WARNING : Improper installation, adjustment , alterat ion, service or maint enance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier .
2 6 720 606 518 This well engineered, gas water heater has been specially designed to operate with incoming pre-heated water: It operates on the principle of heating water instantaneously “on demand”. When a hot water faucet is opened, cold water flows through the coils of the heat exc hanger in the Aquast ar .
3 6 720 606 518 D861_059 M I N I M U M I N S T ALLA TI O N C LE ARAN C E S FR O M CO M B U S TI B LE AN D N ON C OM B U S TI B LE MA TE R IALS FO R AL C OVE OR C L O SET I N S T ALLA TI ON S F RO NT V.
4 6 720 606 518 P RO PE R L OCA TI ON FOR I N ST ALLI NG Y OU R HEA T ER C arefully select the location of your new heater . F or your safety and for proper heater operation, you must provide an abundant supply of combustion air and a proper venting installation.
5 6 720 606 518 WARNING: Flammable materials, gasoline, pressurized containers, or any other items or articles that are pot entially fire hazards must NOT be placed on or adjacent to the heat er . T he appliance area must be kept free of all combustible materials, gasoline and other flammable vapors and liquids.
6 6 720 606 518 Fig. 1 - Mounting the Heater Fig. 2 - Inc andescent Particle T ray Illust ration The incandescent particle tray (shipped loose in the carton with the water heater) must be attached at the bottom of the water heater front cover at the time of installation.
7 6 720 606 518 VENTING V ent pipe connect ion. WARN I NG: Do not reduce the vent pipe size . See Fig . 3 for high altitude inst allations The heater must be vented to the outside following all local ordinances and specifications for installing a gas appliance vent or chimney .
8 6 720 606 518 MASO NRY CH I MN EY : Masonry chimneys shall be built and installed in accordance with N FP S 2 1 1 or local codes . A minimum 5” diameter gas vent pipe (metal double wall T ype B ), or an approved clay flue liner or a listed c himney lining system must be used when venting into a naturally drafting, internal masonr y chimney .
9 6 720 606 518 Fig. 3 – Vent Adaptor for High Altit ude Installat ions 5” X 6” ADAPT O R US E D ON H IG H AL TITU DE T o check t he draft : Close all doors and windows to the outside. T urn on all appliances that force air out of the building .
10 6 720 606 518 GAS CONNECTIONS and Gas Regulator NO TE : T he Aquast ar 1 25 B”S” is supplied wit h a gas pressure regulator t hat must be installed on t he heater before attaching the gas supply line. See figure 5. Failure to install the gas regulator as shown in figure 5 will be a violation of CSA certific ation of t he unit .
11 6 720 606 518 The water heater must be isolated from the gas supply piping system by closing the manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or more than 0.
12 6 720 606 518 O PERA T ING INS T R U C TI ONS Before proceeding with the operation of the heater make sure that the system is filled with water . Open the cold water inlet supply to the heater fully .
13 6 720 606 518 Fig. 8 - Characteristic Pilot Flame 3mm Correct gap between pilot burner tip and piezo electrode tip Piezo Electrode Air screen filter 1 0mm 3/8” Piezo Electrode Thermocouple T o clean t he pilot burner and/ or t he pilot orifice : T urn off the gas at the unit .
14 6 720 606 518 If some burners have yellow flames while others have good flames, it is likely that dust, lint or spider webs have partially clogged the burner venturis.
15 6 720 606 518 T o test the thermocouple, disconnect the thermocouple lead to the ECO. Insert a multi-meter probe into the thermocouple lead and attach or hold the other lead to the metal gas valve (DC common). Light the pilot flame and hold button, meter reading should be 24 mVDC or more.
16 6 720 606 518 See specifications on page 2. Unlike storage tank water heaters, the burners of a tankless water heater must be very powerful to heat water instantaneously since they do this only at the time hot water is actually being used. It is therefore imperative that the gas pressure requirement be met exactly .
17 6 720 606 518 1 . Heat exchanger 2. Pilot assembly 3. Burner manifold gas pressure test nipple 4. Main gas burner 5. Pilot gas tubing 6. Gas valve 7 . Piezo igniter 8. Location of pressure tap screw 9. W ater valve 1 0 . Gas inlet gas pressure test nipple 5 1 4 7 9 3 10 6 2 8 Fig.
18 6 720 606 518 A Q 1 25 BS Fig. 1 1 - I NTER IOR CO MP ON ENTS DIAGR AM AN D P ARTS LI ST.
19 6 720 606 518 Fig. 1 1 INTERIOR COMPONENTS DIAGRAM AN D P ARTS LI ST 1 25B S 1 Cov er 8 705 421 033 2 Cap cov er 8 703 304 011 3 Water connection gasket 8 710 103 043 4 Draf t divertor 8 705 5 05 3.
20 6 720 606 518 Fig. 1 2 - Flow chart of Aquastar 1 25 BS.
21 6 720 606 518 LI M ITE D W AR R ANT Y Aquast ar General Aquastar water heaters are warranted by the Manufacturer ( B OSC H) through BB T North America .
22 6 720 606 518.
23 6 720 606 518.
Replacement Parts available: BB T NO RTH AM E R IC A Bosch Group Bosch W ater heating 340 Mad River Park W aitsfield, V ermont 0567 3 Phone 80 0-642-3 1 1 1 Fax (802) 496-6924 www .boschhotwater .com tec hsupport@boschhotwater .com VULCANO T ermodomésticos S.
デバイスAquaStar 125B NGSの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
AquaStar 125B NGSをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはAquaStar 125B NGSの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。AquaStar 125B NGSの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。AquaStar 125B NGSで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
AquaStar 125B NGSを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はAquaStar 125B NGSの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、AquaStar 125B NGSに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちAquaStar 125B NGSデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。