STEAM DISTRIBUTORS ASD / BSD / CSD Steam Distribution Installation Manual IMPORTANT: Read and save this guide for future reference. This guide to be left with equipment owner.
Table Of Contents INSTALLATION .....................................1 RECEIVING & UNPACKING EQUIPMENT .....................1 PRE-INSTALLATION .................................1 STEAM LINE INSTALLATION ............................1 GUIDELINES .....
INSTALLATION RECEIVING & UNPACKING EQUIPMENT 1. Check packing slip to ensure ALL material has been delivered. 2. All material shortages are to be reported to Walter Meier (NORTEC) within 48 hours from receipt of goods. Walter Meier (NORTEC) assumes no responsibility for any material shortages beyond this period.
Chart #3 Recommended Condensate line at distributor(s) CONDENSATE RETURN GUIDELINES FOR MAIN STEAM LINES 1. Use vertical condensate leg of distributor only. Do not over-tighten clamp. 2. Drip stations on steam mains must be located at all low points in the system, at each elevation change and or directional change.
-3- NHB, NHP , NHMC, RESDELUX ONL Y T o be 2” (50mm) longer then duct static pressu re or minimum. T o be 2” (50mm) longer then duct static pressu re or minimum. 6 ” m i n ( 1 5 0 m m ) 12” (300 mm) 1 2 ” ( 3 0 0 m m ) min. 2º min. 10º Nortec Humidifiers All Models min.
-4- -4 5 º GO T O 1 2 3 C2 +4 5 º 1x B Always align distributor holes so that steam is discharged upwards to ensure condensate will remain in the distributor .
-5- C1 D GO T O ¿ 3.6 mm 81- ... 81-... 61-... 41-... 4 3 m m 6 1 m m 61-... / 41-... ¿ 3 . 6 m m 8 1 - . . . 6 1 - . . . / 4 1 - . . . H X XM i n . HM i n .
-6- C2 D GO T O Always align distributor hole s so that steam is discharged upwards to ensure condensate will remain in the distributor . H 1/ 3W 2/ 3W W 1/ 3W 1/ 3W 1/ 3W 1/ 3W Min.
-7- #10 S c r e w U s e s e l f t appi n g s c r e w s . GO T O E D Figure #6 Distributor Mounting - Horizontal & Vertical Flow E 5/16” 5/16” unc Support Bracke t by Others Mandatory for Distributors longer than 36” (915mm).
-8- ASD & BSD 1506162- Distributor End Cap Assembly CSD 1506164 - Distributor End Cap Assembly Distributor Core Exploded Views December 18, 2002 ASD & BSD 1506161- Distributor Inlet Assembly C.
LIMITED WARRANTY Walter Meier Inc. and/or Walter Meier Ltd. (hereinafter collectively referred to as THE COMPANY), warrant for a period of one year from date of shipment, that THE COMPANY’s manufactured and assembled products, not otherwise expressly warranted, are free from defects in material and workmanship.
Walter Meier (Climate USA) Inc. 826 Proctor Avenue, Ogdensburg, New York 13669 Walter Meier (Climate Canada) Ltd. 2740 Fenton Road, Ottawa, Ontario K1T3T7 Tel: 866 NORTEC 1 Fax: 613 822 7964 nortec@humidity.
デバイスNortec BSDの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Nortec BSDをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはNortec BSDの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Nortec BSDの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Nortec BSDで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Nortec BSDを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はNortec BSDの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Nortec BSDに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちNortec BSDデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。