NordyneメーカーM3RLの使用説明書/サービス説明書
ページ先へ移動 of 36
Installation Instructions M3RL Series 90+ Downflo w Condensing Furnace Direct Vent (Sealed Combustion) Forced Air Gas Furnaces LEAVE THESE INSTRUCTIONS WITH THE HOMEOWNER. ! W ARNING: FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury, death or property damage.
2.
3 Application M-Manufactured Home Furnace Series Comfort Model RL - Condensing Downflow M 3 R L - 060 A - A W Door Color W - White G - Gray Cabinet Dimensions A - 56" x 19-3/4" x 23-3/4” B - w/Coil Cavity, 76" x 19-3/4" x 23-3/4" Electrical Code A - 1PH, 60 Hz, 120 VAC Conversion .
4 19-7/8 19-7/8 24-5/8 24-5/8 56-1/16 56-1/16 20-9/32 20-9/32 21-17/32 21-17/32 21-29/32 21-29/32 21-15/16 21-15/16 19-3/16 19-3/16 23-7/16 23-7/16 28-15/32 28-15/32 3-17/32 3-17/32 4-11/16 4-11/16 4-.
5 ! W ARNING: Do not use this appliance if any part has been submerged under water. Im- mediately call a qualified service tech- nician to inspect the appliance and to replace any part of the control system and any gas control that has been submerged underwater.
6 Follow the instructions in this booklet carefully and this appliance will provide many years of superior performance. If you wish to cool your home automatically with a central air conditioning system investi- gate the excellent NORDYNE cooling systems available from your heating and cooling con- tractor.
7 CE générateur d'air chaud doit être installé conformément aux instructions du fabricant et aux codes locaux. En l'absence de code local, respecter la norme ANSI Z223.,1, institulé Na- tional Fuel Gas Code ou les codes d'installation CAN/GCA-B149.
8 Figure 4. Figure 3. 13 1/4" 10 1/4" 19” 19" T op Vie w of Duct Connector x SUPPLY AIR DUCT FLOOR CAVITY (depth equal to "X" in Figure 5 and Table 5) RETURN AIR PROVISIONS U.
9 Figure 6. Closet or Alcove 10" 23 -1/4" FLOOR OPENING C L C L ALT. FUEL LINE HOLES SIDE WALL RE AR WALL FUEL LINE HOLE Figure 5. X SEE TABLE 5 REDUCER FELT-SEAL( 1 ) SPACERS C ( )OPENING TO DUCT (1) WITH PLATE (C) REMOVED OPENING BECOMES 13-1/4” x 13-1/4” (2) WITH PLATE (C) REMOVED OPENING BECOMES 13" X 13".
10 Figure 7. Cut-Out Locations 2-3/4 2 1-3/4 17-29/32 21-7/16 1-3/4 3-19/32 14-1/2 14-1/2 2-1/4 23-1/4 12-7/8 14-3/4 20 24 21-3/4 10 15-1/2 ˚ AL T FUEL LINE ENTR Y 1-1/4 VENT FUEL LINE ENTR Y FURNACE.
11 Figure 9. Duct Connector Screw Do wn Duct Connectors Platinum Series Figure 8. Mounting Plate REAR W ALL SUPPLY AIR DUCT FUEL LINE HOLES MOUNTING PLATE FLOOR OPENING BEND CONNECTOR TABS UNDER DUCT .
12 TABS TABS DUCT DUCT 1. INSERT DUCT PLENUM CONNECTOR INTO DUCT CUT-OUT. 2. BEND BOTTOM TABS OVER AND ONTO THE UNDERNEATH DUCT SERVICE. Staple Folded Duct Flap (typ) to side of Duct Connector Duct STEP 4.
13 MTG. PLATE TABS SLIDE FURNACE ALL THE WAY BACK ONTO MTG. PLATE S UPPLY AIR D UC T Knockout Over Holes SECURE FURNACE WITH 2 FASTENERS AT FRONT CORNER HOLES SUPPLY AIR DUCT FUEL LINE HOLES MTG. PLATE TABS SLIDE FURNACE ALL THE WAY BACK ONTO MTG. PLATE SECURE FURNACE WITH 2 FASTENERS AT FRONT CORNER HOLES Figure 13.
14 ! CA UTION: Do not allow debris to fall into the fur- nace. This could cause unsafe opera- tion and voids the furnace warranty. VENTING REQUIREMENTS ! W ARNING: FURNACE MUST NOT BE COMMON VENTED WITH OTHER APPLIANCES. General This section specifies installation requirements for 2-pipe combustion air piping.
15 *NOTES 1 . Subtract 3.5 ft. for each additional 3" 90 degree elbow. 2 . Two 45 degree elbows are equivalent to one 90 degree elbow. 3 . One short radius elbow is equivalent to two long radius elbows. 4 . Do not include termination elbows in calculation of vent length.
16 escape through such appliances or vents. Do not vent the furnace to a fireplace chimney or building chase. If removing an existing furnace in a venting system, the venting system may not be properly sized. To test the vent system with the remaining appliances, follow the test outlined below.
17 Figure 16. Horizontal V enting Downflow Furnace Seal/Caulk Around Pipe at Building 90˚ Elbow 12" Min. Normal Snow Level W all Coupling First Support Should be as Close to Furnace Connection a.
18 Horizontal Venting Vent and combustion air intake terminations must be as shown in Figure 19 unless the concentric vent termination kit is used. ! W ARNING: Ensure that the combustion air vent and the exhaust vent are configured as shown in Fig. 19.
19 36" max. 12" min. Exhaust V ent Option B Exhaust V ent Option A Exhaust V ent Option C Mounting Kit Faceplate Secured to Wall with Screws 12" Min. 36" Max. 12" Min. 36" Max. 7" Min. 8" Min. 12" Min. to Normal Snow Level Combustion Air Inlet Grade Level or Normal Snow Inlet Exhaust Figure 20.
20 Figure 21. Furnace with Condensate Drain Trap Assembly A A Clamp Step 1: Loosen Step 2: Rotate to drain direction Step 3: Retighten Keep Downward Slope Alt. Drain Alt. Drain Alt. Drain Alt. Drain Floor Ca vity Floor “Hard ” J Drain T ube Burner Box Collector Box 1.
21 Figure 22. Typical Gas Piping Table 7. Capacity of Black Iron Gas Pipe (cu. ft. per hour) for Natural Gas (specific gravity = .60) To Gas Supply Floor Inducer Alt. Gas Line Entry Floor Cavity Gas Valve Burner Box Control Board Main Blower N OM IN AL LE N G TH OF PIPE R U N B LA C K IR ON ( f ee t ) PIPE DIAM ETER ( i n .
22 Table 8. Approximate Orifice Size for Natural and LP Gases Nat LP Nat LP Nat LP Nat LP Nat LP 060A-A/ B W 60, 000 4 5 0 57 50 57 51 58 51 58 52 59 080A-A/ B W 80,000 5 49 1. 15 mm 49 1.15 mm 50 57 50 57 51 58 Fur na c e Mod el Numbe r M3R L - Fur na c e R a t ing P l ate I n p u t (B tuh) No .
23 Figure 25. T ypical Installation For Sealed Burner Bo x With Access Cover Plate Burner Orifices Gas Manifold Flame Observation Port Gas Valve Access Cover Plate Burner Box Inlet Pressure Ta p Inlet On/Off Lever Figure 24. Burner Inspection Figure 23.
24 7. After the flame ignites, visually inspect the burner assembly to ensure that the flame is drawn directly into the center of the heat exchanger tube, as shown in Figure 23. The end of the flame will be out of sight around the bend of the heat exchanger tube.
25 Field Supplied Disconnect Within Sight of Furnace Field Supplied Panel Connector Field Supplied Fused Service Panel Black (Hot) White (Neutral) Green or Bare (Ground) Black White Black White Black White Field Line Voltage Wiring Factory Line Voltage Wiring Ground Ground Ground Junction Box (may be internal or external to the furnace).
26 Figure 28. Low Voltage Field, Four-wire Heating/Cooling Applications R C Y G W A/C Condensing Unit Condensing Unit Control Box Room Thermostat Flame Signal Light (Yellow) Status Light (Red) 60 90 1.
27 5 . After the furnace has run for approximately five minutes, set the thermostat below room temperature and verify steps 9 - 11 of the SEQUENCE OF OPERATION. Shut Down Procedure In the event that the furnace must be shut down, follow this procedure: 1.
28 TIME FOR TIM E FOR ON E R EV OLU TION ON E R E VOLU TION (S ECONDS ) 1 5 10 (S ECONDS ) 1 5 10 24 150 750 1500 80 45 225 450 26 138 692 1385 82 44 220 439 28 129 643 1286 84 43 214 429 30 120 600 1.
29 Gas Valve – The gas valve controls the flow of gas to the burners. When the gas valve is energized it automatically opens and regulates the gas pressure in the manifold. Pressure Switch – The pressure switch veri- fies that the inducer is drawing the combustion gases through the heat exchanger.
30 ! W ARNING: Never operate the furnace without a filter in place. Dust and lint in the return air can build up on internal compo- nents, resulting in loss of efficiency, equipment damage, and possible fire. Lubrication The bearings in the circulating air blower mo- tors are pre-lubricated and sealed at the fac- tory.
31 Initial Power up: After 30 seconds of igniter warm-up the gas valve (24 VAC) will then open. The igniter circuit will stay ener- gized for 3 seconds after the gas valve opens.
32 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 21 22 M3 Do wnflow Furnace 1 Door Assembly - Louvered 2 Filter Inside Door 3 Blower Assembly 4 Control Board 5 Pressure Switch 6 Flame Rollout Switch 7 “J” Trap Hard Tube 8 Low Voltage Transformer 9 In Line Drain Assembly 10 Junction Box 1 1 Vent Safety Switch Figure 29.
33 Figure 30. Downflow Furnace Wiring Diagram WD #710240B If an y o ft h e ori g ina l wit h th e f u rn ace m us t be re p laced, i t m us t be re p laced wirin g m a t e ri a l h avin g a ratin g of a tl eas t ˚ C. U se co pp e r co n duc t o r s o nl y.
34.
35 UNIT MODEL NUMBER ________________ Minimum Clearances per Table 3? ________ Electrical Connections tight? _____________ Line Voltage Polarity correct? ____________ Supply Voltage: _________________.
O’Fallon, MO 708219E (Replaces 708219D) Specifications and illustrations subject to change without notice and without incurring obligations. Printed in U.
デバイスNordyne M3RLの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Nordyne M3RLをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはNordyne M3RLの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Nordyne M3RLの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Nordyne M3RLで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Nordyne M3RLを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はNordyne M3RLの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Nordyne M3RLに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちNordyne M3RLデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。