O P E R AT I N G I N S T R U C T I O N S Steam Humidifier 2401935 EN 0801 Nor dmann ec onoV ap N O R D M A N N ENGINEERING.
2 Intr oduction You have purchased a NORDMANN steam humidifier which, provided you observe the operating instructions, will ensure fully automatic operation and reliable, low-maintenance service. Therefore, read these operating instructions carefully and pay particular attention to the safety instructions and warnings.
3 General Safety Instructions The econoVap steam humidifier has been designed and constructed in accordance with the latest technology and the accepted safety regulations.
3.1 Dimensions Dimensions of the units Positioning of the humidifier 4 210 5 6 2 354 195 4 0 0 340 6 7 2 490 335 4 9 0 3 Installation Type Dimensions Fixing holes Steam outlet Drainage 4–8 kg/h Fig. 3.1 Fig. 3.2 1 x Ø 22 1 x Ø 22 15–32 kg/h Fig.
5 Dimensions of the steam distribution pipes 3.2 Steam Nozzle For smaller outputs of up to 4 kg/h steam, we offer a nozzle which can be either fitted in air ducts, for instance, or used for direct room humidification. The rules for vaporisation lines (lines needed to mix the steam adequately with air) must be observed here too.
Dimensions of the steam blowers 4-23 kg/h Fixing holes for the Dimensions of the steam blowers 4-23 kg/h steam blowers 4-23 kg/h Dimensions of the Turbo steam blowers 32, 45 und 65 kg/h 6 A B == B A == BA D E CG F BC A D E G F H J B C A D E G F H J A B D C E FG Type A B 4 - 8 kg 1 00 130 1 5-23 kg 1 80 240 Fig.
7 3.3 Fitting the humidifier For the fitting of the humidifier use the material supplied with the unit. Observe the various minimum distances as indicated in figure 3.5. Ensure that there is sufficient room to perform servicing and maintenance work and that the unit is easily accessible.
Steam-distribution pipe fitted on suction side: Because of the under-pressure in the appliance or the duct part, condensate may be kept back in the steam-distribution pipe. If there is an outlet in the empty part of the humidifier, the condensate can be bled off in the immediate vicinity.
9 Technical specifications steam blowers: 3.6 Laying the steam hose The steam hose should be kept as short as possible. It should not be possible to block or obstruct the steam supply lines in any way. Furthermore, they must be protected from outside interference (e.
10 4 W ater connections 3.7 Laying the condensate hose It is advisable to lay the condensate hose as near to the ver- tical as possible and to feed the condensate either directly into an open funnel or below the siphon.
4.2 W ater intake and drainage Please observe the local regulations concerning the connection of appliances to the pressure and drainage system. The humidifier is designed to operate on ordinary tap water only. If you intend to use treated or de-mineralised water, consult your NORDMANN representative beforehand.
6.1 Start-up Prior to starting the unit up, check the correct connections of the steam pipe, water feed pipe, drainage pipes and electrical cables. Open the shut-off valve in the water feed pipe and switch the unit on with the black power switch.
13 6.4 System- and servicing indications LED shining “green” continuously Operation Humidification is demanded. The humidifier operates automatically. Without demand of humidity the LED remains dark. red flash in the shining “green” Niveau max.
14 ! Regular servicing helps to maintain the operation of the humidifier. The following work must be carried out by qualified personnel. 7.1 Regular checks • Inspect the steam cylinder: Are there any deposits in the steam cylinder? ⇒ Remove the drainage strainer and flush the cylinder thoroughly with tap water (without chemical additives).
15 black red white black red white Fig. 7.1 7.4 T aking the humidifier out of operation If the humidifier is out of operation for a longer period of time ( e.g. in summer or when the air conditioning system is not operating), the steam cylinder must be emptied and the power supply disconnected.
9. T echnical specifications Other heating voltages on request. T ype mark: Type 434 834 1 534 2364 3264 4564 6564 Heating voltage V olt 400 V olt, 50/60 Hz Number of phases ~ 3 3 3 3 3 3 3 Heating current A 4.4 8.8 16.5 25.2 35.1 49.4 7 1.3 External fuses p.
デバイスNordmende 2401935EN0801の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Nordmende 2401935EN0801をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはNordmende 2401935EN0801の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Nordmende 2401935EN0801の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Nordmende 2401935EN0801で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Nordmende 2401935EN0801を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はNordmende 2401935EN0801の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Nordmende 2401935EN0801に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちNordmende 2401935EN0801デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。