536636-UIM-D-1211 SINGLE PIECE V ARIABLE SPEED AIR HANDLERS MODELS: A V*(C) SERIES INSTALLATION MANUAL ISO 9001 Certified Quality Management System LIST OF SECTIONS GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
536636-UIM-D-1211 2 Johnson Controls Unitary Products 1. Install this air handler only in a location and position as specified in SECTION III of these instructions. 2. Always install the air handler to operate within the air handler’s intended maximum outlet air t emperature.
536636-UIM-D-1211 Johnson Controls Unitary Produ cts 3 DOWNFL OW AND HORIZONT AL CONVERSION (A V ONL Y) These air handler units are supplied ready to be installed in a upflow and right hand horizontal position. If unit requires left hand positioning, the unit must have the coil assembly repositioned.
536636-UIM-D-1211 4 Johnson Controls Unitary Products CLADDING CONFIGURA TION FOR DOWNF LO W INST ALLA TION (IF USED) T o reconfigure the cladding parts, remove the grille by pulling gently at the top. Once the grille is removed, the circuit breaker cover can also be removed.
536636-UIM-D-1211 Johnson Controls Unitary Produ cts 5 DUCT CONNECTIONS Air supply and return may be handled in one of several ways best suited to the installation.
536636-UIM-D-1211 6 Johnson Controls Unitary Products TXV METERING D EVICES If the model (C) numb er is of the following format: 4F , 4G , 4H, 4J, and 4K will have the coil with R410A TXV metering device installed at the factory .
536636-UIM-D-1211 Johnson Controls Unitary Produ cts 7 DRAIN CONNECTIONS All drain lines should be trapped a minimum of three inches, should be pitched away from unit drain pan and should be no smaller than the coil drain connection.
536636-UIM-D-1211 8 Johnson Controls Unitary Products CONVENTIONAL L OW V OL T AGE CONTROL WIRING (24 V AC) The 24 volt power supply is provi ded by an int ernally wired low voltage transformer which .
536636-UIM-D-1211 Johnson Controls Unitary Produ cts 9 . * Optional dehumidificat ion hu midistat switch cont acts open on humidit y rise. NOTES : 1. “Y/Y2” T erminal on air handler control board must be con nected for full CFM and appli cations requiring 60 second blower of f delay for SEER enhancement.
536636-UIM-D-1211 10 Johnson Controls Unitary Products The low voltage connections may be connected to the screw terminals or the quick connect terminals. T he screw terminals and t he quick con- nect terminals are phy sically connected o n the control board.
536636-UIM-D-1211 Johnson Controls Unitary Produ cts 11 The control energizes the fir st stage of electric heat immediately , the second stage 10 seconds after the call for second st age heat, and the third stage 20 seconds after the call for third stage heat.
536636-UIM-D-1211 12 Johnson Controls Unitary Products SECTION VIII: AIRFLO W AND COMFORT SETTING SELECTION AIRFLOW SELECTION The airflow and comfort setting se lection jumpers must be set properly at the time of installation for proper system operation.
536636-UIM-D-1211 Johnson Controls Unitary Produ cts 13 * May be 0 (no breaker) or 1 (with breaker). TA B L E 8 : Elect rical Data - Cool ing Only (60 Hz) Models T otal Motor Amp s Minimum Circuit Ampacity Max. O.C.P . Amps/T ype 1 Minimum Wire Size A.
536636-UIM-D-1211 14 Johnson Controls Unitary Products * May be 0 (no breaker) or 1 (with breaker). TA B L E 11 : Electrical Data - (For Single Source Power Supply) - Copper W ire - 208/23 0-1-60 Models Heater Models* Heater Amps 240V Field Wiring Min.
536636-UIM-D-1211 Johnson Controls Unitary Produ cts 15 T ABLE 13: Electrical Data - 208/230-3 -60 Models Heat Kit - Three Phase Max. Stat ic Min. Spe ed Ta p To t a l H e a t 1 kW S taging kW MBH W1 Only W2 Only W1 + W2 208V 230V 208V 230V 208V 230V 208V 230V 208V 230V 24B 4HK06501025 0.
536636-UIM-D-1211 16 Johnson Controls Unitary Products T ABLE 16: Air Handler Air Flow Data HIGH/LOW SPEED COOLING AND HEA T PUMP AIRFLOW CFM m 3 /min JUMPER SETTINGS 24B 36C 24B 36C High Low High Low High Low High Low COOL T ap ADJ T ap 1088 707 1387 905 30.
536636-UIM-D-1211 Johnson Controls Unitary Produ cts 17 SECTION X: MAINTENANCE Filters must be cleaned or replaced when they become dirty . Inspect at least once per month. Th e frequency of cleaning depends upon the hours of operation and the local atmospheric conditions.
Subject to change without not ice. Published in U.S.A. 536636-UIM-D-1211 Copyright © 201 1 by Johnson Controls, In c. All ri ghts reserved. Supersedes: 536636-UIM-C-1010 Johnson Contro ls Unit a r y .
デバイスJohnson Controls AV*(C) Seriesの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Johnson Controls AV*(C) Seriesをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはJohnson Controls AV*(C) Seriesの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Johnson Controls AV*(C) Seriesの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Johnson Controls AV*(C) Seriesで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Johnson Controls AV*(C) Seriesを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はJohnson Controls AV*(C) Seriesの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Johnson Controls AV*(C) Seriesに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちJohnson Controls AV*(C) Seriesデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。