Honeywell M9484 AND M9494 MODUTROL MOTORS ARE LOW VOLTAGE, REVERSING PROPORTIONAL CONTROL ACTUATORS FOR VALVES, DAMPERS AND AUXIL- IARY EQUIPMENT. THEY ARE ESPECIALLY DE- SIGNED FORCOMMERCIALOR INDUSTRIALOILOR GAS BURNER CONTROL SYSTEMS. •i Replace M941 motors.
STANDARD MODELS control Type T TTLix Letter 94 is Series 90 ~~ I Power Rating 8 is high torque 150 lb.-in. at standard timing 9 is high torque 300 lb.-in.
AUXILIARY SWITCH RATINGS (amperes): M94XXE has 1 spdt switch. M94XXF has 2 spdt switches. ONE CONTACT a 120v 240v Full Load 7.2 3.6 Locked Rotor 43.2 21.6 a4O VA pilot duty, 1201240 Vat on opposite contact. DIMENSIONS: See Fig. 1. UNDERWRITERS LABORATORIES INC.
f--- 5.37 [136] ADAPTER BRACKET FIG. 1-UIMtNSIUNS IN In. NOTE: M9481, M9491 do not have auxiliary shaft. All other dimensions are the same. LOCATION install the Modutrol motor in any locatio n except .
NON SPRING RETURN MOTORS E373C FIG. 2-LIMITS OF MOTOR ROTATION. ADAPTER BRACKET The220738A Adaptor Bracket, positioned between the motor and the equipment, raises the shaft height ptthe- M9484 motor by 0.
Y BOLTS PROVIDED (4) WIRING BOX MOTOR MACHINE SCREWS OR BOLTS. LTS SECURING BRACKET TO LINKAGE. M 31% TIGHTEN AFTER SECURING MOTOR TO THE BRACKET USING FOUR BOLTS PROVIDED. FIG. 4-MOTO R MOUNTIN G O N VALVE LINKAGE,. 4. Do not exceed the motor ratings in any installation.
CLOSE LIMIT D I R E CTION OF MOTOR TRAVEL AS VIEWED FROM POW E R E N D . & CONNECT 24V POWER TO Tl-T2 TERMINALS ONLY. DO NOT CONNECT POWER SUPPLY TO CONTROLLER TERMINALS. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. n 3 TURN LIMIT POT FULL CLOCKWISE~FOR 160’ STROKE, FULL COUNTERCLOCKWISEr?FOR 90’ STROKE.
AUXILIARY SWITC H CONNECTIONS supplies to de-energize the The M9484E has 1 internal auxiliary switch. The switch wires are color-coded as follows: solid yellow-normally closed (N.C.); solid red-common (COM.); solid blue-normally open (N.O.). The M9484F has 2 internal auxiliary switches which may be used to prove low fire and high fire positions.
MOVE SCREWDRIVE R AT TOP ONLY TO ADJUST CAM: l/8 IN . STRAIGHT BLADE SCREWDRIVER OUTER STROKE OUTER CAM ADJUST CAMS RY SWITCH CAMS A 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. A 2 TRANSFORMER MAY BE EXTERNAL OR INTERNAL.
IMPORTANT Set cams by moving top of screwdriver only. Press- ing screwdriver against sides of cam slots could cause damage to motor end switches. 4. Insert l/ 8 in. screwdriver blade into slot on outer yellow cam and MOVE TOP OF SCREWDRIVER as far as possible clockwise n .
n 1 POWER SUPPLY. PROVlDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. n 2 TRANSFORMER MAY BE INTERNAL OR EXTERNAL TO MOTOR. EJ74C SPDT SWITCH OR SERIES 60 CONTROLLER USED A S A I TRANSFORMER 1 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REOUIRED.
4074EED RESISTOR SELECTION CHART FOR 4-20 mA MIINIMUM OUTPUT VOLTAGE REQUIRED MOTORS (Vdc)b RESISTOR (A) (Ohms) Part No. 1 1.7 237 80213QCDHA 2 2.0 150 802139BFAA : 2.
デバイスHoneywell M9481の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Honeywell M9481をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはHoneywell M9481の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Honeywell M9481の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Honeywell M9481で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Honeywell M9481を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はHoneywell M9481の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Honeywell M9481に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちHoneywell M9481デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。