T874G Thermostats and Q674F ,J Subbases for Heat Pump Systems J.H. • Rev. 7-94 • • ©Honeywell Inc. 1994 • Form Number 69-0435—10 TRADELINE ® TABLE 1—THERMOSTAT/SUBBASE SPECIFICATIONS.
69-0435—10 2 IMPORTANT: Thermostats are calibrated at the factory by using subbases mounted at true level. Inaccurate sub- base leveling will cause thermostat control deviation. LOCATION Install the thermostat about 5 ft [1.5 m] above the floor in an area with good air circulation at average temperature.
3 69-0435—10 Fig. 2—Installation of Q674 Subbase on wall. WIRES THROUGH WALL OPENING WALL WALL ANCHORS (2) SUBBASE MOUNTING HOLES MOUNTING SCREWS (2) M926 Fig.
69-0435—10 4 Fig. 5—Internal schematic and typical wiring diagram for Y594G1252 (T874G1246/Q674F1212); auto changeover in cooling. H2 FALL L1 (HOT) L2 1 R W3 W2 X L G O E Y RTD1 OTD1 EHR1 ODT2 EHR2 RTD2 RTD3 RTD1 SYSTEM MONITOR FAN RELAY RD COOL CHANGEOVER VALVE EM.
5 69-0435—10 Fig. 7—Internal schematic and typical wiring diagram for Y594G1419 (T874G1642/Q674F1444), Y594G1476 (T874G1741/Q674F1477) and Y594G1534 (T874G1824/Q674F1477 sold only in Australia); auto changeover in heating and cooling; fixed anticipation.
69-0435—10 6 Fig. 8—Internal schematic and typical wiring diagram for Y594G1526 (T874G1626/Q674F1436); auto changeover in heating. M1592A (HOT) L1 L2 1 LACO CHP Y B E G L X W2 R ODT 1 RTD 1 EHR 1 RTD 2 ODT 2 EHR 2 RTD 3 RD COMPRESSOR FAILURE FAN RELAY COMPRESSOR CONTACTOR HEAT CHANGEOVER VALVE EM.
7 69-0435—10 Fig. 10—Internal schematic and typical wiring diagram for Y594G1567 (T874G1865/Q674J1209) and Y594G1575 (T874G1873/Q674J1225); auto changeover in cooling. Exact replacement for York model nos. 2TH11702424 and 6TH11702424. EM. HT. AUX.
69-0435—10 8 MOUNTING THE THERMOSTAT 1. Remove the thermostat cover by pulling the bot- tom edge of the cover away from the base until it snaps free of the retaining posts. NOTE: The cover is hinged at the top and must be removed by pulling out at the bottom.
9 69-0435—10 Checkout HEATING Move the system switch on the Q674 Subbase to HEAT. Move the heating set point lever on the T874 Thermostat about 10 ° F [6 ° C] above room tempera- ture. Both stages of heating and fan should start. Move the set point lever about 10 ° F [6 ° C] below room temperature.
69-0435—10 10.
11 69-0435—10.
Home and Building Control Home and Building Control Honeywell Honeywell Limited—Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, Minnesota 55422 Scarborough, Ontario M1V 4Z9 69-0435–10 Printed in U.
デバイスHoneywell Q674F,Jの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Honeywell Q674F,Jをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはHoneywell Q674F,Jの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Honeywell Q674F,Jの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Honeywell Q674F,Jで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Honeywell Q674F,Jを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はHoneywell Q674F,Jの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Honeywell Q674F,Jに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちHoneywell Q674F,Jデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。