INST ALLA TION & OPERA TING INSTR UCTIONS CA T ALOG NO. 2100.50AA Effective: 12-26-07 Replaces: 01-31-07 P/N 240488 Rev . 28 WARNING: If these instructions are not followed exactly , a fire or explosion may result causing property damage, personal injury or death .
2.
WARNINGS 4 Pay Attention to These T erms 4 RECEIVING EQUIPMENT 5 GENERAL SPECIFICA TIONS 5 INST ALLA TION 7 Code Requirements 7 Mounting Base 7 Clearance Requirements 7 Combustion/V entilation Air 8 V.
D ANGER: Indicates the presence of immediate hazards which will cause severe personal injury , death or substantial property damage if ignored. WARNING: Indicates the presence of hazards or unsafe practices which could cause severe personal injury , death or substantial property damage if ignored.
RECEIVING EQUIPMENT On receipt of your equipment, visually check for exter- nal damage to the carton. If the carton is damaged, it is suggested that a note be made on the Bill of Lading when signing for the equipment. Remove the boiler from the carton, and if it is dam- aged, report the damage to the carrier immediately .
6 16 33 1 / 4 22 1 / 8 12 1 / 2 5 18 3 1 / 4 2 THERMOST A T CONN (ELECTRICAL CONN ON OTHER SIDE) GAS CONN 3/4 NPT PIPE TO DRAIN 26 1 / 4 1 / 2 C 11 7 / 8 6 INLET OUTLET 3 1 / 8 MIN 19 K A UTOMA TIC VENT DAMPER (FIELD INST ALLED) B A Fig. 1: Dimensions Model No.
7 INST ALLA TION Code R equir ements Installation must be in accordance with local codes, or in the absence of local codes, with the latest editions of the National Fuel Gas Code, ANSI Z223.
8 3. Except for carpeted flooring, boilers are certified for installation on combustible floors. 4. For un-insulated hot water pipes, maintain a 2" clearance, or consult local authority having juris- diction.
9 Location of the openings is the same as in the previ- ous case - that is, within 12" of the top, and within 12" of the bottom of the enclosure.
10 Roof Pitch (X/12) H (Min. ft) Flat to 6/12 1 6/12 to 7/12 1.25 Over 7/12 to 8/12 1.5 Over 8/12 to 9/12 2 Over 9/12 to 10/12 2.5 Over 10/12 to 1 1/12 3.25 Over 1 1/12 to 12/12 4 Over 12/12 to 14/12 5 Over 14/12 to 16/12 6 Over 16/12 to 18/12 7 Over 18/12 to 20/12 7.
11 At the time of removal of an existing boiler , the follow- ing steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remain- ing connected to the common venting system are not in operation.
12 Mounting On vertical vents, the vent damper may be mounted with the actuator in any position. On horizontal vents, do not mount the actuator either directly above or directly below the vent pipe; mount the vent damper actuator to the side of the vent.
13 2. Turn the thermostat or controller up to call for heat and check that the vent damper indicator points to the open position, as shown in Fig. 1 1. 3. T urn the thermostat or controller down again and check that the vent damper position indicator returns to the closed position.
14 VENT DAMPER.
15 Gas Supply Connections The inlet gas connection of the boiler gas valve is 1/2". Provide an adequate gas piping supply line no smaller than 1/2", according to T able H above. Gas piping must have a sediment trap ahead of the boiler gas controls, and a manual shut-off valve locat- ed outside the jacket.
16 shipped loose. The full open position is appropriate for most systems, and ensures adequate flow through the boiler . If system flow is inadequate, (indicated by excessive temperature drop through the system) the bypass valve can be throttled slightly .
17 Air Scoop Air V ent Diaphragm Expansion T ank Feed Va l v e Pipe Pressure Relief V alve to Drain Cold W ater Inlet Heating Units Fig. 15: Single-Zone Piping Air Scoop Air V ent Diaphragm Expansion T ank Feed Va l v e Pipe Pressure Relief V alve to Drain Cold W ater Inlet Heating Units Circulators 12” Max.
18 Electrical W iring The electrical power supply requirement for these boil- ers is 120 V AC, 60 Hz. Field wiring connections and electrical grounding must comply with the local codes, or in the absence of local codes, with the latest edition of the National Electrical Code, ANSI/NFP A 70.
19 W iring Diag r ams.
20.
21.
22 Fig. 17: Single-Zone T aco V alve Fig. 18: Dual-Zone T aco V alve Fig. 19: Dual-Zone Honeywell V alve NOTE: Maximum three (3) zone valves per one (1) 40 V A transformer .
23 Fig. 20: System with Three (3) Zone Pumps NOTE: Check V A rating of each relay coil. T otal load must not exceed V A rating of transformer . Fig. 21: Power V ent System with Zone V alve.
24 Fig. 22: Primary/Secondary Pumping System Honeywell Zone V alve Fig. 23: Standing Pilot with Low W ater Cut-off Device Note: Low water cut-off (L WCO) and system switch supplied by others.
25 Fig. 24: IID Units with Low W ater Cut-off Device Note: Low water cut-off (L WCO) and system switch supplied by others..
26 SER VICING PR OCEDURES General Location of Controls Fast- Response Temperature Sensor 2-Stage Controller Relay Ignition Module (Auto Ignition Only) Fig.
27 ST AR T -UP PR OCEDURES Lighting the Boiler Safe-lighting and other performance criteria were met with the gas manifold and control assembly provided on the boiler when the boiler underwent tests specified in the latest edition of the ANSI-Z21.13/CSA 4.
28 F or Standing Pilot Models with R ober tshaw Gas V alv e, 2-stage Oper ation (Models 90, 135 & 180) 10. T urn on all electrical power to the boiler .
29 technician. Force or attempted repair may result in a fire or explosion. D. Do not use this boiler if any part has been under water . Immediately call a qualified service techni- cian to inspect the boiler and to replace any part of the control system and any gas control which has been under water .
30 3. T urn off all gas valves supplying gas to the boiler . Refer to operating instruction label on the boiler . 4. Shut-off the water supply to the boiler piping sys- tem loop. 5. Open drain valve on the boiler to remove water from the boiler and the piping circuits.
31 Inspection Procedur es Bur ner s Clean main burners and air louvers of dust, lint and debris. Keep boiler area clear and free from com- bustibles and flammable liquids. Do not obstruct the flow of combustion and ventilation air . Make visual check of burner and pilot flame.
32 Bur ner T r ay R emo val 1. Shut-of f power and gas supply to the boiler . Disconnect union(s) and pilot tubing when pres- ent; then loosen and remove burner hold-down screws. 2. Disconnect wires at gas valve and slide burner tray out. Main Bur ner and Orifice Remo val 1.
9. Install flue collector , jacket top and inspection pan- els. Install top holding screws. Install draft diverter and vent piping if so equipped. 10. If gas piping was disconnected, reconnect gas pip- ing system and check for leakage using a soap solution.
34 TR OUBLESHOO TING These instructions are primarily intended for the use of qualified personnel specifically trained and experienced in the installation of this type of heating equipment and related system components. Installation and service per- sonnel may be required by some states to be licensed.
35 10) Before module goes into a lock-out, check voltage across MV and MV/ PV. If no 24V is present, replace module. If 24V is present, replace gas valve. 1) Adjust inlet gas pressure as shown on rating plate. 2) Clean pilot orifice. 3) Replace thermocouple.
36 Adjustment & R eplacement of Components Gas V alve R eplacement 1. Shut-off electrical power and gas supply to the boiler . 2. Remove gas piping to gas valve inlet. 3. Disconnect wiring connections, pilot tubing (when present). 4. Remove screws (2) holding the burner tray .
37 7. Remove the wedge or retaining clip holding the sensing bulb in the control well in the in/out head- er . 8. Pull out the sensing bulb carefully from the control well. 9. Remove the limit control with capillary from unit. 10. Reverse above procedure to re-install.
38 LIMITED P ARTS W ARRANTY RESIDENTIAL HEA TING BOILERS MODELS 42 TO 180 SCOPE: Raypak, Inc. (“Raypak”) warrants to the original owner that all parts of this boiler which are actually manufacture.
39.
ww w .raypa k . com Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (805) 278-5468 Litho in U.S.A..
デバイスRaypak 0180B Type Hの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Raypak 0180B Type Hをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはRaypak 0180B Type Hの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Raypak 0180B Type Hの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Raypak 0180B Type Hで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Raypak 0180B Type Hを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はRaypak 0180B Type Hの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Raypak 0180B Type Hに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちRaypak 0180B Type Hデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。