TECHNICAL & SER VICE MANU AL <Indoor unit> PDFY-P06NMU-E,PDFY-P08NMU-E PDFY-P12NMU-E,PDFY-P15NMU-E PDFY-P18NMU-E,PDFY-P24NMU-E PDFY-P27NMU-E,PDFY-P30NMU-E PDFY-P36NMU-E,PDFY-P48NMU-E 2005 Models Ceiling Concealed Built-in Ser ies PDFY CONTENTS SAFETY PRECA UTIONS ························· 1.
1 - Inadequate connection and fastening ma y generate heat and cause a fire. • Prepare for typhoons and other str ong winds and ear thquakes and install the unit at the specified place. - Improper installation may cause the unit to topple and result in injury .
2 2 . Precautions for de vices that use Caution: • Do not use the existing refrigerant piping. - The old refr igerant and refrigerator oil in the e xisting piping con- tains a large amount of chlor ine which ma y cause the refrigerator oil of the new unit to deteriorate .
3 PDFY-P06NMU-E PDFY-P08NMU-E PDFY-P12NMU-E PDFY-P15NMU-E PDFY-P18NMU-E PDFY-P24NMU-E PDFY-P27NMU-E PDFY-P30NMU-E PDFY-P36NMU-E PDFY-P48NMU-E 1.8 / 2.0 2.
4 ● ● ● Remote Indoor (Main) Unit controller ● Operation buttons [P AR-21MAA] Once the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF b utton.
5 [Display] C C ON/OFF CENTRALL Y CONTROLLED ERROR CODE CLOCK ON OFF CHECK CHECK MODE FIL TER TEST RUN FUNCTION 1Hr . NOT A V AILABLE ST AND BY DEFROST TEMP .
6 3-1. Specification PDFY-P-NMU-E PDFY-P-NMU-E Notes: *1 Cooling/Heating capacity indicates the maxim um value at operation under the f ollowing condition. Cooling: Indoor: 26.7 ˚ C [80 ˚ F] DB/19.4 ˚ C [67 ˚ F] WB Outdoor: 35 ˚ C [95 ˚ F] DB Heating: Indoor: 21.
7 LEV C1 3.0 µ F X 440V 5.0 µ F X 440V 5.0 µ F X 440V 8.0 µ F X 440V 6.0 µ F X 440V MF1 PDFY- P06,08,12 NMU-E PDFY- P30 NMU-E PDFY- P36 NMU-E PDFY- P48 NMU-E PDFY- P24,27 NMU-E PDFY- P15,18 NMU-E 3-2. Electrical parts specifications Model Pa r t s name T ranrsformer T (Primary) 240V 60Hz (Secondary) (23.
8 123 mm(in.) mm(in.) F 10 E 65 When installing the drain water lifting-up mech(option). (option) 1 3 Suspension bolt hole 2 1 Fresh air intake ø 150(5-29/32)knock out hole 4- ø 3(1/8) Mounting hole Water filling port Control box ø 172 Drain hose Liquid pipe <flare> Gas pipe <flare> 2 1 1 :R410A outdoor unit 2 :R22 outdoor unit 2.
9 PDFY-P36 · 48NMU-E 12(1/2) 1:R410A outdoor unit 2:R22 outdoor unit mm(in.) mm(in.) 30(1-3/16) 52 (2-1/16) 300X4=1200(11-3/16X4=47-1/4) 5- ø 3(1/8)hole 65X20=1300(2-9/16X20=51-3/16) 21X2- ø 3(1/8)hole 35(1-13/32) 1440(56-23/32) 35(1-13/32) 105 65 (2-9/16) 214 33 3 When installing the drain water lifting-up mech(option).
10 WIRING DIA GRAM 5 CN2M ( ) ( ) CN3T NOTE 1 NOTE 1 S(SHIELD) G PARTS LOCATION AC250V 5A F (Green) (Red) (White) (Yellow) (Green) (Yellow) (Green) (Yellow) (White) (White) (White) (Blue) (White) (Blu.
11 PDFY-P36 · 48NMU-E PARTS LOCATION Varistor ZNR1,ZNR901 G 543 2 1 (Green) CN22 (Yellow) CN24 (White) CN25 NOTE1 (Blue) (Red) (White) DP T1 T2 T3 AC250V 5A F ( ) ( ) AC250V 6.3A T S(SHIELD) TB15 (TRANSMISSION TERMINAL BED) TB5 (TRANSMISSION TERMINAL BED) TB2 F2 L2 L1 ZNR901 901 CN2M (Blue) C 1 2 4 2 1 4 2 1 MF CND(Red) 5 3 1 X07 I.
12 Strainer (#100mesh) Strainer (#100mesh) Heat exchanger Room temparature thermistor TH21 Gas pipe thermistor TH23 Liquid pipe thermistor TH22 Linear expansion v alve Gas pipe Flare connection Gas pipe PDFY -P06,08,12,15NMU-E PDFY -P18NMU-E Capacity Item ø 12.
13 Room temparature thermistor (TH21) Liquid pipe thermistor (TH22) Gas pipe thermistor (TH23) T ransformer F an motor Linear e xpansion v alve Disconnect the connector , then measure the resistance using a tester . (Sorrounding temperature 10 ˚ C~30 ˚ C[50 ˚ F~86 ˚ F]) Disconnect the connector and measure the resistance using a tester .
14 0 10 20 30 40 50 -20 -10 0 10 20 30 40 50 < Ther mistor f or lower temperature > T emperature ( ˚ C) -4 14 32 50 68 86 104 122 [ ˚ F] Resistance (k Ω ) 4 ø 4 3 6 5 ø 3 2 ø 2 1 ø 1 ø .
15 Output (Phase) Output ø 1 1 ON ø 2 ON ø 3 OFF ø 4 OFF 2 OFF ON ON OFF 3 OFF OFF ON ON 4 ON OFF OFF ON <Output pulse signal and the valve operation> ➁ Linear e xpansion valve oper ation .
16 1 2 3 4 5 6 7 8 9 10 1~6 1~10 1~4 Thermistor<Intake temperature detection>position ON OFF Filter crogging detection Provided Not provided Filter lif e 2,500hr 100hr Air intake Eff ective Not .
17 0 5 9 4 8 3 7 2 6 1 SW12 10 0 5 9 4 8 3 7 2 6 1 SW1 1 1 0 8 F 7 E 6 D 5 C 4 B 3 A 2 9 1 SW14 3 2 1 0 5 9 4 8 3 7 2 6 1 SW12 0 5 9 4 8 3 7 2 6 1 SW1 1 0 8 F 7 E 6 D 5 C 4 B 3 A 2 9 1 SW14 Address bo.
18 (A) Fig.1 OPERA TING PROCEDURE PHO T OS DISASSEMBL Y PR OCEDURE 8 8-1 CONTROL BO X Be careful removing hea vy par ts. 1.Removing the contr ol box co ver (1)Remov e the fixing screws(two) of the cov er(A) and remov e the cover . (C) (D),(E) Fig.1 Fig.
19 (F),(G) Fig.1 8-3 THERMIST OR (Intake air temperature detection) OPERA TING PROCEDURE PHO T OS 1.Removing the thermistor and thermistor holder (1)Pull out the thermistor holder(F) and ther mistor (G) which are fix ed the control box. (H) 1 2 Fig.1 Fig.
20 (J) Fig.1 Fig.2 (K),(L) OPERA TING PROCEDURE PHO T OS 8-5 THERMIST OR (Gus piping temperature detection) 1.Removing the co ver (1)Remov e the fixing screw of the cov er(J) and remov e the cover . 2.Removing the thermistor (1)Remov e the ther mistor(K), from the ther mistor holder(L), which are installed on the copper tube.
21 (M) (N) (R) fan motor shaft fixing screw Fig.1 Fig.2 Fig.3 1 2 2 3 3 (P) (Q) OPERA TING PROCEDURE PHO T OS 8-6 F AN and F AN MO T OR 1.Removing the filter (1)Press the tabs of the filter and remov e the filter in the direction of the arrow 1 .
22 Fig.1 Fig.2 (S) OPERA TING PROCEDURE PHO T OS 8-7 HEA T EXCHANGER 1.Removing the drainpan with pr ocedure 8-4 2.Removing the co ver(J) with procedure 8-5 3.Removing the Heat e xchanger (1)Remov e the fixing screws of the heat e xchang- er(S) and remov e the heat exchanger .
Issued in Aug. 2005 HWE05160 New publication, effective Aug. 2005 Specifications subject to change without notice.
3400 Lawrenceville Suwanee Road ● Suwanee, Georgia 30024 Toll Free: 800-433-4822 ● Toll Free Fax: 800-889-9904 www.mrslim.com Specifications are subject to ch ange without notice.
デバイスMitsubishi Electronics PDFY-P30NMU-Eの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Mitsubishi Electronics PDFY-P30NMU-Eをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはMitsubishi Electronics PDFY-P30NMU-Eの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Mitsubishi Electronics PDFY-P30NMU-Eの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Mitsubishi Electronics PDFY-P30NMU-Eで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Mitsubishi Electronics PDFY-P30NMU-Eを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はMitsubishi Electronics PDFY-P30NMU-Eの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Mitsubishi Electronics PDFY-P30NMU-Eに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちMitsubishi Electronics PDFY-P30NMU-Eデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。