TECHNICAL MANUAL Manual No.'10•SR-T-091D INVERTER RESIDENTIAL AIR CONDITIONERS (Split system, air to air heat pump type) DRAFT Wall mounted type SRK50Z J -S SRK20ZJX-S SRK 25ZJX-S SRK 35ZJX-S S.
- 1 - '10 • SR-T -091D CONTENTS 1. SPECIFICATIONS ......................................................................................... 2 (1) Wall mounted type (SRK) ......................................................................... 2 (1) Indoor units (1) Indoor units .
- 2 - '10 • SR-T -091D 1. SPECIFICATIONS (1) Wall mounted type (SRK) B R W A000Z225 Model Item SRK50ZJ-S Indoor unit SRK50ZJ-S Outdoor unit SRC50ZJ-S Cooling capacity (1) W 5000 (1600 (Min.) ~ 5500 (Max.)) Heating capacity (1) W 5800 (1600 (Min.
- 3 - '10 • SR-T -091D B R W A000Z229 Model Item SRK20ZJX-S Indoor unit SRK20ZJX-S Outdoor unit SRC20ZJX-S Cooling capacity (1) W 2000 (900 (Min.) ~ 3100 (Max.)) Heating capacity (1) W 2500 (900 (Min.) ~ 4300 (Max.)) Power supply 1 Phase, 220 ~ 240 V, 50Hz Operation data (1) Power consumption Cooling kW 0.
- 4 - '10 • SR-T -091D B R W A000Z229 Model Item SRK25ZJX-S Indoor unit SRK25ZJX-S Outdoor unit SRC25ZJX-S Cooling capacity (1) W 2550 (900 (Min.) ~ 3200 (Max.)) Heating capacity (1) W 3130 (900 (Min.) ~ 4700 (Max.)) Power supply 1 Phase, 220 ~ 240 V, 50Hz Operation data (1) Power consumption Cooling kW 0.
- 5 - '10 • SR-T -091D B R W A000Z229 Model Item SRK35ZJX-S Indoor unit SRK35ZJX-S Outdoor unit SRC35ZJX-S Cooling capacity (1) W 3500 (900 (Min.) ~ 4100 (Max.)) Heating capacity (1) W 4300 (900 (Min.) ~ 5100 (Max.)) Power supply 1 Phase, 220 ~ 240 V, 50Hz Operation data (1) Power consumption Cooling kW 0.
- 6 - '10 • SR-T -091D B R W A000Z229 Model Item SRK50ZJX-S Indoor unit SRK50ZJX-S Outdoor unit SRC50ZIX-S Cooling capacity (1) W 5000 (700 (Min.) ~ 6200 (Max.)) Heating capacity (1) W 6000 (700 (Min.) ~ 8800 (Max.)) Power supply 1 Phase, 220 ~ 240 V, 50Hz Operation data (1) Power consumption Cooling kW 1.
- 7 - '10 • SR-T -091D B R W A000Z229 Model Item SRK60ZJX-S Indoor unit SRK60ZJX-S Outdoor unit SRC60ZIX-S Cooling capacity (1) W 6000 (800 (Min.) ~ 6800 (Max.)) Heating capacity (1) W 6800 (800 (Min.) ~ 9700 (Max.)) Power supply 1 Phase, 220 ~ 240 V, 50Hz Operation data (1) Power consumption Cooling kW 1.
- 8 - '10 • SR-T -091D (2) Floor standing type (SRF) A R WB000Z053 Model Item SRF25ZJX-S Indoor unit SRF25ZJX-S Outdoor unit SRC25ZJX-S Cooling capacity (1) W 2500 (900 (Min.) ~ 3200 (Max.)) Heating capacity (1) W 3400 (900 (Min.) ~ 4700 (Max.)) Power supply 1 Phase, 220 ~ 240 V, 50Hz Operation data (1) Power consumption Cooling kW 0.
- 9 - '10 • SR-T -091D A R WB000Z053 Model Item SRF35ZJX-S Indoor unit SRF35ZJX-S Outdoor unit SRC35ZJX-S Cooling capacity (1) W 3500 (900 (Min.) ~ 4100 (Max.)) Heating capacity (1) W 4500 (900 (Min.) ~ 5100 (Max.)) Power supply 1 Phase, 220 ~ 240 V, 50Hz Operation data (1) Power consumption Cooling kW 0.
- 10 - '10 • SR-T -091D A R WB000Z053 Model Item SRF50ZJX-S Indoor unit SRF50ZJX-S Outdoor unit SRC50ZIX-S Cooling capacity (1) W 5000 (700 (Min.) ~ 5500 (Max.)) Heating capacity (1) W 6000 (700 (Min.) ~ 7000 (Max.)) Power supply 1 Phase, 220 ~ 240 V, 50Hz Operation data (1) Power consumption Cooling kW 1.
- 1 1 - '10 • SR-T -091D A R W A000Z231 Model Item SRR25ZJ-S Indoor unit SRR25ZJ-S Outdoor unit SRC25ZJX-S Cooling capacity (1) W 2500 ( 900 (Min.) ~ 3200 (Max.)) Heating capacity (1) W 3400 ( 900 (Min.) ~ 4700 (Max.)) Power supply 1 Phase, 220 ~ 240 V, 50Hz Operation data (1) Power consumption Cooling kW 0.
- 12 - '10 • SR-T -091D A R W A000Z231 Model Item SRR35ZJ-S Indoor unit SRR35ZJ-S Outdoor unit SRC35ZJX-S Cooling capacity (1) W 3500 ( 900 (Min.) ~ 4100 (Max.)) Heating capacity (1) W 4200 ( 900 (Min.) ~ 5100 (Max.)) Power supply 1 Phase, 220 ~ 240 V, 50Hz Operation data (1) Power consumption Cooling kW 1.
- 13 - '10 • SR-T -091D Model Item FDTC25VD Indoor unit FDTC25VD Outdoor unit SRC25ZJX-S Panel TC-PSA-25W-E Power source 220/230/240V ~ 50Hz Operation data Cooling Heating Nominal capacity kW 2.55 [ 0.9 (Min.) ~ 3.2 (Max.)] 3.45 [ 0.9 (Min.) ~ 4.
- 14 - '10 • SR-T -091D Model Item FDTC35VD Indoor unit FDTC35VD Outdoor unit SRC35ZJX-S Panel TC-PSA-25W-E Power source 220/230/240V ~ 50Hz Operation data Cooling Heating Nominal capacity kW 3.6 [ 0.9 (Min.) ~ 4.1 (Max.)] 4.25 [ 0.9 (Min.) ~ 5.
- 15 - '10 • SR-T -091D 2. EXTERIOR DIMENSIONS (1) Indoor units Model SRK50ZJ-S Space for installation and service when viewing from the front Wired - remote controller 㧔 Option 㧕 Notes 㧔 1 㧕 The model name label is attached ޓޓ ޓ on the underside of the panel.
- 16 - '10 • SR-T -091D Models SRK20ZJX -S, 25ZJX-S, 35ZJX-S , 50ZJX-S, 60ZJX-S G F Hole on wall for right rear piping Hole on wall for left rear piping Gas piping Outlet for wiring Drain hose Liquid piping F E C D B Symbol A 㧔Ǿ 65 㧕 VP16 Ǿ 6.
- 17 - '10 • SR-T -091D (b) Floor standing type (SRF) Models SRF25ZJX-S, 35ZJX-S, 50ZJX-S 600 Unit:mm Hole on wall for right rear piping Hole on wall for left rear piping Gas piping Drain hose Liquid piping F E C D B Symbol A 㧔Ǿ 65 㧕 VP16 Ǿ 6.
- 18 - '10 • SR-T -091D (c) Ceiling concealed type (SRR) Models SRR25ZJ-S, 35ZJ-S A RJD000Z502 8- φ 2.8 Holes for tapping scre ws (φ 4 ) 455 253 325.
- 19 - '10 • SR-T -091D (d) Ceiling cassette-4way compact type (FDTC) Models FDTC25VD, 35VD D G F C B Hole for wiring Suspension bolts Drain piping Liquid piping ( M10 or M8 ) VP20 ( I.D.20,O.D.26 ) Note ( 2 ) φ 6.35 ( 1 / 4" ) ( Flare ) Gas piping A Symbol φ 9.
- 20 - '10 • SR-T -091D (2) Outdoor units Model SRC50ZJ-S RCT000Z005 L2 Intake Outlet Intake L3 L1 Minimum installation space Service space ( ) L4 L2 L3 L4 L1 100 100 250 Open I I I Open 250 80 280 I I I 280 Open 80 75 Examples of Dimensions installation I V 180 Open 80 Open φ 12.
- 21 - '10 • SR-T -091D A RCV000Z007 Models SRC20ZJX-S, 25ZJX-S, 35ZJX-S L2 Intake Outlet Intake L3 L1 Minimum installation space Service space ( ) L4 L2 L3 L4 L1 100 100 250 Open I I I O.
- 22 - '10 • SR-T -091D Models SRC50ZIX-S, 60ZIX-S RCT000Z004 Terminal block L2 Intake Outlet Intake L3 L1 L4 Service space ( ) Minimum installation space Notes ( 1 ) It must not be surrounded by walls on the four sides. ( 2 ) The unit must be fixed with anchor bolts.
- 23 - '10 • SR-T -091D (3) Remote controller (a) Wireless remote controller Models SRK, SRF, SRR 60 17 150 Unit: mm 60 17.3 150 ٨ The wireiess remote controller in the following figure shows for the SRK-50ZJ-S type.
- 24 - '10 • SR-T -091D (b) Wired remote controller (option parts) PJZ000Z274 TEMP ON/OFF 48 غ 120 L C D Wall surface Wiring Electrical box 䋨 Not included 䋩 19 Wiring specifications Exposed mounting 23 46 11.5 11 Remote control outline 120 45 83.
- 25 - '10 • SR-T -091D 250V 3.15A PRINTED CNF CNE CNX CNG 4 CNU 1 3 6 5 ̪ ̪ 35,50 CNY M M M 5 5 U 2 8 2 t o CNS CNM M 5 TO OUTDOOR S/N J L G 1 CIRCUIT BOARD INTERFACE KIT RD BK WH Y BL WIREL.
- 26 - '10 • SR-T -091D Models SRK20ZJX -S, 25ZJX-S, 35ZJX-S , 50ZJX-S, 60ZJX-S 250V F G 3.15A S 㧛 N Va CNU CNS INTERFACE KIT SC-BIKN-E CNG CNE DISPLAY WIRELESS RECEIVER J CNF U M HEAT 1 3 4 .
- 27 - '10 • SR-T -091D (b) Floor standing type (SRF) Models SRF25ZJX-S, 35ZJX-S, 50ZJX-S Color Marks Blue Black BK Red BL RD White WH Yellow 㧛 Green Y 㧛 G Yellow YE Color Mark Heat exch.
- 28 - '10 • SR-T -091D (c) Ceiling concealed type (SRR) Models SRR25ZJ-S, 35ZJ-S Item Meaning of Marks Description Item Description Color Marks Mark Color Mark Color T TO OUTDOOR UNIT RECEIVER BL YE BK RD WH CNG DISPLAY WIRELESS CNY CNE BK BK PRINTED CIRCUIT BOARD F 250V 3.
- 29 - '10 • SR-T -091D (d) Ceiling cassette-4way compact type (FDTC) Models FDTC25VD, 35VD B PJA003Z340 Control PCB Power PCB XR1 XR2 XR3 XR4 XR5 ( Remote operation input:volt-free contact .
- 30 - '10 • SR-T -091D (2) Outdoor units Model SRC50ZJ-S A R WC000Z228 Color RD Mark Orange OR Yellow / Green Y / G Black BK Brown BR Yellow Y White WH Red Description Item Connector CNEEV.
- 31 - '10 • SR-T -091D A R WC000Z227 Models SRC20ZJX-S, 25ZJX-S, 35ZJX-S Color RD Mark Orange OR Yellow / Green Y / G Black BK Yellow Y White WH Red Description Item Connector Electric exp.
- 32 - '10 • SR-T -091D A R WC000Z214 Models SRC50ZIX-S, 60ZIX-S Color RD Mark Orange OR Yellow / Green Y / G Black BK Brown BR Yellow Y White WH Red Description Item Connector CNEEV ~ 20.
DATA BOOK Manual No. '09 • P A C - DB -136 DRAFT INVER TER RESIDE NTIAL AIR CONDI TIONERS Air-Conditioning & Refrigeration Systems Headquarters 16-5, 2-chome, Kounan, Minato-ku, T okyo, 108-8215, Japan Fax : (03) 6716-5926 Copyright MITSUBISHI HEA VY INDUSTRIES, L TD.
デバイスMitsubishi Electronics SRK507J-Sの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Mitsubishi Electronics SRK507J-Sをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはMitsubishi Electronics SRK507J-Sの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Mitsubishi Electronics SRK507J-Sの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Mitsubishi Electronics SRK507J-Sで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Mitsubishi Electronics SRK507J-Sを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はMitsubishi Electronics SRK507J-Sの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Mitsubishi Electronics SRK507J-Sに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちMitsubishi Electronics SRK507J-Sデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。