P OWER A VAILABILITY P o w erSur e PSI™ U SER M ANUAL 1000 - 3000V A 230V V ersion française, : reportez-vous au CD du gu ide d'utilisateur Liebert. Para español, consulte el CD del Manual del Usuario de Liebert. Die deutsche Fassung finden Sie auf der CD des Liebert-Benutzerhandb uchs.
.
i T ABLE OF CONTENTS I MPORT ANT S AFETY I NSTRUC TIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.0 G LOSSARY OF S YMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ii 9.0 V OLT AGE P ROGRAMMING P ROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 10.0 M AINTENAN CE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 I MPORT ANT S AFE TY I NSTRUCTIONS SA VE THESE INSTRUCTIONS This manual co ntains important safety i nstructions that should be followed during the i nstallation and maintenance of the UPS and batt eries. Please re ad this manual th oroug hly before attempting to install or operate this UPS.
2 CONDITIONS OF USE: The mains supply socket must be within 2m (6.5 ft.) of the UPS an d be eas- ily accessible. Your UPS provides conditioned power to connected equipment. This product is designed for Commer- cial use only. It is not intended for use with life support and other design ated “critical” devices.
Glossary of Symbols. 3 1.0 G LOSSARY OF S YMBOLS . Risk of ele ctrical shock Indicates caution followed by important instructions Requests the user to consult the manual Indicates the unit contains a .
Introd uction 4 2.0 I NTRODUCTION Congratulations on your choice of the Liebert Po werSure™ PSI Uninterruptible Power Supply (UPS). It provides conditioned power to microcomput ers and other sensitive electronic equipment. Upon generation, AC power is clea n and stable.
Introd uction 5 Figure 2 1000 and 1440V A PSI—rear view Figure 3 2200 and 3000V A PSI—rear view PHONE / F AX / MODEM / NETWORK PROTECTION BA TTERY CONNECTOR 1440V A/DC 48V/30A 1000V A/DC 48V/20A 1.
Major Compo nents 6 3.0 M AJOR C OMPONENT S Figure 4 Line diagram of Power S ur e PSI 1000V A & 1440V A Figure 5 Line diagram of Power S ur e PSI 2200V A & 3000V A 3.
Major Compo nents 7 3.3 Automatic V olt age Regulator The Automatic Voltage Regulator ( AVR) protects connected equipmen t from power spikes, sags and other abnormalitie s by raising (boostin g) or loweri ng (bucking) the output voltage as needed.
What’ s Included 8 4.0 W HAT ’ S I NCLUDED The PowerSure PSI is shipped with the foll owing items: • PowerSure PSI user manual • MultiLink software CD • MultiLink serial cable, 3m (10 f t) • USB cable, 1.
Installation 9 5.0 I NST ALLATION 5.1 Prep aration 1. Visually inspect the UPS for freight damage. Report damage to the carrier and your local dealer or Liebert representative. 2. De cide where to place the PowerSure PSI. Inst all the UPS in doors in a controlled environment where it cannot b e accidentally turned Off.
Installation 10 5.3 Rack-Mount U PS Conversion and Inst allation 1. For fixed rail installations, install the rack mount handles using four (4) M4x6 screws (see Figure 7 ). Figure 7 Rack mount handles 2. Unpack the two fixed rail assembli es and mounti ng hardware.
Installation 11 4. Attach the two (2) fixed rails to the racks mounting ra ils. The fi xed rail assemblies fit on the inside of the ra ck mounting rails. 5. Ins ert two (2) M5 flat head screws loosely (finge r-tight) into the top and bottom holes on the front of the fix ed rail assembly (see Figure 9 ).
Installation 12 15. Connect Phone/Fax/DSL/Network/Mode m devices to data line connectors. 16. Communication options (see 8.0 - Comm unications for details): Option 1 - Serial Communications Serial communications provides pa rametric data, for example, in put vol tage and battery voltage.
Installation 13 Figure 10 REPO switch connections 5.4 External Battery Cabinet Inst allation Optional Liebert external battery cabinets may be connec ted to the UPS to prov ide additional battery run time. External battery cabinets are designed to be pla ced all on one side of the UPS or stacked beneath the UPS.
Controls and Indica tors 14 6.0 C ONTROLS AND I NDICATORS 6.1 ON/Alarm Silence/ Battery T est Button This button controls output power to co nnected lo ad(s) and has three fun ctions: •O n • Alarm.
Controls and Indica tors 15 6.3 V olt age Programming Button The PowerSure PSI contains a Volt age Programming button that a llows the operator to select the nominal mains voltage. This setting ch anges the mains transfer points (low and high) of the UPS and the nominal output voltage when operating in Ba ttery mode.
Controls and Indica tors 16 6.9 Over T emp Indicator—Amber The Over Temp Indicator flashes wh en the UPS detects an over temper ature condition. This indicator illuminates when the UPS sh uts down due to an over temperature condition (see 11 .0 - Trouble- shooting for details).
Modes of Operati on 17 7.0 M ODES OF O PERATION 7.1 Normal Mode During Normal mode operation, the Po werSure PSI supplies conditioned, co mputer-grade power to the connected equipment: mains power pas.
Modes of Operati on 18 7.3 Battery Mode The UPS switches to Battery mode in the event of an extreme input voltage/f requency condition or complete mains failure.
Communications 19 8.0 C OMMUNICATIONS 8.1 DB-9 Connector The UPS has a DB-9 (9 pin female) connector on the rear to a llow UPS status communications wi th a computer system running Mu ltiLink software. The DB-9 is capab le of supplying serial comm unica- tion, on battery and low battery signals.
Communications 20 8.3 USB Interface Port The PowerSure PSI has a USB interface port for co mmunication that will wo rk with the built-in Microsoft Power Manger software on the user’s PC , if so equipped. It will pro vide UPS status and manages the automatic orderly shutdown of the computer.
V oltage Programming Procedure 21 9.0 V OLTAGE P ROGRAMMIN G P RO CEDURE Figure 17 Load Level Indicators 1. Remo ve the front bezel from the UPS. 2. U PS must be operating in No rmal (AC) mode. 3. The AC Input, Load, and Battery Level Indicators should be lit.
Maintenance 22 10.0 M AINTENANCE The PowerSure PSI UPS requires very little mainte nance. Follow these practices to prevent prob- lems. 10.1 Cleaning the UPS The following will help ensure trouble-free operation for years: • Vacuum dust from the ventil ation intake occasionally.
Maintenance 23 10.3.1 Internal Battery Replacement Proce dure 1. Gently remove the front plas tic bezel cove r from the U PS. 2. Loosen and remove the five (5) screws on the front cover plate. Lay th e cover plate aside for reassembly. 3. Loosen and remove four (4) screws on battery bracket.
Trou bleshooting 24 11 . 0 T ROUBLESHOOTING The information below indicates va rious symptoms a user may encount er in the event the PowerSure PSI experiences a problem. Use this information to determine whether external factors caused the problem. See Table 2 - Troubleshooting chart for suggested remedy.
Trou bleshooting 25 T able 2 T roubleshooting cha rt Problem Cause Solution UPS will not start Short circuit Check the circuit protector on the rear of the U PS. If it is tripped, reset it and restart the UPS. For further help, contact your local dealer, Liebert representative or the Li ebert Worldwi de Support Group.
Specifications 26 12.0 S PECIFICATIONS T able 3 UPS specifications Model Number PS1000RT2-230 PS1440RT2-230 PS2200RT2-230 PS2200RT2-230E PS3000RT2-230 PS3000RT2-230E Power Rating, VA/W 1000VA/750W 1440VA/10 80W 2200VA/1650W 3000VA/2250W Dimensions, W x D x H, mm (in) Unit 87 x 557 x 430 (3.
Specifications 27 Agency Safety EN 62040-1-1; TUV/GS liste d; CE compliance mark Surge EN61000-4-5, Level 3, Criteria B ESD EN61000-4-2, Level 3, Criteria B Susceptibility EN61000-4-3, Leve l 3, Crite.
Specifications 28 T able 5 Battery run ti mes Load% 1000VA 1440VA 2200VA 3000VA Internal Batter y (minutes) 5% 174 138 171 177 10% 118 79 73 91 2 0 % 6 54 54 74 7 3 0 % 4 12 82 62 8 4 0 % 3 72 42 32 2.
.
The Comp any Behind the Products With over a million installations around th e g lobe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a c.
デバイスLiebert PSITMの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Liebert PSITMをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはLiebert PSITMの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Liebert PSITMの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Liebert PSITMで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Liebert PSITMを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はLiebert PSITMの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Liebert PSITMに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちLiebert PSITMデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。