Model 84 76 Thermostat with Event-Based ™ Air Cleaning READ AND SAVE THESE INSTRUCTIONS Safety & Installation Instructions.
2 3 Installation location recommendations ................................................................ 3 Outdoor temperature sensor (optional) ................................................................ 4 Thermostat mounting .................
4 5 OUTDOOR TEMPERA TURE SENSOR (OPTIONAL) Outdoor temperature can be measured by attaching an 8052 sensor to the S1 and S2 terminals. System setting #05 (Remote sensor) is used to enable sensor .
6 7 WIRING TERMINAL Wire specifications 18-24 gauge thermostat wire Installation notes • Ensure power at the HVAC equipment is off. • Loosen screw terminals, insert stripped wire and re-tighten. • Push the excess wire back into the opening and plug the wall opening to prevent drafts.
8 9 INST ALLA TION WIRING – SINGLE TRANSFORMER (USE JUMPER WIRE) FOR HEA T PUMP SYSTEM 1st AUX HEA TING 1st COMPRESSOR FA N REVERSE VA LV E FA ULT DETECT 2nd AUX HEA TING 2nd COMPRESSOR OUTDOOR TEMP.
10 11 SETUP & TESTING SYSTEM SETUP INSTRUCTIONS (CONTINUED) The Model 8476 thermostat has the option of being used in heat pump or heat/cool systems. Switch SW1 located on the back of the thermostat’ s face is used to select this. System setting number 00 will only be shown on these models to display the position of SW1.
12 13 SETUP & TESTING System setting Setting range, default in bold 09 1st stage differential 1°F (0.5°C) 1°F to 4°F (0.5°C to 2°C) 10 2nd stage differential 1°F (0.5°C) 1°F to 4°F (0.5°C to 2°C) 11 3rd stage differential (heat pump only) 1°F (0.
14 15 SYSTEM TEST MODE The system test mode is used to test a system after installation. The outputs of the thermostat can be manually activated one at a time to test their function. The following instructions show how to enter the test mode and turn outputs on and off.
16 17 SETUP & TESTING T est steps for Heat / Cool Step Key Input System Setting Display (Output) #2 01 HEA TING ON (W) 02 HEA TING ON (W2) 01 COOLING ON (Y) 02 COOLING ON (Y2) 01 FAN ON (G) #50 He.
18 19 QUICK REFERENCE TO CONTROLS & DISPLA Y NOTE: BACKLIGHT IS ACTIVA TED WITH FIRST BUTTON PRESS AND AUTOMA TICALL Y TURNS OFF . Includes Event-Base d ™ Air Cleaning CURRENT INDOOR TEMPERA TUR.
20 21 TROUBLESHOOTING DISPLA Y IS BLANK • Check circuit breaker and reset if necessary . • Make sure power switch at heating & cooling system is on. • Make sure furnace door is closed securely . • If thermostat is battery powered, make sure fresh AA alkaline batteries are correctly installed.
22 23 SPECIFICA TIONS Electrical Operating voltage 24 VAC (18 – 30 VAC) Current Maximum: 2.5A (total), 1.0A (single output) Maximum surge current: 5A Power supply Dual power . Can be battery or 24 VAC powered. When both the sources are available, battery will be used as back up power .
24 P.O. Box 1467 • Madison, WI 53701-1467 • Phone: 800/334-6011 • Fax: 608/257-4357 www.aprilairepartners.com 61000893 12.11 B2205693A Patent Pending © 2011 Aprilaire – A division of Research.
デバイスAprilaire 8476の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Aprilaire 8476をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはAprilaire 8476の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Aprilaire 8476の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Aprilaire 8476で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Aprilaire 8476を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はAprilaire 8476の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Aprilaire 8476に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちAprilaire 8476デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。