AquaStarメーカー125B NGLの使用説明書/サービス説明書
ページ先へ移動 of 20
W ARNING : Improper inst allation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer , service agency or the gas supplier .
2 This well engineered, gas water heater has been specially designed to operate as a circulating water heater . FEA TURES - High Quality Materials for Long Working Life. - Copper heating coils for endless supply of hot water . - Safety thermocouple at pilot burner .
3 D861_059 MINIMUM INST ALLA TION CLEARANCES FROM COMBUSTIBLE AND NON COMBUSTIBLE MA TERIALS FOR ALCOVE OR CLOSET INST ALLA TIONS FRONT VIEW SIDE VIEW AQUAST AR MODEL 125BL * Some local codes require .
4 If you are using the AquaStar for combined space heating and potable water heating (see schematic diagram below) , all piping and other components connected to the system must be suit able for pot a.
5 7 . Correct gas pressure is critical for the optimum operation of this heater (see specifications on page 2). Gas piping must be sized to provide the required pressure at the maximum output of the heater , while all the other gas appliances are in operation.
6 dilution of flue gases. Appliances located in confined spaces: The confined space must be provided with two permanent openings, one commencing within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure.
7 Fig. 3 - V ent Adaptor for High Altitude Canadian Installations W ARNING : Failure T O INCREASE THE VENT SIZE TO SIX INCHES AND/or assure that the manifold pressure is set to proper value listed for applications at high altitudes will cause unsafe venting, asphyxiation, and will void CSA Certification.
8 GAS PIPING , CONNECTIONS and Gas Regulator Before connecting the gas supply , check the rating plate on the right side of the front cover to be sure that the heater is rated for the same gas to which it will be connected.
9 THREADED ASSEMBL Y SWEA TED ASSEMBL Y 1/2” FLEX PIPE PRV TO APPROPRIA TE DISCHARGE S FITTING PIPE PRV TO APPROPRIA TE DISCHARGE 1/2” FLEX Fig. 6-Plumbing connections for the Aquastar 125BL NOTE: Do not apply soap solution to pilot filter screen or pilot orifice area.
10 Fig. 7 - Pressure Relief V alve Connecting the pressure relief valve (PRV) A listed pressure relief valve supplied with the heater must be installed at the time of installation. No valve is to be placed between the PR V and the heater . No reducing coupling or other restriction may be installed in the discharge line.
11 T o clean the pilot burner and/ or the pilot orifice : Turn off the gas at the unit. Remove the cover of the heater . T o do so, remove incandescent particle tray and unscrew the central screw located at the bottom of the front cover . Pull main cover out toward you and lift up and out.
12 C . Gas regulator may be shut or damaged. 2. In-line AquaStar gas regulator jammed (usually on LP gas) Replace or unlock the regulator . Note: The regulator furnished with the heater is designed for low gas pressure. Excessive pressure will lock it up (propane only).
13 WA TER IS TOO HOT 1 . Gas flow is higher than necessary . Move gas control slide to the left. 2. T emperature (aquastat) control is set too high If unit is plumbed in a recirculating loop system the aquastat temperature relay for the primary circulator pump is possibly set too high.
14 HOT W A TER TEMPERA TURE FLUCTUA TES 1. Cold water is mixing with the hot water between the AquaStar and the outlet (if not being used with a circulator pump) See #5 under “ Burners do Not Ignite When Hot Water Turned On ” . 2. Storage in tank (recirculating system) has not fully recovered S torage capacity in t ank is inadequate.
15 Fig. 10 - Diagram of AquaS t ar 125 BL 2 4 6 7 1 5 8 10 1. Heat exchanger 2. Pilot assembly 3. Burner manifold gas pressure test nipple 4. Pilot gas tubing 5. Main gas burner 6. Gas valve 7. Gas control slide 8. Piezo igniter 9. Location of pressure tap nipple 10.
16 Fig. 1 1 - INTERIOR COMPONENTS DIAGRAM AND P ARTS LIST.
17 Fig. 1 1 INTERIOR COMPONENTS DIAGRAM AND P ARTS LIST 125BL 1 Cover ¤ 8 705 421 031 2 Cap cover ¤ 8 703 304 01 1 3 W ater connection gasket ¤ 8 710 103 043 4 Draft divertor ¤ 8 705 505 354 5 Hea.
18.
19.
Replacement Parts available from North American Distributor CONTROLLED ENERGY CORP . 340 Mad River Park W ait sfield, V ermont 05673 Phone 800-642-31 11 Fax (802) 496-6924 ww w .controlledenergy .com techsuppport@controlledenergy .com VULCANO T ermodomésticos S.
デバイスAquaStar 125B NGLの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
AquaStar 125B NGLをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはAquaStar 125B NGLの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。AquaStar 125B NGLの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。AquaStar 125B NGLで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
AquaStar 125B NGLを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はAquaStar 125B NGLの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、AquaStar 125B NGLに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちAquaStar 125B NGLデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。