Mitsubishi ElectronicsメーカーMUZ-FD12NAの使用説明書/サービス説明書
ページ先へ移動 of 36
SER VICE MANUAL CONTENTS 1. TECHNICAL CHANGES ··································· 3 2. P ART NAMES AND FUNCTIONS ····················· 3 3. SPECIFICA TION ················································ 4 4.
2 Revision A: • 3. SPECIFICA TION has been corrected. Revision B: • 7. DA T A has been corrected..
3 3 1 TECHNICAL CHANGES MUZ-FD09NA MUZ-FD09NA - U1 MUZ-FD12NA MUZ-FD12NA - U1 1. New model P ART NAMES AND FUNCTIONS 2 MUZ-FD09NA MUZ-FD12NA Air outlet Drain outlet Piping Drain hose Air inlet.
4 3 SPECIFICA TION Outdoor unit model MUZ-FD09NA MUZ-FD12NA Capacity Rated (Minimum~Maximum) Cooling 1 Btu/h 9,000 (2,800~9,000) 12,000 (2,800~12,000) Heating 47 1 Btu/h 10,900 (3,000~18,000) 13,600 (.
5 T est condition ARI Mode T est Indoor air condition (°F) Outdoor air condition (°F) Dry bulb Wet bulb Dry bulb Wet bulb SEER (Cooling) "A" Cooling Steady State at rated compressor Speed .
6 6 OUTLINES AND DIMENSIONS 4 Unit: inch MUZ-FD09NA MUZ-FD12NA Liquid pipe :1/4 (flared) Gas pipe :3/8 (flared) 6-23/32 2 5-7/8 2-23/32 1-3/4 15-3/4 12 ~ 12-3/4 13-9/16 11 / 1 6 1-9/16 7/8 21-5/8 1 1-.
7 7 5 WIRING DIAGRAM MUZ-FD09NA MUZ-FD12NA.
8 6 REFRIGERANT SYSTEM DIAGRAM Unit: inch MUZ-FD09NA MUZ-FD12NA Outdoor heat exchanger Flared connection Defrost thermistor RT6 1 Discharge temperature thermistor RT6 2 Service port Service port Flare.
9 D ATA 7 MUZ-FD09NA MUZ-FD12NA 7-1. PERFORMANCE DA T A 1) COOLING CAP ACITY Model Indoor air Outdoor intake air DB temperature ( ˚ F) IWB ( ˚ F) 75 85 95 105 1 15 TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC MUZ-FD09NA 71 1 1.0 6.9 0.58 10.
10 10 7-2. PERFORMANCE CURVE 65 70 75 75 70 65 12 10 6 4 8 Indoor intake air DB tem perat ure (°F) = 381 CFM Airflow 15 52 5 3 5 4 5 5 5 Outdoor intake air WB temperature (°F) 0.4 0.6 0.8 Indoor intak e air DB temperat ure (°F ) T otal power consumption (kW) T otal capacity (1 0 3 Btu/h) 65 70 75 75 70 65 18 16 14 8 6 12 10 0.
11 11 7-3. CONDENSING PRESSURE Cooling Data is based on the condition of indoor humidity 50 %. Air flow should be set to High speed. MUZ-FD12NA (PSIG) Condensing pressure 86 80 75 70 68 70 75 80 85 90.
75 70 65 (PSIG) (PSIG) Condensing pressure Outdoor ambient temperature 15 5 1 0 2 02 53 03 54 04 55 05 56 06 5 7 0 (°F) 220 200 180 160 140 240 260 280 320 300 340 360 380 400 Ind oor DB tem perat ur.
13 13 7-4. ST ANDARD OPERA TION DA T A Model MSZ-FD09NA MSZ-FD12NA Item Unit Cooling Heating Cooling Heating T otal Capacity Btu/h 9,000 10,900 12,000 13,600 SHF — 0.
14 7-5. CAP ACITY AND INPUT CORRECTION BY INVERTER OUTPUT FREQUENCY Capacity correction factors Input correction factors Input correction factors Capacity correction factors Correction of Cooling capa.
15 15 8 ACTUA TOR CONTROL MUZ-FD09NA MUZ-FD12NA 8-2. R.V . COIL CONTROL Heating . . . . . . . . . . . . . . . . . ON Cooling . . . . . . . . . . . . . . . . . OFF Dry . . . . . . . . . . . . . . . . . . . . OFF NOTE : The 4-way valve reverses for 5 seconds right before start-up of the compressor .
16 SER VICE FUNCTIONS 9 9-1. CHANGE IN DEFROST SETTING Changing defrost finish temperature <JS> T o change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P .
17 Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (10-3.) disappears, the memorized failure details can be recalled. 10-2. F AILURE MODE RECALL FUNCTION 1.
18 Does POWER lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: The outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of POWER lamp. 2 Ye s (Blinks ) No (OFF) The outdoor unit might be abnormal. Con fi rm if outdoor unit is abnormal according to the following procedures.
19 3. Outdoor unit failure mode table POWER lamp (Indoor unit) Abnormal point (Failure mode / protection) LED indication (Outdoor P .C. board) Condition Correspondence Indoor/ outdoor unit failure mode recall function Outdoor unit failure mode recall function OFF None (Normal) —— — — — 2-time fl ash 2.
20 10-3. TROUBLESHOOTING CHECK T ABLE No. Symptom LED indication Abnormal point/ Condition Condition Correspondence 1 Outdoor unit does not oper- ate. 1-time fl ash every 2.
21 No. Symptom LED indication Abnormal point/ Condition Condition Correspondence 18 Outdoor unit operates. 7-time fl ash 2.5 seconds OFF Low discharge tem- perature protection T emperature of discharge temperature thermistor has been 122°F (50°C) or less for 20 minutes.
22 10-4. TROUBLE CRITERION OF MAIN P ARTS MUZ-FD09NA MUZ-FD12NA Part name Check method and criterion Figure Defrost thermistor (RT61) Ambient temperature thermistor (RT65) Outdoor heat ex- changer temperature thermistor (RT68) Measure the resistance with a tester .
23 10-5. TROUBLESHOOTING FLOW Are the voltages balanced? Disconnect the connector (CN61) between compressor and the intelligent power module (IPM). Replace the inverter P .C. board. Check the voltage between terminals. Check the compressor . See 10-5.
24 F Check of compressor start failure D Check of compressor winding E Check of compressor operation time ● Disconnect the connector (CN61) between the compressor and intelligent power module, and measure the resistance be- tween the compressor terminals.
25 Is the thermistor normal? (Refer to 10-6.1.) Reconnect the connector of thermistor . T urn ON the power supply and press EMERGENCY OPERA TION switch. No Replace the thermistor except RT64. When R T64 is abnormal, replace the inverter P .C. board. Does the unit operate for 10 minutes or more without showing thermistor abnormality? OK.
26 I Check of outdoor fan motor J Check of power supply Is the outdoor fan motor normal? (Refer to 10-4.) Replace the outdoor fan motor . Disconnect CN932 from the inverter P .C. board, and measure the resistance of the outdoor fan motor . Replace the inverter P .
27 Press OPERA TE/ST OP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1 Expansion valve operates in full-opening direction. OK. NOTE : After check of LEV , do the undermentioned operations.
28 Check the outdoor fan motor . (Refer to 10-5. .) Is the fuse (F901) blown on the in- verter P .C. board? Check the connection of the connectors (CN932) of the outdoor fan motor . If the connection is poor , make it correct. Operate the outdoor unit by starting EMERGENCY OPERA TION.
29 M How to check miswiring and serial signal error T urn OFF the power supply . Is there rated voltage in the power supply? Ye s No T urn ON the power supply . Check the power supply . Is there rated voltage between outdoor terminal block S1 and S2? No Check the wiring.
30 N Electromagnetic noise enters into TV sets or radios Ye s Is the unit grounded? No Ground the unit. Ye s Is the distance between the antennas and the indoor unit within 9.91 ft., or is the distance between the antennas and the outdoor unit within 9.
31 10-6. TEST POINT DIAGRAM AND VOL T AGE -4 14 32 50 68 86 104 0 10 20 30 40 50 60 70 80 90 100 T emperature(°F) Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger .
32 1 1-1. MUZ-FD09NA MUZ-FD12NA NOTE : T urn OFF power supply before disassembling. OPERA TING PROCEDURE PHOTOS 1. Removing the cabinet (1) Remove the screw fixing the service panel. (See Photo 1.) (2) Pull down the service panel and remove it. (See Photo 1.
33 OPERA TING PROCEDURE PHOT OS 2. Removing the inverter assembly , inverter P .C. board (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following connectors: <Inverter P .C. board> CN721 (R.V .
34 OPERA TING PROCEDURE PHOT OS 5. Removing outdoor fan motor (1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the connectors for outdoor fan motor . (3) Remove the propeller nut. (See Photo 7.) (4) Remove the propeller . (See Photo 7.) (5) Remove the screws fixing the fan motor .
35.
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAP AN © Copyright 2008 MITSUBISHI ELECTRIC CO.,L TD Distributed in Nov . 2008. No. OBH498 REVISED EDITION-B 5 Distributed in Mar . 2008. No. OBH498 REVISED EDITION-A 7 Distributed in Jan.
デバイスMitsubishi Electronics MUZ-FD12NAの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Mitsubishi Electronics MUZ-FD12NAをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはMitsubishi Electronics MUZ-FD12NAの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Mitsubishi Electronics MUZ-FD12NAの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Mitsubishi Electronics MUZ-FD12NAで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Mitsubishi Electronics MUZ-FD12NAを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はMitsubishi Electronics MUZ-FD12NAの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Mitsubishi Electronics MUZ-FD12NAに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちMitsubishi Electronics MUZ-FD12NAデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。