NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 1 36" Wood Burning Fireplaces P/N 850,046M REV. N/C 01/2007 RD-36 HC-36 RD-36-H HC-36-H RDI-36 HCI-36 RDI-36-H HCI-36-H MODELS MERIT ® SERIES This installation manual will enable you to obtain a safe, efficient and dependable installation of your fireplace system.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 2 TABLE OF CONTENTS Safety Rules .................................... page 2 Tools and Building Supplies ............ page 2 Precautions ..................................... page 3 Introduction .......
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 3 Figure 1 TYPICAL INSTALLATION *Construction Materials: • framing materials • paneling • particle board • flooring • dry wall • etc. • plywood PRECAUTIONS Note: These fireplace systems are not difficult to install.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 4 Figure 2 Chimney Height The total height of your completed fireplace system from the surface the fireplace rests on to the chimney top must not exceed 60' and must also meet minimum height requirements.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 5 Note: Install the hearth extension only as illus- trated. The safety strips should extend from front of the fireplace at least 1 ¹⁄₂ " and should extend to be at least flush with the sides.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 6 FIREPLACE SPECIFICATIONS Figure 10 Blocking Metal Safety Strips Figure 8 Figure 9 Step 3. Refer to fireplace drawings and specifi- cations on pages 6 and 7 for framing dimensions and details. Frame appliance enclosure as illus- trated in Figures 11 through 14 on page 8.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 7 Figure 15 Figure 16 Figure 14 Framing Dimensions A 43" 1092 mm B 44 ¹⁄₂ " 1130 mm C 29 ¹⁄₂ " 749 mm D 15 ³⁄₄ " 400.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 8 Step 4. Fireplace should be secured to side framing members using the full length nailing tabs at the top and bottom of the fireplace front face.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 9 Note: If there is a room above ceiling level, firestop spacer must be installed on the bottom side of the ceiling. If an attic is above ceiling level, firestop spacer must be installed on top side of ceiling joist (Figures 21 and 22 ).
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 10 Locking Band Waterproof Caulk Step 9. Security Chimneys locking bands, Model FLB, may be required if the chimney extends too high above the roof flashing.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 11 Using a FTF8-CTDT Chase Termination: Refer to specific installation instructions in- cluded with the FTF8-CTDT chase termination for clearance and installation details.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 12 Step 2. Use “Height of Chimney Only” column in The Vertical Elevation Chart to determine combinations of chimney used above return elbow to achieve desired heights. Reference Components Effective Height Chart in vertical elevation chart section.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 13 A B FTF8-ES30 Number of FTF8 Chimney Sections Offset Height Offset/Return FTF8-S4 (Inches) (Inches) Elbow Stabilizer 12" 18" 38" 48&q.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 14 Figure 43 THIS FIREPLACE IS NOT INTENDED TO BE USED AS A SUBSTITUTE FOR A FURNACE TO HEAT AN ENTIRE HOME.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 15 Figure 44 The FBK-100/200 Blower Kits are design cer- tified by Warnock Hersey for use with these appliances. Always check local building codes. Installation of the FBK Blower Kits must comply with local regulations as well as the National Electric Code.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 16 Figure 47 Glass Doors If glass doors are to be installed on these fireplaces, refer to specific installation instruc- tions packed with the glass doors. Use only the doors that are listed for use with these fire- places.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 17 Figure 48 A B D C C Hearth Extension Dimensions A 16" B 33" C 8" D 49" Note: To convert inches to millimeters divide by 0.03937 Answer - The minimum required thickness of the Micore 160 is .
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 18 Secure the hearth extension to the floor to prevent possible shifting. FINISH TO YOUR TASTE There are a wide variety of “finished looks” for these fireplaces, from formal wall decor with elaborate mantels to rustic wood paneling or warm brick facings.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 19 Chimney Section 63L10 FTF8-12 63L13 FTF8-18 63L14 FTF8-36 63L15 FTF8-48 Canadian 62L92 FTF8-18C Chimney Section 62L93 FTF8-36C 63L38 F8F6 Flashing 6.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE. 20 Printed in U.S.A. © 2007 by LENNOX HEARTH PRODUCTS P/N 850,046M REV. N/C 01/2007 The manufacturer reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products.
デバイスLinksys RDI-36-H HCI-36-Hの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Linksys RDI-36-H HCI-36-Hをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはLinksys RDI-36-H HCI-36-Hの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Linksys RDI-36-H HCI-36-Hの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Linksys RDI-36-H HCI-36-Hで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Linksys RDI-36-H HCI-36-Hを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はLinksys RDI-36-H HCI-36-Hの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Linksys RDI-36-H HCI-36-Hに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちLinksys RDI-36-H HCI-36-Hデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。