User Manual English Smart-UPS ® RT 3000/5000/6000 VA 200-240 Vac Tower/Rack Mount 3U Uninterruptible Power Supply © 2012 APC by Schneider Electric. APC, the APC logo, and Sm art-UPS are owned by Schneider Electric Industries S.A.S., American Power Conversion Corporation, or affiliated companie s.
.
Introduction The APC by Schneider Electric Smart-UPS RT is a high-performance, uninterruptible power supply (UPS) that provides protection for electronic equipment from utility power blackouts, brownouts, sags and su rges.
Wiring and Connecting the UPS 5000/6000 VA XLI MODEL S O NLY : H ARDWIRING I NSTRUCTI ONS Wi ring must be performe d by a qualified electrician. Install a high magnetic 30/32 A utility circuit breaker. Adhere to all national and local electrical codes.
C ONNECTING THE B ATTERY MODULES AND A TTACHING THE F RONT B EZEL . 3.
B ASIC C ONNECTORS serial com Power m anagement software and interface kits can be used with the UPS. Use only inter face kits supplie d or approved by APC. Any other serial interface cable w ill be incompat ible with the UPS connector. normal bypass M anual bypas s enables the us er to manual ly put connecte d equipm ent into bypass m ode.
C ONNECTING E QUIP MENT AND P OWER TO THE UPS 1. Connect equipment to th e UPS (cables not included for XLJ/XLT/XLTW models). 2. Avoid using extension cor ds. 3000 VA XLJ/XLT/XLTW/XLI and 5000/6000 VA XLJ/XLT/XLTW models : Using a power cord, plug the UPS into a two-pole, three-wire, grounded receptacle only.
O PERA TION Load S MART -UPS RT F RONT D ISPLAY Battery Charge Indicator Description Online The Online LED illuminates when the UPS is drawing utility power and performing double con version to su pply power t o connected eq uipment. On Battery The UPS is supplying batter y powe r to the connected equipment.
Feature Function Cold Start When there is no utility power and th e UPS is off, press and hold the button to power up t he UPS and conn ected equipm ent.
U SER C ONFIGURABLE I TEMS N OTE : S ETTINGS ARE MADE THROUGH SUPPLIED P OWER C HUTE SOFTWARE OPTIONAL S MART S LOT ACCESSORY CARDS OR T ERMINAL M ODE .
N OTE : S ETTINGS ARE MADE THROUGH SUPPLIED P OWER C HUTE SOFTWARE OPTIONAL S MART S LOT ACCESSORY CARDS OR T ERMINAL M ODE . F UNCTION F ACTORY D EFAULT U SER S ELECTABLE C HOICES D ESCRIPTION Low By.
Bo th Class 2 and SELV circuits must be isolated from all primary circu itry. D o not connect any circuit to the EPO terminal block unless it can be confirmed that the circuit is Class 2 or SELV. If circuit standard cannot be c onfirmed, use a contact closure switch.
5000/6000 VA models: Terminal Mode is a me nu driven interface that enables enhanced confi guration of the UPS. Connect the serial cable to the se rial port on the back of the UPS. 1. Open a term inal program . Example: Hy perTerminal From the Desktop, go to Start => Programs => Accessories => Com munication => HyperTerminal.
M AINTENANCE AND T RANSPORT Replacing the Battery Module This UPS has an easy to repla ce, hot-swappabl e battery modul e. Replaceme nt is a safe proce dure, isolated from electrical hazards. You may leave the UPS and connected eq uipm ent on during the procedure.
R EPLACING B ATTERY MODULES Disconnecting the Battery for Transport Always DISCONNECT THE BA TTERY(s) before shipping in compliance with U.S. Department of Tr ansportation (D OT) and IATA re gulations. The battery(s) may remain in the UPS.
T ROUBLESHOOTING , S ER VICE , AND W AR RANTY I NFORMA TION Use the table below to solve minor installation and operation problems. Refer to the APC Web site, www.apc.com for assistance with complex UPS problems. P ROBLEM AND P OSSIBLE C AUS E S OLUTION UPS WILL NOT TURN ON Battery not connected properly.
P ROBLEM AND P OSSIBLE C AUS E S OLUTION BYPASS LED ILLUMINATES The bypass switch has been turned on manually or through an accessory. If bypass is the chosen mode of ope ration, ignore the illuminated LED. If bypass is not the chosen mode of operation move the bypass switch on the back of the UPS, to the normal position.
Service If the UPS requires service do not return it to the dealer. Follow these step s: 1. Review the pr oblems discusse d in the Trou bleshooting secti on of this manual to eliminate common pr oblems. 2. If the pro blem persists, cont act APC Custom er Support through t he APC Web site, ww w.
. 17 R EGULA TOR Y Radio Frequency Warnings This equipment has been tested and found to comply with the li m its for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable pr otection against harmful interf erence when the equipment is operated in a commercial environment.
デバイスAPC SURT6000RMXLI-BNDLの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
APC SURT6000RMXLI-BNDLをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはAPC SURT6000RMXLI-BNDLの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。APC SURT6000RMXLI-BNDLの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。APC SURT6000RMXLI-BNDLで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
APC SURT6000RMXLI-BNDLを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はAPC SURT6000RMXLI-BNDLの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、APC SURT6000RMXLI-BNDLに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちAPC SURT6000RMXLI-BNDLデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。