1. If within TEN years after initial installation of.
42.
43.
44 REPLACEMENT P ARTS 5621 W . 1 15TH STREET , ALSIP , IL 60803 PHONE: 800-433-2545 F AX: 800-433-2515 ww w .hotwater .com E-Mail: parts@hotwater .com.
デバイスA.O. Smith DB/DW-720-1810の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
A.O. Smith DB/DW-720-1810をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはA.O. Smith DB/DW-720-1810の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。A.O. Smith DB/DW-720-1810の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。A.O. Smith DB/DW-720-1810で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
A.O. Smith DB/DW-720-1810を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はA.O. Smith DB/DW-720-1810の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、A.O. Smith DB/DW-720-1810に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちA.O. Smith DB/DW-720-1810デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。