1 BLD72, BLD72-1 Bilevel Step Motor Driver User’s Guide #L010011 910 East Orangefair Lane, Anaheim, CA 92801 e-mail: info@anaheimautomation.com (714) 992-6990 fax: (714) 992-0471 website: www.
2 General Description The BLD72 is a step motor driver that can drive motors rated from 1 to 7 amps/phase (unipolar rating). It can handle 6 lead and 8 lead motors. This driver features a unipolar bilevel (or dual voltage) drive tech- nique with short and open circuit protection (with a Fault LED).
3 Clock Modes The BLD72 has two clock options: Clock and Direction, or Dual Clock operation. Jumper JP2 is used to select the clock option. Basically JP2 selects Terminal 5 as either the Direction input or the CCW input.
4 Fault Protection There are 3 types of fault detection. When a fault is detected, the driver turns off the motor current and the red Fault LED indicates which type of fault occurred.
5 Wiring Diagram The wiring diagram in Figure 5 shows the BLD72 with the AA2791 Transformer. For wiring with the AA2793 Transformer, refer to Figure 9.
6 3. 750 MA X 4. 500 3. 100 2. 500 1. 450 MA X 1. 500 .8 00 M A X 2. 350 3. 570 3. 000 Transformer Drawings Note: The AA2793 transformer is the same physical size as the AA2791, but it has two sets of second- ary windings (to power two drivers) and a dual primary winding for 115/230V operation.
7 Figure 9: Wiring for different line voltages for the AA2793 transformer..
8 Note: The BLD72 and BLD72-1 are the same except for the base plate. The BLD72 is a replacement driver for use in Driver Packs. The BLD72-1 is a modular driver which has a larger base plate.
9 13 Pin Terminal Description Motor Compatibility Add suffix “ S ” for single-ended shaft, or suffix “ D ” for double-ended shaft. Notes: Other motors not listed above may be compatible with this driver. Anaheim Automation carries a full-line of standard and high torque step motors.
10 Specifications Control Inputs (All) : (Terminals 5, 6, 8, 9) TTL-compatible Logic “ 0 ” - 0 to 0.8 V Logic “ 1 ” - 3.5 to 5.0 V Fault Reset: (Terminal 4) Pulled up to +5VDC through a 10k Oh.
11 Troubleshooting If a Fault occurs, reset the Fault by applying a logic “ 0 ” to the Reset Fault Input (terminal 4) for at least 100ms (or by cycling power OFF for at least 15 seconds). After resetting, try to run the motor again. If the driver faults again then check the conditions listed below.
12 Torque Speed Curves ANAHEIM AUTOMATION.
デバイスAnaheim BLD72の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Anaheim BLD72をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはAnaheim BLD72の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Anaheim BLD72の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Anaheim BLD72で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Anaheim BLD72を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はAnaheim BLD72の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Anaheim BLD72に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちAnaheim BLD72デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。