H EAT R EMOVAL /E NVIRONMENT AL C ONTROL Dr ycooler s - 60 Hz G ENERAL D AT A.
.
i T ABLE OF CONTENTS L IEBERT D RYCOOLERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 F EATURES AND B ENEF IT S OF L IEBERT D RYCOOLERS . . . . . . . . . . . . . . . . . . . . . .
ii Figures Figure 1 Drycooler model numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Figure 2 Capacity correction factor . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 L IEBERT D RYCOOLERS Liebert drycoolers are designed to be used in conjunctio n with water cooled refrigerat ion and air conditioning machines as well as a variety of commercial and industri al applications requiring the rejection of heat from machinery or processes via a cooling fl uid.
2 F EATURES AND B ENEFITS OF L I EBERT D RYCOOLERS Heat Rejection Module The low-profile direct-driv e propelle r-fan type drycoolers utilize optimum circuitry to balance the heat rejec- tion of the corresponding load. Constructed of al uminum with a copper-tube aluminum coil, the unit is quiet and corrosion resistant.
3 S ELECTION P ROCEDURE Table 4 shows the performance specifications for Liebert drycoolers using a 40% by volume ethylene glycol solution at an av erage fluid temperature of 115°F with flow rates from 1.5 to 3 GPM/circuit and at standard air (.0 75 lbs/ft 3 ).
4 P ERFORMANCE D AT A T able 4 Drycooler perform ance dat a Model Number GPM Range No. of Circuits MBH/°F Initial Temperature Difference 1.5 GPM/CIR 2.0 GPM/CIR 2.5 GPM/CIR 3.0 GPM/CIR MBH/ITD PD ft. water MBH/ITD PD ft. water MBH /ITD PD ft. water MBH/ITD PD ft.
5 Figure 2 Cap acity correct ion factor Figure 3 Pressure drop correction fac tor Quiet-Line Models 040 6-12 4 1.4 7.4 1.5 11.4 1 .6 17.0 1.7 23.5 12-24 8 * 1.6 3.9 1.7 5.9 1.8 8.9 1.8 12.3 057 18-36 1 2* 2.1 3.6 2.2 6.1 2.3 8.6 2.3 11. 9 24-48 16 2.2 3.
6 D IMENSIONAL D AT A Figure 4 Dimensional dat a—1-4 fan models Figure 5 Dimensional dat a—6 & 8 fan models Figure 6 T ypical footprint and unit anchor plan Eyebolt s for lif ting condenser pr.
7 T able 5 Drycooler physic al data Drycooler Model Circuits A B C L #Fans & Motors** Conn FNPT In/Out Standard Models -033 any 42 - 44 51.5 1 3/4 -069 any 42 - 44 51.5 1 1-1/4 -092 any 42 - 44 51.5 1 1-1/2 -109 any 42 - 44 51.5 1 2 -112 any 42 - 44 51.
8 E LECTRICAL D AT A T able 6 Drycooler electrical dat a # of F a n s 123468 Model # 33,69,92,109,112 139,174,197,22 5 260,310,350 352,419,466,491 620,650,700 790,880,940 Pump Hp ph FLA WSA OPD ph FLA WSA OPD ph FLA W SA OPD ph FLA WSA OPD ph FLA W SA OPD ph FLA WSA OPD 208/230/60 0.
9 T able 7 Drycooler electrical dat a—Quietline models # of F a n s 123468 Model # 40,57,6 0 80,111,121 158,173,178 205,248 347,356 453,498 Pump Hp ph FLA WSA OPD ph FLA WSA OPD ph FLA W SA OPD ph FLA WSA OPD ph FLA W SA OPD ph FLA WSA OPD 208/230/ 60 0.
10 G UIDE S PECIFICATIONS St andard Features for Direct Drive Propeller Fan Drycoolers Furnish and install Liebert Model ________ Air-Cooled Drycoo lers, arranged for vertical air flow. Dry- coolers shall be draw-through design and shall perform in accor- dance with the schedule.
11 C OMPONENT A SSEMBLY /I NST ALLATION Leg Assembly The legs are shipped loose and are to be field mounted as shown with the hardware provided. Rigging Holes in the drycooler legs permit lifting the unit. Spreader bars are required. Four, 6 and 8 fan models have additional lifting eyes.
12 A PPLICATION /I NST ALLATION G UIDELINES Location Guidelines To ensure an adequa te air supply, locate drycoolers in a clean air area , away from loose dirt and for- eign matter that may clog the coil. In addition, drycoolers must not be placed near steam, hot air, or fume exhausts.
13 P UMP P ACKAGES & E XP ANSION T ANK - O PTIONS Figure 8 Pump p ackage Figure 9 Pump mounting Notes 1. Sin gle pump packages are 17-1/4" (438 .2 mm) wide. Dual pump packages are 32-1/4" (819.2 mm) wide. 2. Mounting holes are 15-11/32" (389.
14 S UPPLEMENT ARY A PPLICATION D AT A T able 9 Room dew point temperature s Dry bulb °F (°C) Wet bulb °F (°C) Rel. hum. % Dew point* °F (°C) 70 57.
.
The Comp any Behind the Product s With over a million installations around th e globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a c.
デバイスLiebert 60 HZの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Liebert 60 HZをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはLiebert 60 HZの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Liebert 60 HZの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Liebert 60 HZで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Liebert 60 HZを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はLiebert 60 HZの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Liebert 60 HZに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちLiebert 60 HZデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。