Mitsubishi ElectronicsメーカーMUZ-ANAの使用説明書/サービス説明書
ページ先へ移動 of 32
MS-A•W A · MU-A•W A MSZ-A•NA · MUZ-A•NA · MUZ-A•NA - U MSY -A•NA · MUY -A•NA MSZ-FD•NA · MUZ-FD•NA · MUZ-FD•NA - U MSZ-D•NA · MUZ-D•NA · MUZ-D•NA - U MSY -D•NA · MUY -D•NA · MXZ-A•NA SER VICE TECHNICAL GUIDE CONTENTS 1.
2 Revision A: • MXZ-3A30NA- 1 has been added. Revision B: • MXZ-2A20NA- 1 , MXZ-4A36NA, MSZ-FD, MSZ-D and MSY -D have been added..
1. MS MICROPROCESSOR CONTROL ··························································· 4 Indoor unit models Outdoor unit models MS-A09W A MU-A09W A MS-A12W A MU-A12W A 1-1.
4 MS MICROPROCESSOR CONTROL 1 1-1. COOL ( ) OPERA TION MS-A•W A MU-A•W A 2. Indoor fan speed control Indoor fan operates continuously at the set speed by F AN SPEED CONTROL button regardless of the thermostat’s OFF- ON. In AUTO the fan speed is as follows.
5 1. Thermostat control Thermostat is ON or OFF by difference between room temperature and set temperature. 2. Indoor fan speed control Indoor fan operates at the set speed by F AN SPEED CONTROL button. When thermostat OFF (compressor OFF), fan speed becomes V ery Low .
6 1-3. AUTO V ANE OPERA TION 1. Horizontal vane <SWING operation> In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”. According to the temperature of indoor coil thermistor at starting of this operation, next downward blow time is decided.
7 MSZ,MSY MICROPROCESSOR CONTROL 2 2-1. COOL ( ) OPERA TION 2. Indoor fan speed control Indoor fan operates continuously at the set speed by F AN SPEED CONTROL button regardless of the thermostat’s OFF- ON.
8 Set temperature is as shown on the right chart. The system for dry operation uses the same refrigerant circuit as the cooling circuit. The compressor and the indoor fan are controlled by the room tem- perature. By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature decrease.
9 (2) Cold air prevention control MSZ-A09/12/15/17 MSZ-FD MSZ-D When the compressor is not operating, ( ) if the temperature of room temperature thermistor is less than 66 °F , the fan stops.
set position set speed set position set speed Indoor fan Compressor normal Outdoor fan R.V . coil (21S4) OFF (COOL) OFF Maximum frequency horizontal Horizontal vane V ery Low (temperature of indoor co.
11 (2) Mode change In case of the following conditions, the operation mode is changed. COOL mode changes to HEA T mode when 15 minutes have passed with the room temperature 4 °F below the set temperature. HEA T mode changes to COOL mode when 15 minutes have passed with the room temperature 4 °F above the set temperature.
12 <SWING operation> In swing operation of ECONO COOL operation mode, the initial air flow direction is adjusted to “Horizontal”. According to the temperature of indoor coil thermistor RT12 at starting of this operation, next downward blow time is decided.
13 MUZ-A24 MUY -A24 MUZ-D MUY -D POWER SUPPL Y NOISE FIL TER CIRCUIT RESISTOR RELA Y SMOOTHING CAP ACITOR CURRENT TRANSFORMER COMPRESSOR REACTOR P W V U N IPM PFC U W MS 3~ V + Function of main parts NAME FUNCTION INTELLIGENT POWER MODULE (IPM) It supplies three-phase AC power to compressor .
Input current waveform without P AM Input current waveform with P AM Due to the time of no electricity; · Power factor gets worse. · Harmonic gets increased.
15 4. Intelligent power module IPM consists of the following components · IGBT (x6) : Converts DC waveform to three-phase AC waveform and outputs it. · Drive Circuit : Drives transistors. · Protection circuit : Protects transistors from overcurrent.
16 2-7-3. Sine wave control In these air conditioners, compressor equips brushless DC motor which doesn't have Hall element. In short, the motor is sensorless. However , it's necessary to locate the polar direction of rotor in order to drive brushless DC mo- tor ef fi ciently .
17 2-8. OPERA TIONAL FREQUENCY CONTROL OF OUTDOOR UNIT 1. Outline The operational frequency is as following: First, the target operational frequency is set based on the difference between the room temperature and the set tem- perature.
18 2-9. EXP ANSION V AL VE CONTROL (LEV CONTROL) (1) Outline of LEV control The LEV basic control is comprised of setting LEV opening degree to the standard opening °F set for each operational frequency of the compressor .
19 (2) T ime chart OFF T ime Ti m e ON Operational frequency of the compressor Commanded to open Standard opening degree Opening degree is corrected according to discharge temperature.
20 (b) Reference value of LEV standard opening degree (pulse) Applied model A B C D E F MUZ-A09/12 COOL 130 190 240 260 260 260 HEA T 100 130 170 210 230 230 MUZ-A15/17 MUY -A15/17 COOL 290 300 350 35.
21 MXZ MICROPROCESSOR CONTROL 3 3-1. INVERTER SYSTEM CONTROL MXZ-A•NA POWER SUPPL Y NOISE FIL TER CIRCUIT RESISTOR RELA Y SMOOTHING CAP ACITOR CURRENT TRANSFORMER COMPRESSOR REACTOR P W V U N IPM PFC U W MS 3~ V + 3-1-1.
22 3. Power factor improvement Booster coil reactor and PFC rectify AC to DC and control its voltage. In the motor drive system of sine wave control, power factor can be improved by reducing harmonics. PFC and reactor stabi- lize the voltage of DC supplied to inverter circuit and make its waveform smooth.
23 3-2. EXP ANSION V AL VE CONTROL (LEV CONTROL) Linear expansion valve (LEV) is controlled by “Thermostat ON” commands given from each unit. Indoor unit status LEV opening Stop of all indoor unit Opening before stop → 500 pulse in 15 minutes When outdoor unit is operating, some indoor units stop and some operate.
24 In COOL mode, the two indoor coil thermistors (one main and one sub) sense temperature ununiformity (super heat) at the heat exchanger , and when temperature difference have developed, the indoor coil thermistors adjust LEV opening to dimin- ish the super heat.
25 23 54 69 84 100 1 15 131 146 38 14 32 41 50 59 68 77 86 MXZ-2A MXZ-3A/4A 23 Compressor operating frequency (Hz) 4Hz 01 02 03 04 05 06 07 08 09 10 LEV Opening (code) Determination of LEV standard op.
26 MXZ-3A30NA- 1 MXZ-4A36NA Exclusive LEV Standard opening (pulse) LEV Opening (code) 123456789 1 0 COOL 126 130 134 138 150 160 170 180 190 200 HEA T 248 248 258 266 274 280 286 292 300 306 Differenc.
27 (1) LEV opening correction by discharge temperature The target discharge temperature is determined according to frequency zone and number of operation unit of the com- pressor .
28 Correct the LEV opening according to the difference between target discharge temperature and discharge temperature. (2) Separate correction (COOL,DR Y) (Correction by the separate super heat) a) Correct the LEV separately by temperature difference between each gas pipe temperature and the minimum gas pipe temperature of all.
29 3-3. OPERA TIONAL FREQUENCY RANGE b) Correct the LEV separately by temperature difference “ ∆ RT” between main/sub indoor coil thermistor . ∆ RT LEV opening correction (pulse) 10.8 ∆ RT 2 7.2 ∆ RT < 10.8 1 ∆ RT < 7.2 1 In addition, decrease the target discharge temperature corresponding ∆ RT .
30 3-6. OUTDOOR F AN CONTROL Fan speed is switched according to the number of operating indoor unit and the compressor frequency . 3-5. DISCHARGE TEMPERA TURE PROTECTION CONTROL This protection controls the compressor ON/OFF and operation frequency according to temperature of the discharge tempera- ture thermistor .
31 1. Pre-heat control is turned ON for 15 or 30 min, after the breaker is turned ON. 2. 30 min. after the unit is stopped, pre-heat control is turned ON for 15 or 30 min. and turned OFF for 30 min." This is repeated as shown in the graph until the breaker is turned OFF .
New publication, effective Feb. 2008 Specifications subject to change without notice. Copyright 2006 MITSUBISHI ELECTRIC ENGINEERING CO.,L TD Distributed in Feb. 2008. No. OBT16 REVISED EDITION-B 6 Distributed in May 2007. No. OBT16 REVISED EDITION-A 7 Distributed in Apr .
デバイスMitsubishi Electronics MUZ-ANAの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Mitsubishi Electronics MUZ-ANAをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはMitsubishi Electronics MUZ-ANAの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Mitsubishi Electronics MUZ-ANAの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Mitsubishi Electronics MUZ-ANAで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Mitsubishi Electronics MUZ-ANAを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はMitsubishi Electronics MUZ-ANAの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Mitsubishi Electronics MUZ-ANAに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちMitsubishi Electronics MUZ-ANAデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。