Installation, Operating, Maintenance and After Sales Manual. Product Serial Number: Please leave this manual with the end user . Part Number: 1370064 Issue 2 heating through innovation.
1.0 General Information 03 2.0 Heating System Design 03 3.0 Unit Selection/Sizing 03 4.0 Location 03 5.0 Preparation 04 6.0 Fixing 04 7.0 W ater Connections 05 8.0 Electrical Connection 06 9.0 Commissioning Procedur e 07 10.0 T echnical Data 08 11.0 Operating Instructions 09 12.
03 SLIM-LINE RC 1.0 General Information 2.0 Heating System Design G This MYSON SLIM-LINE RC fan convector is designed for wall mounted installation with a minimum installation height of 150mm to the underside of the unit. G The SLIM-LINE RC should only be used on closed circulation, two pipe, pump assisted central heating systems.
04 SLIM-LINE RC 5.0 Preparation Before pr oceeding with the installation, unpack the carton contents and check against the checklist below: 1. SLIM-LINE RC unit. 2. 15mm isolating valves (1 pair). 3. Instruction manual. 4. W arranty card. 5. Fixing kit (rubber mounts and cable gland).
05 SLIM-LINE RC 7.0 W ater Connections G Connect unit to system flow and return pipes using the two 15mm isolating valves (see fig. 2). Note: T o ensure ef fective venting of the heat exchanger the flow pipe should be connected to the bottom connection of the heat exchanger .
06 SLIM-LINE RC G This unit is supplied with factory fitted test leads. Remove these and discard. G A fused electrical spur with a maximum 3A fuse and a switch having 3mm separation on all poles must be provided in an easily accessible position adjacent to the unit.
07 SLIM-LINE RC 9.0 Commissioning Procedur e G Fill and vent the system. G Open both valves fully and vent air from the heat exchanger by unscrewing the air bleed valve situated above the valves in the angled top of the chassis. G Check for leaks at pipe connections.
T ested in accordance with BS 4856 Part 1. Flow rate 340 ltr/h (75 gal/h). Flow Rate Correction Factors: 455 ltr/h (100 gal/h) multiply by 1.03 227 ltr/h (50 gal/h) multiply by 0.
09 SLIM-LINE RC 11.0 Operating Instructions Description This SLIM-LINE RC unit is fitted with a control system that provides either automatic or manual contr ol of the unit.
Manual Manual mode can be used for air circulation without heat or for manual control of the heating function. Use ‘+’ to scroll Selected fan speed beyond 35°C displayed Or use ‘-’ to scroll below 15°C Scrolling back out of manual using the ‘+’ or ‘–’ button will r evert the unit back to last temperature set point.
11 SLIM-LINE RC 12.0 T roubleshooting (continued...) Common Installation Faults For optimum performance, this unit must be correctly sized to match the heat loss requir ements of the space it is requir ed to heat, and the heating system must be correctly designed to provide adequate flow of hot water to the unit (r efer to section 2).
heating through innovation. After Sales Service: MYSON Service, Somerden Road, Hull, East Y orkshire HU9 5PE T : 01482 713927, F: 01482 789056, service.convectors@myson.co.uk Spare parts and technical help on all Convector products ar e available from MYSON Service.
デバイスMyson 1370064の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Myson 1370064をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはMyson 1370064の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Myson 1370064の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Myson 1370064で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Myson 1370064を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はMyson 1370064の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Myson 1370064に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちMyson 1370064デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。