AmtrolメーカーWELL-X-TROLの使用説明書/サービス説明書
ページ先へ移動 of 16
INST ALLA TION, OPERA TION & MAINTENANCE INSTRUCTIONS 9013-0001 (3/08) WELL-X-TROL ® WELL-X1 ™ INST ALLER: LEA VE THIS MANUAL WITH THE OWNER IMPORT ANT GENERAL SAFETY INFORMA TION - ADDITIONAL SPECIFIC SAFETY ALERTS APPEAR IN THE FOLLOWING INSTRUCTIONS.
1. T ABLE OF CONTENTS GENERAL SAFETY INFORMA TION ........................................................... 2 COMPONENTS ........................................................................................... 3 INST ALLA TION AND SIZING CONSIDERA TIONS .
3 3. COMPONENTS The W ell-X1 ™ combines all the standard well tank components in a single, easy to install package. The pressur e tank, control and tank fittings are factory-installed. After removing from the carton, inspect the W ell-X1 ™ for damage and ensure all components ar e present.
4 4. INST ALLA TION AND SIZING CONSIDERA TIONS The W ell-X1 ™ functions like a traditional pressure switch by cycling the pump on and off. The factory pressure settings are 40 psi cut-in and 60 psi cut-out. The controller allows these settings to be adjusted to best suit the application.
5 5. INST ALLA TION CONSIDERA TIONS LOCA TION The W ell-X1 ™ is designed for indoor and outdoor installations. The NEMA 3R enclosure can be installed in direct weather . If installed outdoors, be sure the following conditions are met: • Do not install where ambient temperatures can drop below freezing or exceed 120° F .
6 6. PLUMBING 1. Plumbing connections are similar to a traditional "tank cross" or "tank tee". Provisions are made for popular line sizes via a 1-1/4" NPT male outer thread and a 1" NPT female inner thr ead. The plumbing connections are not directional and allow flow from either side.
7 4. Connect the water line fr om the well pump to the inlet of the W ell-X1 ™ . 5. Plumb the outgoing supply to the building's water supply system or into the water treatment equipment (if present). 6. Install a blow down tube from the relief valve to a drain or to within 6" of the floor as requir ed by local codes.
8 7. WIRING LINE LINE MOTOR MOTOR BLACK WHITE/STRIPE BLUE WHITE TA B TA B SCREW 1. Shut off the circuit br eaker for the well system. Loosen the top screw housing cover . Flip the cover forward and remove to expose the contr ol wires. Electrocution hazard.
9 8. ST AR TUP & ADJUSTMENT 1. After plumbing and wiring are complete, close the service valve to allow startup without pr essurizing the entire plumbing system. If a service valve was not installed, close all fixtures in the home. Ensure the bottom drain is closed.
10 8. ST AR TUP & ADJUSTMENT (con't) 5. The factory cut-out (pump off) setting is 60 psig. When the pump reaches 60 psig, the W ell-X1 ™ will shut the pump off.
11 1. T o enter the programming mode, press and hold the MODE button until LO appears. This is the cut-in setting. Factory default will be 40 psi. 2. Use the s and t arrows to raise or lower the cut- in setting. Adjustment can be made within 10 psig or as wide as 55 psig of the cut-out setting to 60 psig.
12 3. T o adjust the cut-out, depress MODE once and the display will read HI . Again, press the t or s buttons to raise or lower the setting. The same 10-55 psig differ ential range applies. Maximum setting is 80 psig. 4. After adjusting the cut-in and cut-out, r elease the buttons.
13 9. PUMP PROTECTION AND DIAGNOSTICS The W ell-X1 ™ continually monitors pr essure, cycle time and voltage to protect the well pump. The following error codes alert the user to a potential problem, pr ompting service.
14 10. TROUBLESHOOTING PROBLEM POSSIBLE CAUSE SOLUTION Alarm sounds 1. Error encounter ed 1. See Error Code section for possible causes. No water at fixtures 1. Error encounter ed 2. No power 3. W ater line obstructed 4. Faulty pump 5. Drain or relief valve open 6.
15 11. REPLACEMENT P AR TS DESCRIPTION POSITION WX1-202 WX1-203 WX1-250 WX1-251 WX1-302 Replacement tank: Blue 1 144R273 146R825 145R379 145R380 150R92 Replacement tank: T uf Kote™ 1 144R274 146R826.
16 AMTROL INC. LIMITED PRODUCT WARRANTY Products cover ed: all Products manufactured by AMTROL Inc. (“AMTROL”). This warranty cannot be transferred – it is extended only to the original Purchaser or First User of the Product.
デバイスAmtrol WELL-X-TROLの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Amtrol WELL-X-TROLをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはAmtrol WELL-X-TROLの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Amtrol WELL-X-TROLの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Amtrol WELL-X-TROLで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Amtrol WELL-X-TROLを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はAmtrol WELL-X-TROLの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Amtrol WELL-X-TROLに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちAmtrol WELL-X-TROLデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。