Do Not Attempt Installing Unit Without First Reading Entire Manual. OPERA TION AND INST ALLA TION MANUAL CAUTION Before installation, careful consideration must be given to how the system will operate if connected to any other piece of mechanical equipment, i.
2 INTRODUCTION These Heat Recovery Ventilators (HRVs) are designed for commercial and industrial applications to provide fresh air to a building while exhausting an equal amount of stale air. During the winter months the incoming cold fresh air is warmed by utilizing the heat recovered from the stale air before it is exhausted to the outdoors.
3 MAKE UP HEA T REQUIREMENT at 1200 CFM (566L/s) Nominal Nominal Nominal Outdoor Temp. kW Req. for kW Req. for kW Req. for C° F° 20°C (68°F) 25°C (77°F) 30°C (86°F) Air Delivery Air Delivery A.
4 Supply to building Supply from outside Exhaust from building Exhaust to outside Heat Exchanger Service Panel* Filter Service Panel* Electrical Service Panel* 47" 47" 89.9" 38.4" 24" 16" SIDE VIEW FRONT VIEW BACK VIEW *NOTE: Removable service access panels on both sides of 2500IFD cabinet.
5 PERFORMANCE OPTIONS AND ACCESSORIES 99-101: CRANK TIMER Mechanical timer to activate high speed. 99-116: DEHUMIDISTAT VENTILATION CONTROL (DVC) Turns unit on/off via slider switch and high/low via built-in dehumidistat. 99-130: DEHUMIDISTAT Activates high speed when indoor humidity rises above set point on control.
6 Hoods (2) c/w Bug Screen Motors (2) Supply to Duct 24"x16" Drain Pans (2) Heat Exchange Core Exhaust Duct 24"x16" 4" Filters Supply Hoods Exhaust Hoods Roof Curb Heat Exchanger Service Panel* Filter Service Panel* Electrical Service Panel* 47" 18" 18" 27" 89.
7 PERFORMANCE OPTIONS AND ACCESSORIES 99-101: CRANK TIMER Mechanical timer to activate high speed. 99-116: DEHUMIDISTAT VENTILATION CONTROL (DVC) Turns unit on/off via slider switch and high/low via built-in dehumidistat. 99-130: DEHUMIDISTAT Activates high speed when indoor humidity rises above set point on control.
8 Oper ation Instructions The LIFEBREA TH 2500 series HRV is designed tobe operated continuously or intermittently to meet the requirements of the application. CONTINUOUS OPERA TION For continuous operation, a simple jumper across the ON/OFF and COMMON jumper terminals is needed.
9 Off 10 20 30 40 50 60 Optional Remote Controls ON OFF HIGH LOW Supplied and Installed by Contractor Dehumidistat Setting Relative to Outside Conditions WINTER: Set dehumidistat between 30% to 40%. If home is too dry, adjust to higher setting.
F an Defrost The Models 2500IFD and 2500EFD are equipped with an electronically controlled fan defrost system to remove frost that collects on the warm air side of the aluminum heat transfer surfaces of the heat exchanger core.
11 Mounting the 2500 2500EFD Roof mount NOTE: Roof curb is one inch smaller than outside dimensions of cabinet Roof curb 2500IFD Platform mount (not provided) Mount unit on wooden or metal support assembly. Unit must be raised an adequate height for installation and slope of drain lines.
FRAME ASSEMBL Y 1. T ake one end piece (locking tabs) and one side piece (slots). Stand both pieces vertically on the floor or roof. See Figure 1. 2. Raise slightly the corner of the end piece (locking tabs) and mate with side piece (slots), ensuring that lower locking tab with leading edge is through slot opening.
13 Dr ains Connect the stainless steel drain pans in the bottom of the HRV to a drain line fastened to the holes provided. See pg.10 for location of the drain pans and the drain connections. Create a "P" trap to prevent odours from being drawn through.
14 Stale Air Return S yst em The stale air return system is used to draw air from the points in the building where the worst air quality prob- lems occur . Balancing dampers and/or adjustable grilles are recommended on all return air lines which are used during installation to help balance the "draw" from different areas of the building.
15 It is necessary to have balanced air flows in an HRV. The volume of air brought in from the outside must equal the volume of air exhausted b y the unit.
16 The Integr ated HV A C S ystem The 2500 is a quiet, efficient, low pressure system. Special care and attention should be given if connecting this unit to any other air handler that may draw more air than the 2500 is designed to accommodate. The HRV has become an integral component of the HV AC system.
17 DAMPERS OR ADJUSTABLE GRILLES BALANCING DAMPERS HRV UNIT EXHAUST TO HRV SUPPLY DUCT RETURN AIR DUCT FRESH AIR SUPPLY FRESH AIR TO BUILDING STALE AIR EXHAUST ROOFTOP HEAT/COOL UNIT Check design stat.
18 C1 HIGH BLACK - HIGH YELLOW - COM BLUE - MID RED - LOW SUPPL Y M OTO R SUPPL Y BRO WN BRO WN CAP C2 F2 L1 L2 F3 MAX 15A MAX 15A LOW TIMER ON/OFF ON/OFF 24V F.
19 CO MMERCIAL LIFEBREA TH ® HEA T REC O VER Y VENTILA TORS • T wo Y ear Limited W arranty • 15 Y ear Core W arranty NUTECH ENERGY SYSTEMS INC. ® (NUTECH) warrants to the purchaser of the Commercial LIFEBREATH ® model and accessories referred to below, to be free from manufacturing defects.
511 McCormick Blvd. London, Ontario N5W 4C8 Ph: (519) 457-1904 Fx: (519) 457-1676 Email: nutech@lifebreath.com Website: www.lifebreath.com.
デバイスLifebreath 2500IFDの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Lifebreath 2500IFDをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはLifebreath 2500IFDの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Lifebreath 2500IFDの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Lifebreath 2500IFDで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Lifebreath 2500IFDを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はLifebreath 2500IFDの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Lifebreath 2500IFDに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちLifebreath 2500IFDデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。