PV500 - 17 05 - 2000 Section 17 1 INSTALLATION & MAINTENANCE MANUAL FOR MAXIM INTEGRATED WATER HEATING SYSTEM TABLE OF CONTENTS Start - up Procedures 2 Maintenance & Safety Inspections 3 - 5 Wiring Diagrams 6,7 Burner 8 Burner Start - up 9 - 12 Burner Troubleshooting 13.
PV500 - 17 05 - 2000 Section 17 2 START - UP PROCEDURES CAUTION: DO NOT RELIGHT PILOT OR START BURNER WITH COMBUSTION CHAMBER FULL OF GAS OR OI L VAPOR, OR WITH VERY HOT COMBUSTION CHAMBER. 1. Study the burner start - up information included in this manual carefully.
PV500 - 17 05 - 2000 Section 17 3 MAXIM MAINTENANCE AND SAFETY INSPECTIONS 1. Establ ish a preventive maintenance program to assure a longer water heater life. 2. The tank should be flushed at two - or three - month intervals depending on water conditions in your location.
PV500 - 17 05 - 2000 Section 17 4 MAXIM MAINTENANCE AND SAFETY INSPECTIONS (continued) Periodic Inspection of Operation Components (continued) CAUTION: THE RELIEF VA LVE IS A PRIMARY SAFETY DEVICE.
PV500 - 17 05 - 2000 Section 17 5 MAINTENANCE & SAFETY INSPECTION REPORT DATE BURNER INSPECTION COMBUSTION ANALYSIS TANK INSPECTION TANK FLUSH & CLEANOUT TANK FITTING INSPECTION VENT INSPECTIO.
PV500 - 17 05 - 2000 Section 17 6 MAXIM AXIAL FLOW GAS BURNER CARBON MONOXIDE WARNING: CAUTION: IMPROPER COMBUSTION MAY CAUSE SERIOUS INJURY. PVI recommends a s easonal or annual combustion check - out be performed by a qualified service agency to ensure safe and efficient operation.
PV500 - 17 05 - 2000 Section 17 7 MAXIM AXIAL FLOW GAS BURNER START - UP (Refer to Figure 17 - 2, page 6 to identify burner parts) 1. Remove the enclosure panel cover on the water heater or boiler to expose the control circuit. A wiring diagram, included in this packet, will show the controls used in our circuitry.
PV500 - 17 05 - 2000 Section 17 8 MAXIM AXIAL FLOW GAS BURNER START - UP (continued) PRESSURE PLATE Set up and Tolerances Figure 17 - 3 13. Connect a test meter to the control for reading the flame response signal. NOTE: Some controls read the flame signal in micro amps and some in volts DC.
PV500 - 17 05 - 2000 Section 17 9 MAXIM AXIAL FLOW GAS BURNER START - UP (continued) This section pertains to MC120 control only. When the blower motor starts, the air proving light on the MC - 120 should be on. This indicates a positive air flow condition.
PV500 - 17 05 - 2000 Section 17 10 MAXIM AXIAL FLOW GAS BURNER START - UP (continued) 17. Check flue gases with a flue analyzer to make final settings of the air shutter. a. The readings need to be taken from a hole in the vent several inches above the heater vent connection, but before draft regulator.
PV500 - 17 05 - 2000 Section 17 11 MAXIM TROUBLESHOOTING SUGGESTIONS AXIAL FLOW GAS BURNER 1. BURNER FAILS TO START Defective On/Off switch. Replace switch. A. Control circuit has an open control contact. Check limits, low water cutoff, proof of closure switch and others as applicable.
PV500 - 17 05 - 2000 Section 17 12 MAXIM TROUBLESHOOTING SUGGESTIONS AXIAL FLOW GAS BURNER (continued) C. Defective automatic main or auxiliary gas shut off valves. Check electrical circuitry to valves. Replace valves or correct circuitry a s required.
デバイスPVI Industries MAXIM INTEGRATED WATER HEATING SYSTEMの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEMをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはPVI Industries MAXIM INTEGRATED WATER HEATING SYSTEMの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEMの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEMで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEMを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はPVI Industries MAXIM INTEGRATED WATER HEATING SYSTEMの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、PVI Industries MAXIM INTEGRATED WATER HEATING SYSTEMに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちPVI Industries MAXIM INTEGRATED WATER HEATING SYSTEMデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。