INTEGRATION MANUAL Put Bar Code Here 63-4524-01 BACnet Integration Manual for TB7200 & TB7300 Series Thermost at s TB7200 Series Thermostat TB7300 Series Thermostat with Occupanc y Sensor Contents Product Overview ............ ........... ........
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 63-4524—0 1 2 COMP ATIBILITY Honeywell TB7200 and TB7300 Series the rmostat compatiblity information is p rovided in T able 1. T able 1. TB7200 Series and TB7300 Series Thermostat Comp atib ility Information * 128 total devices supported.
BACNET INTEGRATION MANUAL F OR TB7200 & TB7300 SERIES THERMOSTATS 3 63-4524—01 • T o assign a Room T emperature (A V7) value ma nually , users must first enable the Override mode in the Room T emp Override (BV8) object.
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 63-4524—0 1 4 Cable T ype Honeywell recommends the use of balan ced 22-24 AWG twist ed pair with a characteristic imp edance of 100-130 ohms, capacitance of 30 pF/f t or lower . A braided shield is also recommended .
BACNET INTEGRATION MANUAL F OR TB7200 & TB7300 SERIES THERMOSTATS 5 63-4524—01 NETWORK CONFIGURATION EIA-485 networks use a daisy chain configurat i on. A daisy chain means that there is only o ne main cable and every network device is connected directly along its path.
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 63-4524—0 1 6 Maximum Cable Length The maximum length of a chain is related to its transmission speed . The lon ger the chain, the sl owe r the speed. Using proper cable, the maximum length of an EIA-485 daisy cha in is 4000-ft (1200 m).
BACNET INTEGRATION MANUAL F OR TB7200 & TB7300 SERIES THERMOSTATS 7 63-4524—01 End Of Line (EOL) Resistors MS/TP network must be prop erly terminated. Fo r daisy chain configu rations, you must inst all an EOL resistor at each end of the daisy chain.
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 63-4524—0 1 8 NETWORK ADAPTER The polarity of the connection to the cable is impo rtant. From one module to th e other it is important that the same colored wi re be connected to “pl us” or “+” and the o ther colored wire b e c onnected to the “minus” or ”-“.
BACNET INTEGRATION MANUAL F OR TB7200 & TB7300 SERIES THERMOSTATS 9 63-4524—01 INTEGRATION Global Commands The following figure shows which objects from the thermostat can be monitored and commande d from the BAS front-end. Fig. 6. Global commands from a BAS fron t-e nd to a typical TB7300 Series thermostat.
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 63-4524—0 1 10 TB7200 Integration – Graphical User Interface (GUI) object s The following objects sho uld be typically used in .
BACNET INTEGRATION MANUAL F OR TB7200 & TB7300 SERIES THERMOSTATS 11 63-4524—01 TB7300 Integration – Graphical User Interface (GUI) Object s The following objects should be typically used in a.
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 63-4524—0 1 12 Configuration Object s The following objects and group objects should be typically used for configu ration purpose.
BACNET INTEGRATION MANUAL F OR TB7200 & TB7300 SERIES THERMOSTATS 13 63-4524—01 Graphical interfaces For example, some graphic interface mig ht poll every data linked to the graphic page on a COV basi s.
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 63-4524—0 1 14 T ROUBLESHOOTING Error / Tr ouble Condition Possible Cause Solution Thermostat does not come online Two or more control lers have the same MAC address. Modify each duplicate address to a unique number.
BACNET INTEGRATION MANUAL F OR TB7200 & TB7300 SERIES THERMOSTATS 15 63-4524—01 APPENDIX TB7200 & TB7300 Series Protocol Im plement ation Conf ormance St atement (PICS) V endor Name: Honeywe.
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 63-4524—0 1 16 BACNET OBJECTS SUPPORTED Device Object s T able 4. Device Object s. Object Name Type and Instance Object Property Thermostat Parameter TB7200X5x14B TB73xxX5X14B Device Object_Identifier Property 75 (R,W) Unique ID number of a device on a network.
BACNET INTEGRATION MANUAL F OR TB7200 & TB7300 SERIES THERMOSTATS 17 63-4524—01 Object s T able T able 5. Objec t s. Object Name Type and Instance Object Property TB7200C5x14B TB7200F5x14B TB730.
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 63-4524—0 1 18 Filter Alarm BI 36 Present_Va lue (R) Service Alarm BI 37 Present_Value (R) .
BACNET INTEGRATION MANUAL F OR TB7200 & TB7300 SERIES THERMOSTATS 19 63-4524—01 Proportional Band MV 65 Present_Value (R,W) Auto Fan BV 66 Present_Value (R,.
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 63-4524—0 1 20 S t andard Object T ypes Supported T a ble 6. St andard object types supported.
BACNET INTEGRATION MANUAL F OR TB7200 & TB7300 SERIES THERMOSTATS 21 63-4524—01 Property V alue Ra nge Restrictions T able 8. Property value range restrictions. Object name Object Type and inst ance Minimum range value Maximum range value Default value Room Temperature AV 7 -39.
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 63-4524—0 1 22 Property Enumeration Set s for BV & BI Object s T able 9. Prop erty enumeration sets for BV and BI object s. (**) This object will be linked to the value of the “UI 3 Conf iguration” obje ct.
BACNET INTEGRATION MANUAL F OR TB7200 & TB7300 SERIES THERMOSTATS 23 63-4524—01 Enumeration Set s for MV Objects T able 10. Proper ty enumera tion sets fo r MV objects . NOTES: 1. Enumeration sets for MV16 depends on Sequence of Operation (MV15) value upon device discovery .
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 63-4524—0 1 24 T able 10. Property e numeratio n sets for MV objects. (Continued) 6. Enumeration sets for MV26 depends on Control T ype (BV75) value and Pipe Numbe r (MV52) value upon device dis- covery .
BACNET INTEGRATION MANUAL F OR TB7200 & TB7300 SERIES THERMOSTATS 25 63-4524—01 BV75 Value MV52 Ind ex MV27 Object Name Function MV26 State Text Index Defau lt Value On/Off 1 (2 pipe) Heat/Cool .
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS 63-4524—0 1 26 Fan Mode Sequence MV 58 1 Low-Med-High On-Auto 2 Low-High 3 Low-Med-High-Au to 4 Low-High-Auto 5O n - A u t o Temp.
BACNET INTEGRATION MANUAL F OR TB7200 & TB7300 SERIES THERMOSTATS 27 63-4524—01 Floating Motor Timing MV 76 1 0.5 minute 1.5 minutes 2 1 minute 3 1.5 minutes 4 2 minutes 5 2.5 minutes 6 3 minutes 7 3.5 minutes 8 4 minutes 9 4.5 minutes 10 5 minutes 11 5.
BACNET INTEGRATION MANUAL FOR TB7200 & TB7300 SERIES THERMOSTATS Automation and Control Solutions Honeywell International Inc. 1985 Douglas D rive North Golden Valley, MN 55422 Honeywell Limi ted-Honeywell Limi tée 35 Dynamic Drive Toronto, Ontario M1V 4Z9 customer.
デバイスHoneywell TB7200の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Honeywell TB7200をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはHoneywell TB7200の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Honeywell TB7200の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Honeywell TB7200で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Honeywell TB7200を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はHoneywell TB7200の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Honeywell TB7200に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちHoneywell TB7200デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。