PRODUCT DA T A ® U.S. Registered Trademark Copyright © 1997 Honeywell Inc. • All Rights Reserved D896 Automatic V ent Damper GENERAL D896 Automatic V ent Dampers are used with atmospheric type, gas-fired equipment to reduce home heating losses b y closing off the vent betw een heat cycles.
D896 A UT OMA TIC VENT D AMPER 68-0186 2 ORDERING INFORMA TION When purchasing replacement and modernization products from your TRADELINE® wholesaler or distr ibutor , ref er to the TRADELINE® Catalog or price sheets for complete ordering number .
D896 A UT OMA TIC VENT D AMPER 68-0186 3 NO TE: A minimum of a 30 V A transf or mer must be used when D896 is installed with S86/S8600/S8610/ S8620. Electrical Connections: F our-wire plug receptacle. Thermostat Anticipator Setting: 0.13A. Operating Times: Appro ximate Damper Opening Time: 30 seconds.
D896 A UT OMA TIC VENT D AMPER 68-0186 4 IMPORT ANT 1. The atmospheric draft hood outlet area must be smaller or equal to the inlet area of the damper assembly . 2. If a second gas valv e needs to be installed, refer to the gas valv e manufacturer instructions f or the procedure.
D896 A UT OMA TIC VENT D AMPER 68-0186 5 Fig. 3. Installing D896 V ent Damper . IMPORT ANT Ne ver mount the vent damper with the motor actuator abov e or below the vent. Do not install the damper blade plug if the v ent damper is installed on a system with a continuous or standing pilot.
D896 A UT OMA TIC VENT D AMPER 68-0186 6 Fig. 5. D896 with co ver off. Honeywell D892/D896 Wires Honeywell D80B Wires Johnson Q35 Wires EFFIKAL RVG Wires Yellow Orange Green 1 Orange Blue and Red Whit.
D896 A UT OMA TIC VENT D AMPER 68-0186 7 MV MV/PV PV GND (BURNER) 24V GND 24V SPARK S8600F, H, M; S8610F,H POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. REMOVE PLUG ONLY IF USING VENT DAMPER. FUSE BLOWS ON STARTUP WHEN PLUG IS REMOVED; THEN MODULE OPERATES ONLY WHEN VENT DAMPER IS CONNECTED.
D896 A UT OMA TIC VENT D AMPER 68-0186 8 Fig. 10. Snap-Tite™ Bo x Connector release. Checkout Heating 1. Tu rn on the po wer supply . 2. If using a thermostat, set the heat anticipator at 0.13A. 3. Set the thermostat or controller to 10 ° F (6 ° C) above the room temperature to call f or heat.
D896 A UT OMA TIC VENT D AMPER 68-0186 9 Thermostat Setting Symptom Possible Cause Action Set thermostat 10°F above room temperature to call for heat. No response from D896. Incorrect wiring or blown fuse. • Check the circuit breaker or fuse and, if necessary, reset or replace.
D896 A UT OMA TIC VENT D AMPER 68-0186 10 ANSI ST ANDARDS EXHIBIT A Procedure For Saf ety Inspection of an Existing Appliance Installation The f ollowing procedure is intended as a guide to aid in determining that an appliance is proper ly installed and is in a safe condition f or continuing use.
D896 A UT OMA TIC VENT D AMPER 68-0186 11 EXHIBIT B Procedure f or Installing Electrically Operated Automatic Vent Damper De vices on Existing Appliances This procedure is intended as a guide to aid in safely installing an electrically operated or mechanically actuated automatic vent damper de vice on an existing appliance .
D896 A UT OMA TIC VENT D AMPER 68-0186 12 Honeywell Europe S.A. 3 Avenue du Bourget B-1140 Brussels Belgium Honeywell Asia Pacific Inc. Room 3213-3225 Sun Hung Kai Centre No.
デバイスHoneywell D896の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Honeywell D896をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはHoneywell D896の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Honeywell D896の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Honeywell D896で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Honeywell D896を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はHoneywell D896の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Honeywell D896に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちHoneywell D896デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。