Package 1 of 1 contains: 1 - Assembled ventilator 1 - Bag assembly containing: 4 - Hanging straps 1 - Installation manual 1 - Remote electrical control box 1 - Bag containing sealant putty Installatio.
2 3 2 1 20 40 60 80 100 120 140 0 0.1 0.2 0 .3 0.4 0.5 0 .6 0.7 0.8 0 .9 Stat ic P ressure (i n w.g. ) Air Flow (c fm ) 3 - High Speed 2 - Medium Low Speed 1 - Low speed Engineering Data Model RNC120F THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE The cross-flow heat recovery core transfers heat between the two airstreams.
ALL DUCT CONNECTION COLLARS ARE 5" DIAMETER FRESH AIR FROM OUTSIDE EXHA UST AIR FROM BUILDING FRESH AIR T O BUILDING EXHA UST AIR T O OUTSIDE T OP VIEW SER VICE CLEARANCE FROM BO TTOM OF UNIT IS .
4 Engineering Data Model 120ERV Latent Recovery/Moisture Transfer Core The cross flow energy recovery core transfers heat and water vapor between the two air streams. It is easily removed for cleaning and service. MOTORS AND BLOWERS Each Air stream has an independent motorized impeller.
5 Engineering Data Model 120ERV ALL DUCT CONNECTION COLLARS ARE 5" DIAMETER FRESH AIR FROM OUTSIDE EXHA UST AIR FROM BUILDING FRESH AIR T O BUILDING EXHA UST AIR T O OUTSIDE T OP VIEW SER VICE CL.
6 Installation Instructions The RNC120F model can be setup in two different airflow configurations as illustrated in the engineering data sec- tion of the manual.
7 Location Selection The HRV must be located in a heated space where it will be possible to conveniently service the unit. Typically the HRV would be located in the mechanical room or an area close to the outside wall where the weather hoods will be mounted.
36" (1m) recommended min. 36" (1m) recommended min. 6' (2m) recommended min. 18" (460mm) min. 18" (460mm) min. OUTSIDE CORNER INT AKE EXHA UST INSIDE CORNER 8 When installing the weather hood, its outside perimeter must be sealed with exterior caulking.
9 Air Duct Design and Installation A well designed and installed ducting system will allow the HRV to operate at its maximum efficiency. Always try to keep duct runs as short and straight as pos- sible. See Installation Diagrams for various installation options.
10 Stale Air Exhaust System The stale air exhaust system draws air from the points in the house where the worst air quality problems occur. Stale air ducts should be installed in the bathroom, kitchen, and laundry room. Applications such as green- houses, atriums, swimming pools, saunas, etc.
11 DIRECT CONNECTION of the SUPPLY AIR STREAM to the AIR HANDLER COLD AIR RETURN (Stale air drawn from key areas of home) Air Handler Outdoors *Unit is normally balanced on HIGH speed with air handler blower ON. High efficiency filter or electronic air cleaner Cool Air Return NOTES: 1.
12 DIRECT CONNECTION of both the HR V SUPPL Y AIR STREAM and EXHA UST AIR STREAM to the AIR HANDLER COLD AIR RETURN Defrost air port needs to be drawn fr om clean area without combustion appliances. T o av oid backdrafting of comb ustion pr oducts, never draw defrost air from a room with a naturally aspirated appliance, i.
13 Outdoors *Unit is normally balanced on HIGH speed with air handler blower ON. NOTES: 1. Weather hood arrangement is for drawing purposes only. 6' (2m) minimum separation required. 18" (460mm) above grade minimum or above anticipated snow level .
14 DIRECT CONNECTION of the SUPPLY AIR STREAM to the AIR HANDLER COLD AIR RETURN (Stale air drawn from key areas of home) Air Handler Outdoors *Unit is normally balanced on HIGH speed with air handler blower ON. High efficiency filter or electronic air cleaner Cool Air Return NOTES: 1.
15 DIRECT CONNECTION of both the HRV SUPPLY AIR STREAM and EXHAUST AIR STREAM to the AIR HANDLER COLD AIR RETURN Defrost air port needs to be drawn fr om clean area without combustion appliances. T o av oid backdrafting of comb ustion products, never draw defrost air fr om a room with a naturall y aspirated appliance, i.
16 Outdoors *Unit is normally balanced on HIGH speed with air handler blower ON. NOTES: 1. Weather hood arrangement is for drawing purposes only. 6' (2m) minimum separation required. 18" (460mm) above grade minimum or above anticipated snow level .
17 Ventilation Dehumidistat PART NO. 99-116 The High/Low Speed Switch initiates High or Low speed ventila- tion. This control also has an ON/OFF Switch and a Dehumidistat Dial (refer to "The ON/OFF Switch" and "The Dehumidistat Dial" descriptions).
18 Wiring the Controls Red to Red Black to Black Green LED Drive to Green DEH UMIDISTA T Red to Red Orange to Orange Black to Black Dehumidistat Ventilation Control Part No. 99-116 20 Minute Timer (shown in a Decora cover plate)* Red to Red Black to Black Remote Dehumidistat Part No.
19 The HRV unit should be plugged into a standard designat- ed (120VAC) electrical outlet with a ground. The outlet should be serviced by a separate 15 amp/120V circuit. An extension cord should not be used with this appliance. A qualified service technician should make any required electrical connections.
20 Operation Self T est The ventilator will automatically initiate a self test sequence when power is applied. Fan motor is cycled and then damper motor is cycled.
21 Wiring Diagrams HRV CONTROL BOX FA N B FA N A F AN A F AN B.
22 When using the Interface relay contacts to initiate b lower operation on a fur- nace, cer tain thermostats will initiate the outdoor cooling condenser when R and G are closed. Use this wiring configur ation to prev ent the Interf ace rela y contacts from initializing the condenser unit.
23 The fan defrost HRV is equipped with an electronically controlled fan defrost system to remove frost that collects on the warm air side of the aluminum heat transfer sur- faces of the heat exchanger core. When the outside air temperature drops below 27°F (3°C), defrost is activated which provides for an automatic defrost cycle.
24 It is necessary to have b alanced air flow in an H R V . The volume of air b rought in from the outside must e q ual the volume of air e x hausted b y the unit.
MAGNEHELIC MAGNEHELIC Placement of Pitot T ube HR V MAG NEHELIC DUCT AIR FLOW Pitot tube High Pressure Side Low Pressure Side Magnehelic gauge Pitot T ube and Gaug e Pitot T ube Air Flow Balancing Kit with magnehelic gauge, Pitot tube, hose and carry case.
Troubleshooting 26 Poor A ir Flow Supply air feels cold Dehumidistat is not O perating H umidity L evels are too H igh in Winter Condensation is appearing on the windows H umidity L evels are too L ow.
1. Inspect Exterior Hoods at least once a month. Make sure exhaust and fresh air supply hoods are not blocked or restricted by leaves, grass, or snow. In winter, it is especially important to make sure snow is not blocking the hoods or that frost has not built up on the wire mesh (bird screen).
28 Date Maintenance Performed Contractor Maintenance Record Note: It is important to maintain this product regularly to ensure optimal performance..
デバイスLifebreath 120ERVの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Lifebreath 120ERVをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはLifebreath 120ERVの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Lifebreath 120ERVの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Lifebreath 120ERVで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Lifebreath 120ERVを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はLifebreath 120ERVの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Lifebreath 120ERVに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちLifebreath 120ERVデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。