Central Controller Model: G-50A Mitsubishi Electric Air-conditioner Network System Instruction Book Contents 1. Safety …………………………………………… ……………………….
.
-1- 1 . SAFETY Please take a moment to re view these saf ety precautions. They are pro vided f or your protection and to pre vent damage to the controller .
-2- 2 . Product Features [ 1 ] User operating function The central controller is capable of controlling up to 50 air conditioner units. It supports the following operating 1. Virtually almost functions operated by local remote controller are supported.
-3- The central controller is supplied power from the P AC-SC50KUA Power Supply Unit via the M-NET transmission line and DC power line. The DC power between the P AC-SC50KUA Power Supply Unit and the central controller should be 10m or less. The central controller allows to be connected to M-NET transmission line at any position.
-4- Cool (Dr y) oper ation : 19 30 ˚ C / 67 87 ˚ F Heat operation : 17 28 ˚ C / 63 83 ˚ F A uto operation : 19 28 ˚ C / 67 83 ˚ F DC24V ,0.02A(Maximum loading) P ower receiv ed from P AC-SC50KU A P ower Supply Unit via M-NET tr ansmission line. DC12V ,0.
-5- ectiv e or per group . [V entilation operation] Low speed/High speed/V entilation OFF The ov erall status lamp displa ys conditions of the collective statues. Item Operation Monitor Prohibit local remote control Specification The specific functions of a local remote controller can be prohibited as a collective or per group .
-6- G-50A management range Unit Unit Another system controller management range of G-50A Management range M-NET Gatew a y management range Unit Unit ent OA processing unit, LOSSNA Y and slav e system controllers) are performed on the group setting screen.
-7- Master system Group Group Group controller Slav e system controller Group Group Group Master system controller 1 Master system controller 2 Group Group Group Group Master system controller 1 Master system controller 2 Slav e system controller NO TE : The f ollowing group setting cannot be perf or med.
-8- Display P 4 NEXT Continuously press 04-2002 MON and (2 seconds or longer) G-50A 001 PROHI BITED 01 3 - 2 Displa y Screen The lamp indicates the unit op- eration condition.
-9- POWER GND 12VDC 9 1 CN2 5 1 CN1 RS232C Ethernet ABS M-NET BA CK 6 ADDRESS SETTING 7 FUNCTION SETTING 8 IP ADDRESS SETTING VER. LAN changeover s witch Ref er to section "5. Initial setting ( page 25 ) " for e xplanation of the operation of these s witches.
-10- 4 . User operation Used the following two screens when user operation is performed. Operation monitor screen This screen displays ON/OFF and malfunction condition of unit. Operation setting screen The unit operations can be performed by individual group or collective G-50A normally displays this screen.
-11- • Note that operation is different for each of the following display methods. Press the switch to change the display group in desired opera- Press the switch to move the " " select the group number to be operated. Press the switch to set the displayed group unit is indicated by the " " symbol to the on/off mode.
-12- 19 30 ˚ C / 67 87 ˚ F 17 28 ˚ C / 63 83 ˚ F 19 28 ˚ C / 67 83 ˚ F 4 - 2 Operation setting 4 - 2 - 1 Gr oup operation setting • There are two methods for the oper ation, perf or ming the oper ation classified by groups or collectiv e operation.
-13- No. Name of switches Current time setting switch Air direction setting switch V entilation V entilation volume setting display The operation mode of the interlocked setting switch Remote operatio.
-14- (1) Local remote control operation prohibition setting. • G-50A can prohibit the operation of item such as connected local remote controller or slave system controller for each group.
-15- (2) G-50A operation prohibition (3) Using the function area • The operation of this controller is prohibited when an operation prohibition setting f or this controller is received from a system controller other than this controller or when an e xter nal input signal is used.
-16- 4 - 2 - 2 Collective operation setting (1) Collectiv e operation setting • A collectiv e operation setting and a collective prohibit setting can be perf or med f or all the group managed b y this controller at one time. Press the s witch to set "COL.
-17- (2) Collectiv e prohibit setting Press the s witch to set "PROH. (PROHIBIT)" in blinking displa y and press the switch on the collectiv e operation setting initial screen. The collective prohibit setting initial screen is displa yed. Select the items to be prohibited or permitted on the collective prohibit setting initial screen.
-18- The collective oper ation setting initial screen is displa yed. Press the s witch to set "REMO TE CONTROL PR OHIBIT ". Remote operation prohibition/permission display ("REMO TE CONTROL PROHIBIT " ) is displa yed with blinking.
-19- • A weekly schedule setting can be specified for each group. • Possible to set on the timer the schedule to prohibit operation of the local remote controller in addition to ON/OFF • Always set to current time on the current time setting screen when the schedule setting is performed.
-20- • F ollow the procedures described below to set each daily schedule pattern for each group . • The setting temperature or set-back v alues setting are also perf or med in the schedule setting oper ation. T o enter the setting temperature or set-bac k value setting select SET -BACK or SET TEMP .
-21- Press the s witch to display the g roup in desired weekly Press the s witch to mov e the cursor to the pat- ter n position to be set. schedule setting.
-22- Press the (CLOCK/P A TTERN) switch to select P1 to P4 or ( - ). Press the switch one time to complete the setting.(The cursor will move to the next setting position. ) Repeat operations and to assign the schedule pattern to each day. When the No.
-23- 4 - 4 Malfunction • The malfunction monitor function is used for conforming to the details of the malfunction condition when a malfunction is displayed on the operation monitor screen.
-24- 4 - 5 Current time setting < Sifting to the current time setting screen > The current time, day , month and year are set on the current time setting screen. Press the switch to select "5 CURRENT TIME SETTING". Press the switch to back to Press the switch to move the cursor position to be set.
-25- MENU WED 15:29 1 ADDRESS SETTING 2 FUNCTION SELECT 4 GROUP SETTING PLEASE SET INITIAL SETTING 3 IP ADDRESS SETTING MENU WED 15:29 6 ADDRESS SETTING M-NET ADDRESS 7 FUNCTION SETTING BA CK 8 IP ADDRESS SETTING 6 M-NET ADDRESS: 000 5 - 1 Shifting to initial setting menu 5 .
-26- MENU WED 15:29 6 ADDRESS SETTING 7 FUNCTION SETTING BACK 8 IP ADDRESS SETTING OFF ON 3 No. 1 No. 2 No. 3 No. 4 No. 5 No. 6 No. 7 No. 8 <Function selects> FUNCTION SETTING OFF ON : Active 3 .
-27- 1 ADDRESS SETTING 2 FUNCTION SETTING 3 IP ADDRESS SETTING 4 GROUP SETTING PLEASE SET INITIAL SETTING WED 15:29 5 - 4 Gr oup configuration setting • Registration can be made f or the indoor unit.
WED 15:29 MENU NEXT Set all the units and controllers to be registered in the displayed group number . Repeat operation to to set all groups managed by this control- When all setting are completed, press the switch.
-29- 5 - 5 Interloc ked operation setting • Registration of interlock ed operation of V entilation unit (OA processing unit and LOSSNA Y) with single or multiple indoor unit is perf or med. All indoor units to be inter loc ked with v entilation unit for operation should be registered f or the interlocking with ventilation unit.
Used the numeric ke ypad s witch to set the address of the indoor unit that operates with displa yed interloc ked O A processing unit or LOSSNA Y . NO TE: When the indoor unit which address is 012.
-31- 5 - 6 Group name setting • Specify new group name. • Either alphabet, numeric characters, hyphens or spaces can be used for name setting. • Maximum of ten characters can be set. are displayed. The group configuration setting screen is displayed.
Simultaneously press the and keys on the initial setting menu screen for 2 seconds to complete user operation. When the group name setting is completed, press the switch. The group configuration setting screen is displayed. Repeat operation to and perform the group name setting for each group.
-33- • A cer tain group name can be copied to another g roup . • It is conv enient to use a group name for other g roups because a group name that was copied can also be cor- rected. Press the s witch to display the original group on the g roup name setting screen.
5-7 User setting To match the needs for the user this menu is to specify some of the indications and functions that appear on the user operating screen. Press the switch to select "5 USER SETTING" on the initial setting menu screen. The user setting screen is displayed.
-35- 5-8 IP address setting 5-9 Initial setting tool connection function MENU WED 15:29 6 ADDRESS SETTING 7 FUNCTION SETTING BA CK 8 IP ADDRESS SETTING IP ADDRESS SETTING IP ADDRESS : MASK ADDRESS : 192 .168.001.001 255.255.255.000 • This function allows setting of the IP address and mask address needed at LAN connection.
-36- 6. Maintenance 6-1 Refrigerant system monitor • This function allows monitoring of the address of the outdoor units, and BC controller connected to the refrig- erant system. It is useful for checking address settings, transmission line connection during installation.
-37- 6-2 Malfunction log monitor • This function allows monitoring of a log of the last 64 malfunctions. • The contents of malfunction and time the malfunction occurred is display ed. The contents of malfunction is the address of the unit where it occurred, the error code and the address of the unit that detected the malfunction.
-38- 7.External input/output function (1) The function of external input (A) Level signal (2) Level signal and pulse signal (3) Specification of external input interface 7-1 External input function .
-39- 1 1 2 3 (B) Pulse signal Even if the ON signal is input during ON, the status will remain at the ON status. When the local remote controller is prohibited, the ON/OFF operation, operation mode selection and temperature setting from the local remote controller is prohibited.
-40- MENU WED 15:29 1 ADDRESS SETTING 2 FUNCTION SELECT 4 GROUP SETTING PLEASE SET INITIAL SETTING 3 IP ADDRESS SETTING GROUP NAME G01 M MM R 1 AB C DE F G H I JKL NO P Q RS T U V W X Y Z M 2345678 9 .
M-NET ADDRESS: 000 M-NET ADDRESS FUNCTION SETTING ON 12 3 4 56 78 OFF IP ADDRESS SETTING IP ADDRESS : MASK ADDRESS : 192 .168.001.001 255.255.255.000 INTERLOCKED SETTING INTERLOCKED UNIT ADDRESS UNIT ADDRESS 005 USER SETTING GROUP NO . /NAME 1 OPERA TION MONITOR 2 SCHEDULE DA T A 3 FIL TER SIGN 4 GROUP NO .
-42- Over all status lamp Shows the operation panel, screen, etc. for user operation. ON … During operation Collective oper ation switch OFF … All group are stopping BLINKING … Malfunction Appen.
-43- * P1 to P3 of a composite pattern composed of P1 to P3 and P4. • : Change the display group . • : Move the cursor to the pattern position. • : Select P1 to P4 or ( - ) • : Complete the setting. The cursor will move to the ne xt setting position.
WT03945X01 Printed in Japan Recycled P aper NO TE: This equipment has been tested and f ound to comply with the limits for a Class B digital de vice, pursuant to P ar t 15 of the FCC Rules . These limits are designed to pro vide resonable protection against harmful interf erence in a residential installation.
デバイスMitsubishi Electronics G-50Aの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Mitsubishi Electronics G-50Aをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはMitsubishi Electronics G-50Aの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Mitsubishi Electronics G-50Aの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Mitsubishi Electronics G-50Aで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Mitsubishi Electronics G-50Aを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はMitsubishi Electronics G-50Aの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Mitsubishi Electronics G-50Aに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちMitsubishi Electronics G-50Aデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。