A.O. SmithメーカーDREの使用説明書/サービス説明書
ページ先へ移動 of 28
1 COMMERCIAL ELECTRIC W A TER HEA TERS CAUTION TEXT PRINTED OR UNDERLINED IN RED CONT AINS INFORMA TION RELA TIVE TO YOUR SAFETY . PLEASE READ THOROUGHL Y BEFORE A TTEMPTING ANY CONVERSION. PRINTED IN U.S.A. 0906 P ART NO. 196674-001 A DIVISION OF A.O.
2 Rough-in-Dimensions Model Number T ank Cap acity in Gallons A B Inlet/Outlet DRE/DVE-52 50 55 1/4 21 3/4 1 1/4 DRE/DVE-80 80 59 1/2 25 1/4 1 1/4 DRE/DVE-120 1 19 62 1/4 29 1/2 1 1/4 Get to know your.
3 Contents Page ROUGH-IN-DIMENSIONS ....................................... 2 GET TO KNOW YOUR W ATER HEA TER ............... 2 RECOVERY CAP ACITY ........................................... 3 APPROV ALS ...............................................
4 Model and Rating Foreword Detailed installation diagrams are in this manual. These diagrams will serve to provide the installer with a reference for the materials and method of piping suggested. IT IS NECESSARY THA T ALL W A TER PIPING AND THE ELECTRICAL WIRING BE INST ALLED AND CONNECTED AS SHOWN IN THE DIAGRAMS.
5 Inst allation REQUIRED ABILITY INST ALLA TION OR SERVICE OF THIS W A TER HEA TER REQUIRES ABILITY EQUIV ALENT TO THA T OF A LICENSED TRADESMAN IN THE FIELD INVOL VED. PLUMBING AND ELECTRICAL WORK ARE INVOL VED. GENERAL The installation must conform to these instructions and the local code authority having jurisdiction.
6 The pressure setting of the relief valve should not exceed the pressure capacity of any component in the system. The temperature setting of the relief valve should not exceed 210°F . An unplugged 3/4" relief valve opening is provided for installing temperature and pressure relief valve.
7 Piping Diagrams ONE TEMPERA TURE WITH CIRCULA TING LOOP INSERT B V ACUUM RELIEF V AL VE. INST ALL PER LOCAL CODES. CAUTION: IF BUILDING COLD W ATER SUPPL Y HAS A BACK- FLOW PREVENTER, CHECK V A L VE OR WA TER METER WITH CHECK V A L VE. PROVISIONS FOR THERMAL EXP ANSION OF W A TER IN THE HOT W A TER SYSTEM MUST BE PROVIDED.
8 INSER T B V ACUUM RELIEF V AL VE. INST ALL PER LOCAL CODES. DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERA TURE A T FIXTURES. SEE WA TER TEMPERA TURE CONTROL WARNING ON P AGE 6. IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY T O O BTAIN ADEQUATE BOOSTER OUTPUT , A DD AN ANTI-SCALD V AL VE FOR HOT WA TER SUPPLIED TO FIXTURES.
9 INSER T B V ACUUM RELIEF V AL VE. INST ALL PER LOCAL CODES. DANGER TEMPERA TURE SETTING SHOULD NOT EXCEED SAFE TEMPERA TURE AT FIXTURES. SEE W A TER TEMPERATURE CONTROL WARNING ON P AGE 6. IF HIGHER PREHEAT TEMPERA TURES ARE NECESSARY TO OBT AIN ADEQUA TE BOOSTER OUTPUT , ADD AN ANTI-SCALD VA LVE FOR HOT WA TER SUPPLIED T O FIXTURES.
10 ONE TEMPERA TURE ONE HEA TER VERTICAL ST ORAGE T ANK FORCED CIRCULA TION WITHOUT BUILDING RECIRCULA TION TWO TEMPERA TURE WITH MIXING V AL VE AND CIRCULA TING LOOP INSER T B V ACUUM RELIEF V ALVE.
11 INSER T B V ACUUM RELIEF V ALVE. INST ALL PER LOCAL CODES. DANGER TEMPERA TURE SETTING SHOULD NOT EXCEED SAFE TEMPERA TURE A T FIXTURES. SEE WA TER TEMPERA TURE CONTROL WARNING ON P AGE 6. IF HIGHER PREHEA T TEMPERA TURES ARE NECESSAR Y TO OBT AIN ADEQUA TE BOOSTER OUTPUT , ADD A N ANTI-SCALD VAL VE FOR HOT W A TER SUPPLIED TO FIXTURES.
12 DANGER TEMPERA TURE SETTING SHOULD NOT EXCEED SAFE TEMPERA TURE A T FIXTURES. SEE WA TER TEMPERA TURE CONTROL WARNING ON P AGE 6. IF HIGHER PREHEA T TEMPERA TURES ARE NECESSAR Y TO OBT AIN ADEQUA TE BOOSTER OUTPUT , ADD A N ANTI-SCALD VAL VE FOR HOT W A TER SUPPLIED TO FIXTURES.
13 INSER T B V ACUUM RELIEF V AL VE. INST ALL PER LOCAL CODES. DANGER TEMPERA TURE SETTING SHOULD NOT EXCEED SAFE TEMPERA TURE A T FIXTURES. SEE WA TER TEMPERA TURE CONTROL WARNING ON P AGE 6. IF HIGHER PREHEA T TEMPERA TURES ARE NECESSAR Y TO OBT AIN ADEQUA TE BOOSTER OUTPUT , ADD A N ANTI-SCALD VAL VE FOR HOT W A TER SUPPLIED TO FIXTURES.
14 MANIFOLD KITS ALL DIMENSIONS IN INCHES. TWO HEA TERS Part Model Number H W D A DRE/DVE-52 9003429 66 1/4 56 3/4 27 1/4 13 1/4 DRE/DVE-80 9003429 70 1/2 60 1/4 31 1/4 9 3/4 DRE/DVE-120 9003429 73 1/.
15 BRANCH CIRCUIT The branch circuit wire and fuse size should be established through reference to the current version of the National Electrical Code or any other locally approved source in conjunction with the heater amperage rating. Branch circuit wires should have a temperature rating no less than 75°C.
16 Full Load Current in Amperes KW Number of Element Single Phase Three Phase No. of No. of Input Elements W attage 208V 240V 277V 480V 208V 240V 480V Thermostat s Fuses 6 2000 28.8 25.0 21.7 12.5 16.7 14.4 7.2 9 3000 43.3 37.5 32.5 18.8 25.0 21.7 10.
17 DVE CONTROL CIRCUIT DIAGRAMS.
18 POWER CIRCUIT The power circuit wiring is 12 Awg. AWM or TEW type, rated 600 volts, 105°C. Power circuit fusing consists of three 30 amp class G fuses for each contactor .
19 CONVERSION TO SINGLE PHASE When the heater is shipped for connection to a three-phase electrical service, it may be connected to a single-phase electrical service of the same voltage by: 1. Disconnect blue wires and yellow wires from terminal L3. 2.
20 HEA TER CIRCUITS—DRE MODELS The water heater's electrical components are pictured and identified on pa ge 2. The following describes the heater circuits and includes wiring diagrams. All heater circuits are designed for 60/50 hertz alternating current.
21 CONVERSION TO SINGLE PHASE When the heater is shipped for connection to a three-phase electrical service, it may be connected to a single-phase electrical service of the same voltage by: 1. Disconnect blue wires and yellow wires from terminal L3. 2.
22 Operation GENERAL Never turn on power to the water heater without being certain the water heater is filled with water , and a temperature and pressure relief valve is installed in the relief valve opening. DO NOT TEST ELECTRICAL SYSTEM BEFORE HEA TER IS FILLED WITH W A TER.
23 MAINTENANCE SCHEDULE Component Operation Interval Required T ank Flushing Periodically Un•Lime ® Element s Lime Scale As needed delimer & Removal element gaskets, Part Anode Inspect As needed T ank flushing should be performed in accordance with the above schedule.
24 12. Attach element wires to connection point s from which they were removed. 13. Follow FILLING instructions to restore hot water service. • Check for water leaks around elements and proper operation when heater is filled. • Close the front panel.
25 Leakage Checkpoint s INSTRUCTIONS: USE THIS ILLUSTRA TION AS A GUIDE WHEN CHECKING FOR SOURCES OF W A TER LEAKAGE. YOU OR YOUR DEALER MA Y BE ABLE TO CORRECT WHA T APPEARS TO BE A PROBLEM. Where possible, remove or lift top cover to examine threads of fittings installed into tank for evidence of leakage.
26 A. O. Smith Corporation, the warrantor, extends the following LIMITED W ARRANTY to the owner of this water heater: 1. THE T ANK If the glass-lined tank in this water heater shall prove upon examina.
27.
28 McBee, South Carolina 29101 Phone: 1-800-527-1953 Fax: 800-433-2515 w w w .hotwater .com e-mail: p ar ts@hotwater .com.
デバイスA.O. Smith DREの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
A.O. Smith DREをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはA.O. Smith DREの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。A.O. Smith DREの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。A.O. Smith DREで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
A.O. Smith DREを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はA.O. Smith DREの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、A.O. Smith DREに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちA.O. Smith DREデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。