A.O. SmithメーカーFDVの使用説明書/サービス説明書
ページ先へ移動 of 24
1 Thank you for buying this energy efficient water heater from A.O. Smith Water Products Company . We appreciate your confidence in our products. Y ou should thoroughly read this manual before installation and/or operation of this water heater .
2 CERT AIN MODELS ARE EQUIPPED WITH SIDE PLUMBING CONNECTIONS FOR SP ACE HEA TING. THE HOT AND COLD FITTING ASSEMBLIES (P ART #900126-2) CAN BE ORDERED THROUGH THE MANUFACTURER. REPLACEMENT P ARTS Replacement parts may be ordered through authorized servicers or distributors.
3 GENERAL SAFETY INFORMA TION EXTERNAL DAMAGE Do not operate the water heater until it has been fully checked out by a qualified technician, if the water heater: • Has been exposed to fire or damage. • Displays evidence of sooting. • Produces steam or unusually hot water .
4 the heater . Such pans should have a minimum length and width of at least 2 inches greater than the diameter of the heater and should be piped to an adequate drain. Drain pans suitable for these heaters are available from your dealer or A. O. Smith Water Products Company , 5621 W .
5 torque when attaching gas supply pipe to thermostat gas inlet. The thermostat inlet has a pad for use with a backup wrench. Apply joint compounds (pipe dope) sparingly and only to the male threads of pipe joints. Do not apply compound to the first two threads.
6 FIGURE 5 FIGURE 6 FIGURE 7 FIGURE 8 FLUE EXTENSIONS There are three optional extension kits available. Any combination of the three kits can be chosen; however , only one kit can be used vertically and/or horizontally . (See Figures 10 and 1 1.) VENTING CLEARANCES • 18” minimum in all directions from any obstruction that may interfere.
7 W ARNING At no time can more than one V ertical and/or one Horizontal V ent Kit be used. VERTICAL (EXTENSION KIT) HEIGHT It is simple to determine which kit is needed for vertical height.
8 T ABLE 2. *See models and rating plate attached to the water heater for specific model number and other detailed information. W ARNING Be sure vent pipe is properly connected to prevent escape of dangerous flue gases which could cause deadly asphyxiation.
9 4. First remove the 3” horizontal extension from the elbow . Starting with the long end (with four securing holes), place the 6” diameter vent elbow over the 3” diameter elbow . Bend the round end “oval” to fit the flared oval end of the jacket top.
10 FIGURE 26 12 . Four wood screws are supplied to temporarily attach the collar to the exterior wall of the building. However , other types of screws may have to be substituted depending on the material used in the construction of the exterior wall. FIGURE 27 13.
11 Use the simple equation below, chart and drawing to find the length of expansion of the telescoping flue sections. Because of manufacturing tolerances, place the telescoping extension on the water heater and adjust the height (“X” Dimension) and mark the point.
12 8. Making sure the 6” diameter elbow is centered around the 3” diameter flue, secure the 6” diameter vent pipe using two sheet metal screws at the connection of the elbow and 6” vertical extension. FIGURE 41 9. The standard vent kit includes a 6” diameter extension pipe which is used when “E” dimension over 6 1/2”.
13 17. Connect the vent cap by sliding its end over the 3” diameter extension pipe and O-ring. NOTE: T o facilitate ease of assembly of the vent cap to the 3” pipe, a soap solution can be applied to the O-ring gasket. FIGURE 50 18. The vent cap has 4 holes around the outer edge.
14 FIGURE 57 5. Making sure the 6” diameter elbow is centered around the 3” diameter flue, secure the 6” diameter vent pipe using four sheet metal screws at the connection of the jacket top. FIGURE 58 6. The standard kit includes a single piece of 3” flue and 6” vent pipe which will not be used in conjunction with the horizontal kit.
15 14. Place the vent cap in the vent collar assembly . FIGURE 67 15. The vent cap has 4 holes around the outer edge. Remove the 4 screws used to temporarily attach the collar to the exterior wall. Then secure the vent cap assembly with the vent collar assembly to the exterior wall using the same 4 screws.
16 FIGURE 74 Use the simple equation below , chart and drawing to find the length of expansion of the telescoping flue sections. Because of manufacturing tolerances, place the telescoping extension on the water heater and adjust the height (“X” Dimension) and mark the point.
17 8. The standard kit includes a single piece of 3” flue and 6” vent pipe which will not be used in conjunction with the optional horizontal kit. FIGURE 82 9.
18 4 screws used to temporarily attach the collar to the exterior wall. Then secure the vent cap assembly with the vent collar assembly to the exterior wall using the same 4 screws. NOTE: Screws are supplied; however , substitution may be necessary depending on the exterior wall material.
19 FOR YOUR SAFETY READ BEFORE LIGHTING W ARNING If you do not follow these instructions exactly , a fire or explosion may result causing property damage, personal injury or loss of life. LIGHTING INSTRUCTIONS A. This appliance has a pilot which must be lighted by hand.
20 TEMPERA TURE REGULA TION DANGER THIS W A TER HEA TER IS EQUIPPED WITH AN ADJUST ABLE THERMOST A T TO CONTROL W A TER TEMPERA TURE. HOT W A TER TEMPERA TURES REQUIRED FOR AUT OMA TIC DISHW ASHER AND LAUNDRY USE CAN CAUSE P AINFUL SCALDING WITH POSSIBLE SERIOUS AND PERMANENT INJURY .
21 be called to determine the reason for limit operation and thus avoid repeated thermostat replacement. Lower the temperature adjustment dial setting on the new control. VENTING HA VE VENTING SYSTEM CHECKED EVERY SIX MONTHS FOR OBSTRUCTIONS AND/OR DETERIORA TION IN VENT PIPING.
22 TROUBLESHOOTING Please check guidelines below . For your safety , water heater service should be performed only by a qualified service technicia n. Read the GENERAL SAFETY INFORMA TION section first. PROBLEM POSSIBLE MALFUNCTION SERVICE TO BE PERFORMED POSSIBLE SOLUTION NO HOT W A TER 1) No pilot A.
23 THIS WARRANTY IS APPLICABLE TO THE ORIGINAL OWNER ONL Y . I f the glass lined tank in this water heater shall prove upon examination by A. O. Smith Corporation (the warrantor) to have leaked during.
5621 W . 1 15TH STREET , ALSIP , IL 60803 PHONE: 1-800-433-2545 F AX: 1-800-433-2515 www .hotwater .com / email: par ts@hotwater .com.
デバイスA.O. Smith FDVの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
A.O. Smith FDVをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはA.O. Smith FDVの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。A.O. Smith FDVの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。A.O. Smith FDVで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
A.O. Smith FDVを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はA.O. Smith FDVの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、A.O. Smith FDVに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちA.O. Smith FDVデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。