Raypakメーカー241275の使用説明書/サービス説明書
ページ先へ移動 of 22
This manual should be maintained in legible condition and kept adjacent to the heater or in another safe place for future reference. Catalog No: 1000.57A Effective: 02-28-07 Replaces: 02-24-06 P/N 241275 Rev .
2.
GENERAL SAFETY T o meet commercial hot water use needs, the high limit safety control on this water heater is adjustable up to 210°F . However , water temperatures over 125°F can cause instant severe burns or death from scalds. When supplying general purpose hot water , the rec- ommended initial setting for the temperature control is 125°F .
4 COLD WA TER ST AR T Before arriving at the job site to begin the installation, it's important to first inspect the system and determine what materials you will need. Some parts are includ- ed with the controller while others you will need to provide.
5 Connecting P ow er to the Controller Supply power from the 120 V AC power input from the heater to the controller power inputs T erminal Block (TB1). This is accomplished by connecting wiring from the control box to the heater TB1 board 120 V AC power input connections.
6 Cold Star t Sequence of Operation 1) 120V AC to heater sends 120V AC to Cold Start control on terminal block 1. 2) 120/24V AC transformer and 120V AC-12VDC con- verter are powered.
7 NO TE: Elodrive actuator is Nema 4 rated. TR OUBLESHOO TING Check your power source using a V olt-Ohm meter; check the following voltages at TB1 terminal block: TB1-1 to TB1-2 = 108 V AC Minimum, 132 V AC Maximum TB1-1 to TB1-3 = 108 V AC Minimum, 132 V AC Maximum TB1-2 to TB1-3 = Must be less than .
8 Cold Wa ter Star t T r oubleshooting Guide.
9 W iring Dia gr am.
10 COLD WA TER R UN Pur pose The Cold W ater Run system utilizes a variable-speed pump to inject the proper amount of water from the main system loop into the boiler to maintain the opti- mum inlet temperature.
11 Injection & Heater Pump Comparison — Hi Delta Heater Pump Injection Pump Heater Model Flow T emp. Rise Press. Drop Flow T emp. Rise Injection Pump Heater Pump 302 32 16 2 13 40 191 1- 1 ⁄ 4 hp 11 2 402 34 20 2 17 40 191 1- 1 ⁄ 4 hp 11 2 502 42 20 2.
12 Fig. 13: Remove the pump body Fig. 14: Be sure not to damage the seal when removing or replacing the pump body Injection Pump Co v er Installation Before Star ting 1) T urn off power to the unit at the circuit breaker . 2) T urn off gas supply . 3) Shut off the water supply to the heater and, if nec- essary , drain water from the system.
13 3. Insert and tighten all eight (8) wrench bolts, secur- ing the pump body in place. 4. Y ou will now be able to install the pump cover . See Fig. 18 and 19.
14 Typical Boiler Piping (Hi Delta sho wn).
15 ST AR T -UP PROCEDURE • Run full system flow for two minutes. • Initiate PID pump control to achieve target inlet temperature by slowing injector pump. • Boiler ΔT will not increase during bypass operation. • If target temperature is not achieved after seven minutes from “call for heat”, the system will shut down.
16 W iring Dia gr am.
17 Cold Wa ter Run T roubleshooting Guide Ste p 9 Ste p 8 Ste p 10 Step 1 Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Is th ere a C all F or Heat at t he heat er? Is th e 220 VAC inver ter in t he cold .
18 ILL USTRA TED P ARTS LISTS Cold Wa ter Star t.
19 1-M 4-M 2-M 3-M CALL OUT DESCRIPTION HI DEL T A MVB F 7 1 7 1 1 0 F 7 1 7 1 1 0 L O R T N O C - Y S S A D R A O B C P C - 1 F 8 1 7 1 1 0 F 8 1 7 1 1 0 R E M R O F S N A R T C - 2 3-C POWER SUPPL Y.
20 Cold Wa ter Run.
21 CALL OUT B V M A T L E D I H N O I T P I R C S E D F 7 1 7 1 1 0 F 7 1 7 1 1 0 L O R T N O C - Y S S A D R A O B C P C - 1 F 0 2 7 1 1 0 F 0 2 7 1 1 0 C A V 4 2 T D P D - Y A L E R C - 2 F 9 3 0 9 .
ww w .raypak.c om Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (805) 278-5468 Raypak Canada Limited, 2805 Slough St., Mississauga, Ontario, Canada L4T 1G2 (905) 677-7999 Fax (905) 677-8036 Litho in U.
デバイスRaypak 241275の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Raypak 241275をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはRaypak 241275の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Raypak 241275の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Raypak 241275で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Raypak 241275を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はRaypak 241275の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Raypak 241275に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちRaypak 241275デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。