Smart-UPS ® RT Uninterruptible Power Supply SURT 8000/10000 VA 200-240 VAC Tower/Rack-Mount 6U English © 2012 APC by Schneider Electric. APC, the APC logo, Sm art-UPS and PowerChute are owned by Schneider Electric Industries S.A.S., American Power Conversi on Corporation, or affiliated companies.
.
Introduction The APC ® by Schneider Electric Sm art-UPS ® RT is a high-performance, uninterruptible power supply (UPS) that provides protection for electronic equipment from utility power blackouts, brownouts, sags and su rges.
Hardwiring Wiring must be performed by a qualified electrician. 1. Install a utility circuit breaker in accordance with local electrical codes (see tables below) for input wiring. 2. Switch the UP S input circui t breaker (see A ) and utility circuit breakers OFF.
7. XLI mo del only: For three-phase input, set the Input Phase Selector switch (see C ) to ‘3’. For single-phase input, leave switch in default position of ‘1’. 8. Switch the circuit breakers ON. 9. Check line voltages. 10. Replace the ac cess panel.
Installing and Connecti ng the Batteries and Attaching the Front Bezel 4.
C ONNECTING P OWER AND E QUIPMENT TO THE UPS 1. Hardwire the UPS (see Hardwiring ). 2. Connect equipment to th e UPS (cables not included for XLT/XLJ/XLTW models). 3. Turn on all connected equipm ent. To use the UPS as a m aster on/off switch, be sure that all connected equipm ent is switched ON.
B ASIC C ONNECTORS Serial Port Power m anagement software and inte rface kits can be used with the UPS. Use only inter face kits suppli ed or approved b y APC.
O PERA TION F RONT D ISPLAY P ANEL Indicator Description Online The UPS is drawing utility power and performin g double conversion to sup ply power to connected equipm ent (see Troubl eshootin g ). On Battery The UPS is supplying batter y powe r to the connected equi pment.
Feature Function Normal /Bypass Manually switch connected eq uipment to bypass mode, so that utility power is sent directly to connected equipment. Battery op eration is not available while the UPS is in bypass mode. (See Troubleshooting. ) Cold Start This is not a normal condition.
U SER C ONFIGURABLE I TEMS N OTE : S ETTINGS ARE MADE THROUGH SUPPLIED P OWER C HUTE SOFTWARE , N ETWORK M ANAG E ME NT CAR D , OPTIONAL S MA RT S LOT A CCESSORY CARDS OR T ERMINA L M ODE .
N OTE : S ETTINGS ARE MADE THROUGH SUPPLIED P OWER C HUTE SOFTWARE , N ETWORK M ANAG E ME NT CAR D , OPTIONAL S MA RT S LOT A CCESSORY CARDS OR T ERMINA L M ODE .
EPO (Emergency Power Off) Option The output power can be disabled i n an emerge ncy by closing a switch connected to t he EPO. Adhere to national an d local electrical codes when wiring. The switch should be connected in a normally open switch contact.
Terminal Mode to Configure UPS Parameters Terminal Mode is a me nu driven interface that enables enhanced c onfiguration of the UPS. Connect the serial cable to the se rial port on the back of the UPS.
M AINTENANCE , S ERVICE , W ARRANTY , AND T RANS PORTING Replacing the Battery Module(s) This UPS has e asy to replace, hot -swappable ba ttery m odules. Replacement is a sa fe procedure, isolated from electrical hazards. You may leave the UPS and connected eq uipment on during the procedure.
T ROUBLESHOOTING Use the table below to solve minor installation and operation problems. Refer to the APC Web site, www.apc.com for assistance with complex UPS problems. P ROBLEM AND P OSSIBLE C AUS E S OLUTION UPS WILL NOT TURN ON Batteries are not connected properly.
15 P ROBLEM AND P OSSIBLE C AUS E S OLUTION BYPASS LED ILLUMINATES The bypass switch has been turned on manually or through an accessory. If bypass is the chosen mode of ope ration, ignore the illuminated LED. If bypass is not the chosen mode of operation move the bypass switch on the back of the UPS, to the normal position.
Service If the UPS requires service do not return it to the dealer. Follow these step s: 1. Review the pr oblems di scussed in the Tr oubleshoot ing section of this manual to eliminate common pr oblems. 2. If the pro blem persists, co ntact APC C ustomer Su pport thro ugh the APC Web site, ww w.
17 R ADIO F REQU ENCY W ARNINGS This equipment has been tested and found to comply with the li m its for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable pr otection against harmful interf erence when the equipment is operated in a commercial environment.
デバイスAPC SURT8000XLI+LE600Iの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
APC SURT8000XLI+LE600Iをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはAPC SURT8000XLI+LE600Iの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。APC SURT8000XLI+LE600Iの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。APC SURT8000XLI+LE600Iで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
APC SURT8000XLI+LE600Iを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はAPC SURT8000XLI+LE600Iの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、APC SURT8000XLI+LE600Iに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちAPC SURT8000XLI+LE600Iデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。