Quattro ™ DC Elevator Drive Technical Manual TM7310 rev 01 © 2006 Magnetek Elevato r.
WARRANTY Standard products manufactured by the Company are warranted to be free from defects in workmanship a nd material for a period of one year from t he date of shipment, and any products which are defect ive in workmanship or material will be repaired or replaced, at the Company’s o pti on, at no charge to the Buyer.
Table of Contents Introducti on ............................................................................................................. 10 Drive Ratings and Specific ations ........................................................................
LS Power Data D3 submenu ....................................................................................................... ...... 69 Utility U0 menu ................................................................................................
Quattro DC Quick Parameter Reference Sub menu Parameter Units Range Default Site Setting A1 Drive A1 Submenu – See Drive A1 submenu on page 30. fpm 0.0 – 1500.0 400.0 A1 CONTRACT CAR SPD m/s 0.000 – 8.000 2.000 A1 CONTRACT MTR SPD RPM 30.0 – 3000.
Quattro DC Quick Parameter Reference Sub menu Parameter Units Range Default Site Setting A2 S-Curves A2 Submenu – See S-Curve s A2 submenu on page 39. ft/s 2 0.00 – 7.99 7.99 A2 ACCEL RATE 0 m/s 2 0.000 – 3.999 2.435 ft/s 2 0.00 – 7.99 7.99 A2 DECEL RATE 0 m/s 2 0.
Quattro DC Quick Parameter Reference Sub menu Parameter Units Range Default Site Setting A3 Multistep Ref A3 Submenu – See M ultistep Ref A3 submenu on page 41. ft/min -3000.0 – +3000.0 0.0 A3 SPEED COMM AND 1 m/sec -16.000 – +16.000 0.000 ft/min -3000.
Quattro DC Quick Parameter Reference Sub menu Parameter Units Range Default Site Setting A5 Line Side Power converter A5 Submenu – See Line Side Power Converter on page 46. A5 Id REG PROP GAIN none 0.00 – 9.99 0.30 A5 Id REG INTGRL GAIN none 0 – 999 10 A5 Iq REG PROP GAIN none 0.
Quattro DC Quick Parameter Reference Sub menu Parameter Units Range Default Site Setting C1 User Switches C1 Subm enu con tinued … C1 PreTorque SOURCE none − none − analog Input − serial NONE .
Quattro DC Quick Parameter Reference Sub menu Parameter Units Range Default Site Setting C2 Logic Inputs C2 Submenu – See Logic Inputs C2 submenu on page 61.
Quattro DC Quick Parameter Reference Menu Parameter Unit D1 Elevator Data Submenu D1 Speed Command ft/min or m/sec D1 Speed Reference ft/min or m/sec D1 Speed Feedback ft/min or m/sec D1 Speed Error f.
Quattro DC Introduction Introduction Drive Ratings and Specifications The Quattro drive is designed for conn ection to a 4 wire grounded 3-phase input along with a single-phase 230 VAC cont rol power input.
Quattro DC Introduction Drive Model Numbers The Quattro DC drive is currently available with three different output currents and a variety of options. The enclosure options co nsist of a customer I/O panel and a side Dynamic Braking Resistor box.
Quattro DC Startup Guide Quattro startup guide Initial Inspection Unpacking 1. When unpacking, check dri ve for any shipping damage. 2. The 200A and 250A versions of the Quattro arrive in separate shipping containers, which require connection in t he field.
Quattro DC Startup Guide − Open F1 and F2 and ensure control po wer brought into fuse F1 and F2 is 230VAC! IMPORTANT: Double-check all the power wires and motor wires to make sure that they are securely tightened down to their respective lugs (loose wire co nnections may cause problems at any time).
Quattro DC Startup Guide 2. CONTRACT MTR SPD (A 1) parameter programs the motor speed at elevator contract speed in RPM. Line voltage setup Enter / Verify the line voltage parameter: 1. INPUT L-L VOLTS (A5) parameter programs the line voltage level Auto tune Procedure Refer to page 95 on how to implement Auto tune if desired.
Quattro DC Interconnections Interconnections QUATTRO S I GNAL CONNECT I ONS – A6 TB1 11 1 2 3 4 5 6 7 8 9 44 45 TB1 47 48 25 26 27 28 29 30 31 32 33 45 21 22 23 24 12 13 14 1 3 5 8 10 12 34 35 36 37.
Quattro DC Interconnections 16 GND L( 1 ) L( 2 ) L( 3 ) * N o te 1 * N o te 1 H( X) H( 1 ) Pr ovi d ed f or th e P rim a ry si de of t he 230V co nt r ol power t r ansfor m e r T o Q u a ttro D riv e .
Quattro DC Interconnections Contact Cfirm Encoder Connections The Quattro DC has conn ections for an incremental two-channel quadrature encod er. The Quattro DC requires the use of an encoder coupled to the motor shaft. The encoder power can be either a +5VDC or +12VDC.
Quattro DC Interconnections 18 Figure 6: Logic Inputs (External Supp ly) Analog Inputs The Quattro DC has two non-pro grammable differential analog input channels. • Analog input channel 1 is reserved for the speed command (if used). • Analog input channel 2 is reserved for the pre-torque command (if used) o r torque command source (if used).
Quattro DC Interconnections 19 Logic Outputs The Quattro DC’s seven programm able logic outputs are opto-isolated, open collecto r. The outputs are normally open and can withstand an applied maximum voltage of 30VDC.
Quattro DC Interconnections 20 For more on the gain or offset parameters, see section Drive A1 submenu on page 30. Analog Outputs The Quattro DC has two programm able differential analog output channels. The two analog output channel s were designed for diagnostic help.
Quattro DC Drive Sequencing Drive Sequencing NORMAL operating sequence 1. Motor field current is at Stand-By during drive idle. The No Faults relay is active. Full-Field and Run command signal s are OFF. Motor contactor Safety circuits may be open or closed.
Quattro DC Drive Sequencing c. Pre-charge contactor PCM is then pulled in. This provides resisto r limited inrush current to DC bus ca pacitors from AC mains and separat e rectifier.
Quattro DC Drive Operat ion and Feature Overview Drive Operation and Feature Overview The Quattro DC drive is a velocity and torque regulated motor drive desi gned specifically for operating elevators. Many of the features described below can be sel ectively programmed to customize an individual application.
Quattro DC Drive Operat ion and Feature Overview there will be no timed delay for current ramp- down. This time may be adjusted by the function RAMPED STOP TIME (A1). Over-Speed Test A reference speed multiplier is provided to help testing of the elevat or governor over-speed trip.
Quattro DC Drive Operat ion and Feature Overview Status Indicator Lights Five status indicator lamps are provided on the front panel of the drive. READY – (GRN) Power is applied to the drive, there are no drive Faults and drive is ready to Run when requested.
Quattro DC Parameters Parameters Parameter Introduction This section describes the parameter menu structure of the Magnet ek Operator, how to navigate this menu structure, and a detai led description of each para meter.
Quattro DC Parameters Menu Navigation The digital operator keys operate on three levels, the menu level, the sub-menu level and the entry level. At the menu level, they function to navigate between menus or sub - menus. At the sub-menu level, they navigate between sub-menus or menu items.
Quattro DC Parameters Parameter Tree Display D0 Adjust A0 → Elevator Data D1 • Speed Command • Speed Reference • Speed Feedback • Speed Error • Pre-Torque Ref • Ext-Torque Cmd • Spd Re.
Quattro DC Parameters Configure C0 Utility U0 Faults F0 → Password U1 • Ne w P as s wo rd • Enter Password • Password Lockout → Active Faults F1 • Display Active Faults • Reset Active Fa.
Quattro DC Drive Parameters A1 Adjust A0 menu Drive A1 submenu Parameter Description Units Default Range Hidden Item Run lock out fpm 400.0 0.0 – 1500.0 CONTRACT CAR SPD (Contract Car Speed) Adjusts the elevat or contract speed in feet per minute (fpm) or meters per second (m/s).
Quattro DC Drive Parameters A1 Parameter Description Units Default Range Hidden Item Run lock out TACH FILTER BW (Tach Filter Bandwidth) Breakpoi nt of tachometer / encoder feedback signal. rad/sec 100 1 – 100 Y N TA CH RA TE GA IN (Tach Rate Gain) Used to help reduce the effects of rope resonance.
Quattro DC Drive Parameters A1 Parameter Description Units Default Range Hidden Item Run lock out OVERSPEED LEVEL (Over speed Level) Sets the percentage of rated speed the drive uses (in conjunction with OVERSPEED TIME, below) to determine when an OVERSPEED fault occurs.
Quattro DC Drive Parameters A1 33 Parameter Description Units Default Range Hidden Item Run lock out EXT TORQUE BIAS (External Torque Bias) This param eter subtracts an effective vo ltage to the actual analog pre torque / torque command (channel 2) voltage signal.
Quattro DC Drive Parameters A1 34 Parameter Description Units Default Range Hidden Item Run lock out AN A O U T 1 GAIN (Digital to Analog #1 Output Gain) Adjusts the scaling for the Analog Output Channel #1.
Quattro DC Drive Parameters A1 Parameter Description Units Default Range Hidden Item Run lock out TRQ LIM MSG DLY (Torque Limit Message Delay) This parameter determines the amount of time the drive is in torque limit before the “HIT TORQUE LIMIT” alarm message is displayed.
Quattro DC Drive Parameters A1 Detailed descriptions GAIN CHNG LEVEL (Gain Change Level ) Works in conjunction with HI/LO GAIN SRC in menu C0. When the gain control source is set to internal, this parameter sets the speed reference level that controls the Hi/Lo gain switch.
Quattro DC Drive Parameters A1 SPD DEV LO LEVEL and SPD DEV HI LEVEL (Speed Deviation Low / High Level) These two functions are available to indicate how the speed feedback is tracking the speed reference. • Speed Deviation Low – indicates that the speed feedback i s tracking the speed reference within a defined range.
Quattro DC Drive Parameters A1 NOTCH FILTER FRQ (Notch Filter Center Frequ ency) Although originally created for gea rless applications where elevat or rope resonance is sometimes an issue, this filter affects the torque command output of the speed re gulator and will filter out specific frequencies.
Quattro DC Drive S-Curves A2 S-Curves A2 submenu The drive speed comman d is passed through an internal S-curve in order to produce the speed reference. In general, the S curve function takes an arbitrary speed comm and and generates a speed reference subj ect to the conditions that the maximum accel, decel and jerk rates not be exceeded.
Quattro DC Drive S-Curves A2 Parameter Description Units Default Range Hidden Item Run lock out ft/s 2 7.99 0.00 – 7.9 9 ACCEL RA TE 0 Acceleration rate limit m/s 2 2.435 0.000 – 3.999 N Y ft/s 2 7.99 0.00 – 7.9 9 DECEL RA TE 0 Deceleration rate limit m/s 2 2.
Quattro DC Multistep Ref A3 Submenu Multistep Ref A3 submenu The multi-step speed reference function is one possible way for the drive to accept speed command. To use this function, the user can enter up to fifteen speed commands (CMD1 – CMD15) and assign four logic inputs a s speed command selections.
Quattro DC Multistep Ref A3 Submenu Parameter Description Units Default Range Hidden Item Run lockout ft/min 0.0 -300 0.0 – + 300 0.0 SPEED COMMAND 1 Multi-step speed command #1 m/sec 0.000 -16.000 – +16.000 N Y ft/min 0.0 -300 0.0 – + 300 0.0 SPEED COMMAND 2 Multi-step speed command #2 m/sec 0.
Quattro DC Motor Side Power Convert A4 Submenu Motor Side Power Convert A4 submenu Parameter Description Units Default Range Hidden Item Run lock out ARM RESISTA NCE (Armature Circuit Resistance) Affects tuning of the armature current regulator. Load this parameter with known or measured value.
Quattro DC Motor Side Power Convert A4 Submenu Parameter Description Units Default Range Hidden Item Run lock out GAIN BANDWIDTH A (Gain Bandwidth Armature) If GAIN SELECTION (C1) is set to MANUAL, this parameter is used to convert ARM RESISTANCE (A4) and ARM INDUCTANCE (A4) into the integral and proportional gains used by the current regulator.
Quattro DC Motor Side Power Convert A4 Submenu Parameter Description Units Default Range Hidden Item Run lock out MAIN FAN CONTROL (Main Fan Control Select) Selects primary method of cooling fan control. − AUTO – All cooling fans turn OFF after Fan Off Delay time, after DSPR becomes active.
Quattro DC Line Side Power Convert A5 Submenu Line Side Power Converter A5 submenu NOTE: The only parameter that sh ould ever need to be adjusted is INPUT L-L VOLTS.
Quattro DC Motor A6 Submenu Motor Parameters A6 submenu Parameter Description Units Default Range Hidden Item Run lock out MOTOR ID (Motor Identification) This parameter allows for the selection of specific sets of motor parameters. This is yet to be determined for DC machines.
Quattro DC Motor A6 Submenu 48 Parameter Description Units Default Range Hidden Item Run lock out OVLD START LEVEL (Motor Overload Start Level) This parameter defines maxim um current at which motor can run continuousl y without triggering the motor overload.
Quattro DC Motor A6 Submenu Figure 14: Motor Overload Curv e . 110% 130 % 150% 170% 190% 210% 230% 250% 10 100 1000 10,000 current (percentage of rated motor current) default motor overload trip time .
Quattro DC User Switches C1 Configure C0 menu User Switches C1 submenu Parameter Description Default Choices Hidden Item Run lock out SPD COMMAND SRC (Speed Command Source) This parameter designates the source of the drive’s speed command.
Quattro DC User Switches C1 Parameter Description Default Choices Hidden Item Run lock out HI/LO GAIN SRC (High / low gain change s witch source) This parameter determines the source of the high / low gain switch.
Quattro DC User Switches C1 Parameter Description Default Choices Hidden Item Run lock out MOTOR ROTATION (Motor Rotation) This parameter allows the user to change th e direction of the motor rotation.
Quattro DC User Switches C1 Parameter Description Default Choices Hidden Item Run lock out PreTorque LATCH (PreTorque Latch) If Pre-T orque latching is NOT selected, the Pre-Torque signal must be valid when the speed regulator is command ed to run. For verification on timing, see NORMAL operating sequence o n page 21.
Quattro DC User Switches C1 Parameter Description Default Choices Hidden Item Run lock out OVERSPD TEST SRC (Overspeed Test Source) This switch determines the source of the overspeed test. Operation of the overspeed test function is specified by the OVRSPEED MULT (A1) parameter.
Quattro DC User Switches C1 Parameter Description Default Choices Hidden Item Run lock out EXT TORQ CMD SRC (Torque Command Source) Sets the source of an external torque command, if any.
Quattro DC User Switches C1 Parameter Description Default Choices Hidden Item Run lock out S-CURVE ABO R T (S-Curve Abort) This parameter, S-CURVE ABORT (C1), addresses how the S-Curve S peed Reference Generator handles a reduction in the speed command before the S-Curve Generator has reached its target speed.
Quattro DC User Switches C1 Parameter Description Default Choices Hidden Item Run lock out STOPPING MODE (Multi-step Stopping Mode Selection) When the speed command source is set to multi-step (SPD COMMAND SRC (C1)=multi- step), the parameter, STOPPING MODE (C1), determines the stopping mode of the Drive.
Quattro DC User Switches C1 Parameter Description Default Choices Hidden Item Run lock out AUTO STOP (Auto Stop Function Enable) When the speed command source is set to multi-step or serial (SPD COMMAND SRC (C1)=multi-step or serial), the parameter determines the stopping mode of the drive.
Quattro DC User Switches C1 Detailed descriptions HI/LO GAIN SRC (High / Low Gain Source) This parameter determines the sou rce of the high / low gain switch.
Quattro DC User Switches C1 The tracking delay shown is define d as (1/RESPONSE) seconds. The tracking delay is not effected by the gain reduce multiplier.
Quattro DC Logic Inputs C2 Submenu Logic Inputs C2 submenu (Logic Inputs 1-9) This parameter defines the function of the logic inputs. NOTE: The user can assign particula r functions to each input terminal. Only one function per terminal is allowed and mult iple terminals cannot have the same function (except “No Function”).
Quattro DC Logic Inputs C2 Submenu choices contact cfirm (Contactor closed) Feedback from an auxiliary contact on t he motor contactor. Default is that the drive expects a normally closed contact to energize the input w hen the contactor is not pulled in.
Quattro DC Logic Outputs C3 Submenu Logic Outputs C3 submenu LOGIC OUTPUT x (Logic Outputs 1-4) This parameter defines the function of the logic outputs. NOTE: The current setting of each parameter is displayed in all caps; all other choices in the list are displayed in lower case.
Quattro DC Logic Outputs C3 Submenu choices contin u ed ground fault (Ground Fault) The output is true when the sum of all phase current exceed s 50% of rated current of the drive. in low gain (In Low Gain) The output is true when the sp eed regulator is in “lo w gain” or response mode.
Quattro DC Analog Outputs C4 Submenu Any value over 100% will cause the analog channel to saturate. Description Analog Outputs C4 submenu With a gain of 1.0 and an offset of 0.0, 10V will indicate 100% or full value based on programmed values. For ex ample, with the above scenario of a gain of 1.
Quattro DC Display Data D0 Menu Parameter Description Display D0 menu Elevator Data D1 submenu Units Hidden Item SPEED COMMAND (Speed Command) Monitors the speed com mand before the speed reference generator (i nput to the S-Curve). This command comes from either multi-step references, speed comma nd from analog channel , or the serial channel.
Quattro DC Display Data D0 Menu Parameter Description Units Hidden Item RX COM STATUS (continued) Bit Severity Name Description/Reason 7 Info RX_INVALID_MONITOR_ID (Not available in Mode 2) Set if the Monitor_I d received in the run message is not in rang e.
Quattro DC Display Data D0 Menu Parameter Item MS Power Data D2 submenu Description Units Hidden ARM CURRENT (Armature Current) Measured motor armature current amps N FIELD CURRENT (Field Curr ent) Me.
Quattro DC Display Data D0 Menu LS Power Data D3 submenu Parameter Description Units Hidden Item LS PWR OUTPUT (Line Side Power Output) Estimated power transfer to and from the AC Line. Value is positive when drive is pulling power from the line, and negative when drive is deliv ering power back to the line.
Quattro DC Utility U0 Menu Utility U0 menu U0 Parameter Description Default Choices Hidden Item Run lock out U1 PASSWORD For mo re in formatio n, see P o n page 7 .
Quattro DC Utility U0 Menu The following three different screens a re used by the password function: NOTE: Remember that a valid password must be entered at the ENTER PASSWORD screen before the password lockout condition can be changed.
Quattro DC Utility U0 Menu Overspeed Test via Serial Chann el • Press the ENTER key again. The sub menu LED will go out and data ent LED will turn on.
Quattro DC Utility U0 Menu Restore Motor Defaults This function resets the parameters in the MOTOR A6 sub-menu to the defaults. The following shows how to restore the motor defaults: Press the enter k.
Quattro DC Utility U0 Menu MS S/W DATE Screen Gives the date of the released motor sid e code version. MS S/W TIME Screen Displays the time of the released motor side code version. MS FPGA REV Screen Gives the revision number for the motor side FPGA. MS CUBE ID Screen Displays the cube identification number of the drive.
Quattro DC Utility U0 Menu LS CUBE ID Screen Displays the cube identification number of the drive. This number identifies specific drive ratings related to detected equipm ent hardware. HEX MONITOR (Hex Monitor) The hex monitor was designed for fault a nd parameter diagnostics.
Quattro DC Fault F0 Menu Fault F0 menu The FAULTS F0 menu does not access settable parameters; instead, it provides a means of examining the drive’s active faults and the fault history. This menu also allows for clearing of a ctive faults in order to get the drive ready to return to operation after a fault shutdown.
Quattro DC Fault F0 Menu FAULT HISTORY This sub-menu contains a li st of up to the last sixteen faults. NOTE: The fault history is not affected by the fault reset or a power loss. The fault history can only be cleared by a function in this sub - menu.
Quattro DC Maintenance Maintenance Maintenance Overview Preventive maintenance is primarily a matter of routine inspection and cleaning. The m ost important maintenance factors are the following: Is t.
Quattro DC Troubleshooting There are four means of fault annunciation: Troubleshooting Faults and Alarms Two classes of warning s are reported by the Drive; these are identified as Faults and Alarms.
Quattro DC Troubleshooting Drive Faults, Alarms, and operator messages al ong with possible cause s and corrective actions are listed below. Note: • fault - a severe failure that will stop a drive if it has been running and prevent the drive from starting as long as it is present.
Quattro DC Troubleshooting Name Description Possible Causes & Correctiv e Action Brk Pick Flt The brake pick command and the brake feedback did not match for the time specified with Brake Pick Time parameter.
Quattro DC Troubleshooting Name Description Possible Causes & Correctiv e Action Cont Pwr Lost Motor contactor power was removed while the drive was commanding it to be energized.
Quattro DC Troubleshooting Name Description Possible Causes & Correctiv e Action Drive Ovrload The drive has exceeded the drive overload curve. Excessive Field Weakening Verify Weak Field moto.
Quattro DC Troubleshooting Name Description Possible Causes & Correctiv e Action Extrn Fault 2 User defined external logic fault input ...Closure of this contact will cause the drive to declare th.
Quattro DC Troubleshooting Name Description Possible Causes & Correctiv e Action Field Overcurrent An over current condition has been detected in the field circuit by the hardware.
Quattro DC Troubleshooting Name Description Possible Causes & Correctiv e Action LS BRDG GND The hardware has detected a ground fault on the line side power bridge. IGBT Breakdo wn Inspect and measure for physical volta ge breakdown damage on IGBTs and DC bus LS Charge The DC bus did not charge up within the expected time.
Quattro DC Troubleshooting Name Description Possible Causes & Correctiv e Action LS Hit Current LMT (alarm) The line side is or was being limited by the motoring current limit or regenerative current limit setting.
Quattro DC Troubleshooting Name Description Possible Causes & Correctiv e Action LS Overtemp (fault) One or more of the IGBT modules on the line side power bridge has exceede d 105 ° C (221 ° F).
Quattro DC Troubleshooting Name Description Possible Causes & Correctiv e Action LS PCU Data PCU parameters che cksum is invalid on the line side. Parameters Corrupted Check & re-enter Line Sid e parameters and power cycle the drive LS Phase The line side converter has detected the loss of one or more phases of the AC line.
Quattro DC Troubleshooting Name Description Possible Causes & Correctiv e Action ME Cont Pwr Motor contactor power wa s removed while the drive was commanding it to be energized. Contactor Problem Check motor co ntactor pow er ME Pwr Avail Motor contactor power wa s not available when the drive was commanded to sta rt.
Quattro DC Troubleshooting Name Description Possible Causes & Correctiv e Action No Field Cable A disconnected field ca ble has been detected. Missing Cable Check for def ective of missing fie.
Quattro DC Troubleshooting Name Description Possible Causes & Correctiv e Action Overvolt Flt The DC bus voltage has exceeded the maximum allowed value.
Quattro DC Troubleshooting Name Description Possible Causes & Correctiv e Action Setup Fault 6 This fault is decla red if the multi-step speed references have exceeded a defined limit, which is defined in terms of a percentage of contract speed (CONTRACT CAR SPD parameter).
Quattro DC Troubleshooting Name Description Possible Causes & Correctiv e Action Undervolt Flt Generated during a run condition when the DC bus voltage drops below the user specified percent of the DC link voltage. The fault level is specified by the UV Fault Level parameter.
Appendix – Auto Tune Procedure − Armature Inductance IMPORTANT: Brake must be set while auto tune is running for valid data. Appendix Auto Tune Procedure The following details the procedure on how to run auto tune on a Quattro DC drive.
Appendix – Inertia Calculation Inertia Calculation Appendix The Quattro DC software can b e used to calculate the inertia of the entire elevator, which is used for accurate tuning of the speed regulator. The following is a step-by-step procedure for using the Quattro DC to estimate the elevator system inertia.
Appendix – EMC Compliance Appendix EMC Compliance The Quattro DC drive require s EMC Compliance (EN12015 and EN12016) to function at the highest performance leve l possible. The following pages will provide the user with an installation guideline for fiel d personnel regarding proper metallic bonding for EMC compliance.
Appendix – Re-Assembly Procedure 8 9 0 0 Appendix Re-Assembly Procedure for 200A / 250A drives The followings tools are require d to properly reconnect the two cabinets: − Socket wrench and ratchet with 150mm (6.0”) extension − 10mm hex socket − #2 Phillips screwdriver, 50mm (2.
Appendix – Re-Assembly Procedure 1 22 The connections are a s follows: Figure 2 : Motor Side Module Position 3. Make the following electrical connection s from the DC Bus Board in the Line Side Converter enclosure flowing straig ht across to the PWM DC Bus Board in the Motor Side Inverter enclosure.
Appendix – Re-Assembly Procedure The positive voltage for F1 is located on A24-TB1-2 (labeled SW OUT). The negative voltage for F2 is located on A24- TB1-3 (labeled DC- O UT). Use a #2 Phillips screwdriver with 50mm (2”) shaft to tighten connections to 2.
Appendix – Re-Assembly Procedure 7 Auxiliary Connection Figure 2 : Motor Contactor Connections 9. Using a flat screwdriver, 3mmx100mm (1/8”x4”), torque t he following auxiliary terminals to 2.0 N-m (17.5 in-lb s) on the right side of the motor contactor.
Appendix – Power Ratings Appendix Control Power Consumption Control Power (230VAC) consumption (max)* Drive Model Number kVA Watts Current (Amps) QDC125-xxxx-xxx 0.
Appendix – Wire Terminal Specs Power Terminals Control Wiring Terminals Appendix Wire Terminal Specs English / Imperial Units Ground Terminals Control Power Terminals (F1 & F2) 230VAC Control Wi.
Appendix – Dimensions and Weights Dimensions* Appendix Dimensions / Weights Excluding customer I/O panel Height Width Depth Weight Drive Model Number inches mm inches mm inch es mm lbs kg QDC125-xxx.
Appendix – Dimensions and Weights 105 0 Figure 3 : 125A unit Dimensions without optional Customer I/O Panel.
Appendix – Dimensions and Weights 1 Figure 3 : 200A and 250A unit dimensions without optional Cu stomer I/O Panel 106.
Appendix – Dimensions and Weights 2 Optional System Panel Figure 3 : 125A unit Dimensions with Optional System Panel 107.
Appendix – Dimensions and Weights Figure 33: 200 / 250 A unit Dimensions with Optional System Panel Optional System Panel 108.
Appendix – Component Locations Figure 34: 125A Component Lo cations Appendix Component Locations PCM UTM Control Power EMI Filter A C Powe r EMI Filte r Contactor Control Board (A9) Motor Voltage Fe.
Appendix – Component Locations 5 3-Phase In p ut Powe r Control Powe r EMI Filte r PCM Control Powe r Fuses (F1 & F2) Motor Voltage Feedback Board ( A8 ) Cooling Fan Status LEDs and Operato r UT.
Appendix – Component Locations 6 Line Side Main Control Board (A1) Line Side Product Interface Board (A3) Line Side Cube I.D. (A25A3J P10) Magnetek Operator Status LEDs Motor Side Cube I.
Appendix – Component Locations 7 DC Bus Capacitor PCB A ssembl y Pre-Char ge PCB Current Transducers IGBT / Gate Assembly Bus Discha rge Resistor Figure 3 : 125A IGBT Heatsink Assembly Note: The Pow.
Appendix – Component Locations 8 Line Side Main Control Board (A1) Line Side Product Interface Board (A3) Line Side Cube I.D. (A25A3J P10) Magnetek Operator Status LEDs Motor Side Cube I.
Appendix – Component Locations Pre-Char ge PCB IGBT / Gate Assembly DC Bus Capacitor PCB A ssembl y Current Transducers Figure 39: 200 / 250 A Motor Side Power Section 114.
Appendix – Component Locations 0 1 15 ( + ) 3 24 6(-) A1 A2 Optional Dynamic Braking Resistor To Motor Inverter Figure 4 : Motor Contactor Connections TB1 TB2 RS422 TB1-25 TB1- 1 TB1-48 TB1-24 TB2-8.
Appendix – Spare Parts List Appendix Spare Parts Quattro DC Drive Quantity Per Drive Drive Rating Reference Designator Magnetek kit Number Description Description Main Control PCB (Line Side) Contro.
Appendix – Spare Parts List Quantity Per Drive Drive Rating Reference Designator Magnetek kit Number Description Description 125A A26A4JP10 LA46S03842-0600 1 200A A26A4JP10 LA46S03842-0620 1 Cube ID.
Appendix – Spare Parts List Quantity Per Drive Drive Rating Reference Designator Magnetek kit Number Description Description 125A LA46S03828-1110 200A LA46S03828-1150 Control Tray Includes: 1. Fully tested door assembly w ith cables. Prewired control tray with power supply and interfacing cables.
119 Brk Pick Flt .................................................... 81 BRK PICK FLT ENA user switch .................. 54 Index A A to D F ault .................................................... 80 A0 - Adjust Menu ................................
FULL FLD AMPS paramet er......................... 47 Dir Conf lict ..................................................... 82 Full Fld Time Fault ........................................ 85 DRIVE ENABLE logic input ........................... 62 Drive Ov rload .
121 RUN COMMANDED logic output.................. 64 LS DCU Data Fault ........................................ 86 LS Hit Current Lmt Alarm .............................. 87 LS HW/SW Fault ...........................................87 LS IGBT Fault ...
U2 - Hidden Items Submenu ........................ 71 U3 - Units Submenu ..................................... 71 U4 - Overspeed Test Submenu .................... 71 RUN UP logi c input ........................................ 62 S S-Chain Event .....
.
QUATTRO DC Data subject to change without notice. Qu attr o is a trademark o f Magnetek, Inc. Magnetek Elevator Products N50 W13775 Overview Drive Menomonee Falls, Wisconsin 53051 (800) 236-1705, (262) 252-69 99, FAX (262) 790-4 142 http://www.elevatordrives.
デバイスMagnetek Quattro DC Elevator Driveの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Magnetek Quattro DC Elevator Driveをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはMagnetek Quattro DC Elevator Driveの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Magnetek Quattro DC Elevator Driveの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Magnetek Quattro DC Elevator Driveで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Magnetek Quattro DC Elevator Driveを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はMagnetek Quattro DC Elevator Driveの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Magnetek Quattro DC Elevator Driveに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちMagnetek Quattro DC Elevator Driveデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。